Loading…

Variable Name: var_ds_fIoFactor

Variable ID: 0x404E

Variable Label: Io Factor

Variable Help: Io Factor Defines the threshold where the interference radiation detection responds. With the default value of 1.5, the threshold is 1.5 times the active empty count rate and is suitable for most applications. You can adjust the factor for the threshold yourself. Note that a value below 1.5 may trigger faulty switching caused by fluctuations in the measured values. Increasing the factor decreases the sensitivity. Increase the factor if false alarms are triggered by significant fluctuations in the measured values, for example, by agitator blades.

Variable Handling: R/W

Variable Class: Device

Variable Size: 4

Variable DataType: Float

Variable Display Format: |en|.1f

Variable Edit Format: |en|.1f

Variable Unit:

Variable Max:

Variable Min:

Variable Read Command List

Command Number Command ID Command Name
200 422B cmd_rd_radiation_interference

Variable Write Command List

Command Number Command ID Command Name
201 422C cmd_wr_radiation_interference