Loading…

Variable Name: transfer_function

Variable ID: 0x1F84

Variable Label: Transfer Function

Variable Help: Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation.

Variable Handling: R/W

Variable Class: InputBlock

Variable Size: 1

Variable DataType: Enum

Variable Enum Value Variable Enum Text
0x0000 Linear
0x0001 Square Root
0x0002 Square Root Third Power
0x0003 Square Root Fifth Power
0x0004 Linear Table 22pt
0x00F0 Bi-Directional Square Root
0x00F1 Cylindrical tank- fixed table
0x00F2 Spherical tank- fixed function

Variable Display Format:

Variable Edit Format:

Variable Unit:

Variable Max: N/A

Variable Min: N/A

Variable Read Command List

Command Number Command ID Command Name
15 00B7 read_pv_output_info

Variable Write Command List

Command Number Command ID Command Name
47 0FB4 write_pv_transfer_function