Loading…

Variable Name: device_status

Variable ID: 0x0097

Variable Label:

Variable Help: Field Device Status- Data indicating that the Field Device has detected condition(s) in the Field Device relating to: its hardware / the validity of a variable / its operating status / an internal process

Variable Handling: R/W

Variable Class: Dynamic | Diagnostic | HART

Variable Size: 1

Variable DataType: BitEnum

Variable Enum Value Variable Enum Text
0x0001 Process applied to the primary variable is outside the operating limits of the field device
0x0002 Process applied to the non-primary variable is outside the operating limits of the field device
0x0004 Analog output 1 and its digital representation are outside the operating range limits, and not responding to input
0x0008 Analog output 1 and its digital representation are in fixed mode, and not responsive to input changes
0x0010 Field device has more status available
0x0020 A reset or self test of the field device has occurred, or power has been removed and reapplied
0x0040 A modification has been made to the configuration of the field device
0x0080 Field device has malfunctioned due to a hardware error or failure

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
131 400C read_actuator_information
133 400D read_PV_sensor_information
141 401B read_lever_zeropoint
143 4020 read_switch_code
146 4027 read_counter_values
151 4035 read_static_variables
153 403F read_alarm_range_values
191 4044 Get_SetpointMode
189 4047 ReadDigitalSetpoint
167 4048 read_valve_range_values
169 404C read_setpoint_cutoff
171 404F read_stoketimedata
173 4056 read_travel_range_values
175 405A read_alarm_mask
177 405D read_readback_range
180 406E read_control_data1
204 407A read_measering_task
193 407F GetDigitalInputFunction
195 4082 Get_ActuatorType
0 00AE read_unique_identifier
1 00AF read_pv
2 00B0 read_pv_current_and_percent_range
3 00B1 read_dynamic_variables_and_pv_current
12 00B4 read_message
13 00B5 read_tag_descriptor_date
16 00B8 read_final_assembly_number
48 0FCE read_additional_transmitter_status

Variable Write Command List