Variable Name: device_status
Variable ID: 0x0097
Variable Label:
Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process
Variable Handling: R/W
Variable Class: Dynamic | Diagnostic | HART
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Process applied to the primary variable is outside the operating limits of the field device |
0x0002 | Process applied to the non-primary variable is outside the operating limits of the field device |
0x0004 | Analog output 1 and its digital representation are outside the operating range limits, and not responding to input |
0x0008 | Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes |
0x0010 | Field device has more status available |
0x0020 | A reset or self test of the field device has occurred, or power has been removed and reapplied |
0x0040 | A modification has been made to the configuration of the field device |
0x0080 | Field device has malfunctioned due to a hardware error or failure |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
133 | 4089 | svp_read85_cmd |
135 | 408A | svp_read87_cmd |
138 | 408B | svp_read8a_cmd |
140 | 408C | svp_read8c_cmd |
142 | 408D | svp_read8e_cmd |
144 | 408E | svp_read90_cmd |
146 | 408F | svp_read92_cmd |
148 | 4090 | svp_read94_cmd |
150 | 4091 | svp_read96_cmd |
152 | 4092 | svp_read98_cmd |
154 | 4093 | svp_read9a_cmd |
156 | 4094 | svp_read9c_cmd |
158 | 4095 | svp_read9e_cmd |
164 | 4096 | svp_reada0_cmd |
192 | 40AD | svp_f_factory_num_cmd |
193 | 40AE | svp_f_readc1_cmd |
194 | 40AF | svp_f_readc2_cmd |
195 | 40B0 | svp_f_readc3_cmd |
196 | 40B1 | svp_f_readc4_cmd |
198 | 40B2 | svp_f_readc6_cmd |
200 | 40B3 | svp_f_readc8_cmd |
202 | 40B4 | svp_f_readca_cmd |
204 | 40B5 | svp_f_readcc_cmd |
206 | 40B6 | svp_f_readce_cmd |
0 | 00AE | read_unique_identifier |
1 | 00AF | read_pv |
2 | 00B0 | read_pv_current_and_percent_range |
3 | 00B1 | read_dynamic_variables_and_pv_current |
12 | 00B4 | read_message |
13 | 00B5 | read_tag_descriptor_date |
14 | 00B6 | read_pv_sensor_info |
15 | 00B7 | read_pv_output_info |
16 | 00B8 | read_final_assembly_number |
48 | 0FCE | read_additional_transmitter_status |
Variable Write Command List