Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label: Device status

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
160 4080 rd_gas_name
170 4081 rd_calgas_name
167 408D rd_gas2lel_ppm
177 4097 rd_cal2lel_ppm
168 409E rd_gas2lel_lim_ppm
178 40A5 rd_cal2lel_lim_ppm
175 40B1 rd_calkonz_lim_u
174 40B2 rd_calkonz_u
213 40B5 rd_range_limits_u
164 40B6 rd_range_u
162 40BF rd_gasunit
172 40C0 rd_calunit_rdc
144 40D3 rd_capt_ppm
150 40D4 rd_capt_ppm_rdc
149 40DC rd_capt_lim_ppm
146 40DD rd_kat
136 40DF rd_fR
142 40EC rd_zonen0
145 40ED rd_zonen1
141 40F1 rd_analog
237 40F7 rd_SILlock
128 40F8 read_mw
132 40F9 cmd132
130 141E read_transmitter_info
133 40FA cmd133
131 40FB cmd131
137 4102 rd_gas_ident
138 4109 rd_Cal_ident
211 4117 rd_gasinfo
212 411B rd_unitinfo
184 4127 calib
148 4170 rd_Spec_Comm
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
48 1043 read_additional_device_status

Variable Write Command List

None