Variable Name: PFS_FrequencyMinValue_1

Variable ID: 0x416F

Variable Label: Measuring value at minimum frequency

Variable Help: Enter lower range value for the measured value range. Additional information: - Depending on the setting selected for the "Measuring mode" parameter, the value specified for this parameter and the "Measuring value at maximum frequency" parameter must have the same algebraic sign or not. - As a rule, the lower range value is scaled to be lower than the upper range value. As a result, the behavior of the frequency output is proportional to the process variable assigned. If the lower range value is scaled to be higher than the upper range value, then the behavior of the frequency output will be inversely proportional to the process variable assigend.

Variable Handling: R/W

Variable Class:

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.4f

Variable Edit Format: |en|.4f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
173 42E8 read_index_parameter_173

Variable Write Command List

Command Number Command ID Command Name
178 42E6 write_index_parameter_178