Variable Name: bConfigFlags1_TightShutoff
Variable ID: 0x4094
Variable Label: Tight Shutoff
Variable Help: Tight Shutoff Limit- Threshold for tight shutoff: when selected, if the input signal would position the valve below the tight shutoff value, full supply or atmosphere pressure is supplied to the actuator to close the valve with full seating force. Set the TS value between -1% and 20%, then enable the TS function.
Variable Handling: R/W
Variable Class: Correction
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | Disabled |
0x0001 | Enabled |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
210 | 4107 | cmdReadConfiguration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
165 | 40EC | cmdWriteConfiguration |