Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
131 4021 readSensorInformation
136 4028 readDate
139 402A readCfgLimits
153 402B readCalInterval
140 406C readRangeReference
151 406D readResolutionInfo
154 4070 readAlarmDeadBands
155 4074 readAlarmLevels
220 4030 readSensorLock
221 407E read_rs485_info
146 1550 readErrorSignalCfg
144 152B readMaintSignalConfig
145 1531 readWarningSignalConfig
128 1418 read_PV_in_units
128 1418 read_PV_in_units
128 1418 read_PV_in_units
130 141E read_transmitter_info
132 1426 read_measure_gas_n_unit
133 1430 read_sensor_analytical_data
141 1437 read_human_interface_parameters
143 143C read_analog_warning_state
184 1455 ctrl_calibration_calculated
184 1455 ctrl_calibration_calculated
193 147F read_status_history
201 1488 control_measurement_gas_config
201 1488 control_measurement_gas_config
201 1488 control_measurement_gas_config
203 1492 control_calibration_gas_config
203 1492 control_calibration_gas_config
203 1492 control_calibration_gas_config
211 1497 read_gas_information
211 1497 read_gas_information
211 1497 read_gas_information
211 1497 read_gas_information
212 1499 read_unit_information
212 1499 read_unit_information
212 1499 read_unit_information
213 149B read_range_info
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status
48 0FCE read_additional_transmitter_status

Variable Write Command List

None