Loading…
Loading…
Variable Name: SPV_SimulateDiagCode_1
Variable ID: 0x4235
Variable Label: Sim. diag. event
Variable Help:
Variable Handling: R/W
Variable Class:
Variable Size: 4
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x80EC | Off |
0x1D40000 | 004 Sensor defective |
0x1D00000 | 022 Temperature sensor defective |
0x1D10000 | 046 Sensor limit exceeded |
0x220000 | 062 Sensor connection defective |
0xE70000 | 082 Data storage |
0xA00000 | 083 Memory content |
0x1D70000 | 114 Sensor leaky |
0x1C40000 | 122 Temperature sensor defective |
0x670000 | 242 Software incompatible |
0x6B0000 | 252 Modules incompatible |
0x950000 | 261 Electronic modules |
0x7E0000 | 262 Module connection |
0x780000 | 270 Main electronic failure |
0x7D0000 | 271 Main electronic failure |
0x790000 | 272 Main electronic failure |
0xE50000 | 273 Main electronic failure |
0x7A0000 | 275 I/O module failure |
0x7B0000 | 276 I/O module failure |
0x1ED0000 | 277 Electronics defective |
0x620000 | 282 Data storage |
0x9E0000 | 283 Memory content |
0x1EE0000 | 302 Device verification active |
0xE10000 | 311 Electronic failure |
0x1EA0000 | 350 Pre-amplifier defective |
0x1E90000 | 351 Pre-amplifier defective |
0x1D90000 | 370 Pre-amplifier defective |
0x1DF0000 | 371 Temperature sensor defective |
0x8B0000 | 410 Data transfer |
0x680000 | 411 Up-/download active |
0x40000 | 431 Trim 1 |
0x600000 | 437 Configuration incompatible |
0x6A0000 | 438 Dataset |
0x990000 | 441 Current output 1 |
0x940000 | 453 Flow override |
0x900000 | 484 Simulation failure mode |
0x930000 | 485 Simulation measured variable |
0xE0000 | 491 Simulation current output 1 |
0x15E0000 | 495 Simulation diagnostic event |
0x1E70000 | 538 Flow computer configuration incorrect |
0x1E50000 | 539 Flow computer configuration incorrect |
0x1E80000 | 540 Flow computer configuration incorrect |
0x1E40000 | 570 Inverted delta heat |
0xCB0000 | 801 Supply voltage too low |
0xAD0000 | 803 Current loop |
0x1DE0000 | 828 Ambient temperature too low |
0x1DD0000 | 829 Ambient temperature too high |
0xC30000 | 832 Electronic temperature too high |
0xC10000 | 833 Electronic temperature too low |
0xC50000 | 834 Process temperature too high |
0xC60000 | 835 Process temperature too low |
0x540000 | 841 Flow velocity too high |
0x910000 | 842 Process limit |
0x1D80000 | 844 Sensor range exceeded |
0x920000 | 862 Partly filled pipe |
0x1B90000 | 870 Measuring inaccuracy increased |
0x1E10000 | 871 Near steam saturation limit |
0x1E20000 | 872 Wet steam detected |
0x1E30000 | 873 No steam detected |
0x1EF0000 | 874 Wet steam detection uncertain |
0x310000 | 882 Input signal |
0x1E00000 | 945 Sensor range exceeded |
0x1D20000 | 946 Vibration detected |
0x1D50000 | 947 Vibration exceeded |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
173 | 4430 | read_index_parameter_173 |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
178 | 442E | write_index_parameter_178 |