Loading…
Loading…
Variable Name: tvl_auto_calib_status
Variable ID: 0x40A7
Variable Label: Last AutoCal Status
Variable Help:
Variable Handling: R
Variable Class: Device
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | No AutoCal status |
0x0001 | AutoCal was successful |
0x0002 | Power failure occured during Auto Calibration. |
0x0003 | User aborted AutoCal |
0x0004 | Did not reach 5 % travel. |
0x0005 | Did not reach 95 % travel. |
0x0006 | Auto Calibration did not complete within the time limit. |
0x0007 | Insufficient travel. |
0x0008 | Drive signal exceed low limit; check supply pressure. |
0x0009 | Drive signal exceed high limit; check supply pressure. |
0x000A | Travel Sensor Out of Range. Make sure magnet array is properly installed. |
0x000B | Travel Sensor Out of Range. Make sure magnet array is properly installed. |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
129 | 41FB | fcmd_129 |
Variable Write Command List
None