Loading…

Variable Name: fTSLimit

Variable ID: 0x4095

Variable Label: Tight Shutoff Value

Variable Help: Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Value between -1% and 20% and not to include.

Variable Handling: R/W

Variable Class: Correction

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.1f

Variable Edit Format: |en|4.1f

Variable Unit:

Variable Max: 19.9

Variable Min: 0.99

Variable Read Command List

Command Number Command ID Command Name
210 4107 cmdReadConfiguration

Variable Write Command List

Command Number Command ID Command Name
165 40EC cmdWriteConfiguration