Loading…
Loading…
Variable Name: nDamping
Variable ID: 0x40CA
Variable Label: Damping
Variable Help: Coefficient to increase the valve response for some applications. A value of 0 gives no Damping. 0 to 250 seconds is for slow down in both directions. -1 to -250 is for slow down in OPEN direction ONLY. -1001 to -1250 is for slow down in CLOSE direction ONLY.
Variable Handling: R/W
Variable Class: Dynamic | Correction
Variable Size: 2
Variable DataType: Integer
Variable Display Format: |en|5d
Variable Edit Format: |en|5d
Variable Unit:
Variable Max: 1001
Variable Min: 1250
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
216 | 410B | cmdReadPidData |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
173 | 40F3 | cmdWritePidData |