Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
131 408E read_date_time
133 4090 read_dig_io_states
136 4093 read_system_parameter
138 4095 read_number_of_detectors
140 4097 read_detector_id
142 4099 read_detector_address
144 409B read_detector_setup
145 409C read_detector_raw_data
146 409D read_cps_measured
147 409E read_test_data
150 40A1 read_error_current_setup
152 40A3 read_dig_out_id
153 4154 read_polling_address
155 40A5 read_dig_out_setup
157 40A7 read_interference_detect_setup
160 40AA read_damping_data
162 40AC read_cps_limits
165 40AF read_dig_in_id
167 40B1 read_dig_in_setup
168 40B2 read_aux_dynamic_variables
173 40B6 read_calibration_data
177 40BA read_adjust_curve
183 40BF read_rr_status
186 4155 read_interference_detect_delay
188 40C1 read_damping_sigma
191 40C4 read_plateau_data
193 4157 read_calibration_variables
194 4158 read_id_variables_part1
197 40C7 read_analog_input_setup
198 40C8 read_analog_input_values
202 40CC read_tc_setup
204 40CE read_suspension_setup
206 40D0 read_massflow_setup
208 40D2 read_meas_mode
212 415C read_error_current_setup_2
214 415E read_PA_address
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
14 00B6 read_pv_sensor_info
15 00B7 read_pv_output_info
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status
60 0FE5 read_analog_output_and_percent_of_range
63 0FED read_analog_output_information

Variable Write Command List

None