Variable Name: IsDI1ForCalStateGated
Variable ID: 0x403E
Variable Label: Calibration gating
Variable Help: This point specifies the calibration gating for digital input 1 (DI1) when it is configured (via IsDI1UsedForCal) for use in synchronizing a calibration. When FALSE, the calibration is started/stopped via an inactive->active edge; when TRUE, the calibration is started via an inactive->active state change and stopped via an active->inactive state change. The active edge/state is specified via the IsDI1ForCalActiveLow data point.
Variable Handling: R/W
Variable Class:
Variable Size: 1
Variable DataType: Enum
Variable Enum Value | Variable Enum Text |
---|---|
0x0000 | DI1 Cal Edge Gated |
0x0001 | DI1 Cal State Gated |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
143 | 40C7 | ReadDigitalInputConfiguration |
Variable Write Command List
Command Number | Command ID | Command Name |
---|---|---|
142 | 40C6 | WriteDigitalInputConfiguration |