Variable Name: diagnosisElectronics
Variable ID: 0x4002
Variable Label: Electronics status
Variable Help: Electronics status of the device- The value represents the sum of the status bit values. Status bit values: 0x01 = Temperature sensor electronic failure, 0x02 = Memory failure, 0x04 = Max. number write cycles exceeded, 0x08 = Non vol. storage or check active, 0x10 = Device not calibrated. Example: 0x15 = 0x01 (Temperature sensor electronic failure) + 0x04 (Max. number write cycles exceeded) + 0x10 (Device not calibrated).
Variable Handling: R
Variable Class: Diagnostic | Device
Variable Size: 1
Variable DataType: BitEnum
Variable Enum Value | Variable Enum Text |
---|---|
0x0001 | Temp snsr electronic failure |
0x0002 | Memory failure |
0x0004 | Max number write cyc exceeded |
0x0008 | Non vol storage or check active |
0x0010 | Device not calibrated |
Variable Display Format:
Variable Edit Format:
Variable Unit:
Variable Max: N/A
Variable Min: N/A
Variable Read Command List
Command Number | Command ID | Command Name |
---|---|---|
48 | 0FCE | read_additional_transmitter_status |
Variable Write Command List
None