Method Name: RTD_Calibration

Method ID: 0x4233

Method Label: Calibrate RTDs

Method Help: Use this function to calibrate the probe RTDs for the temperature and flow measurements. The probe tip must be submerged in a constant temperature water bath. A separate accurate temperature reading device must be used to determine the actual water bath temperature. An inaccurate calibration temperature entry will result in performance that is out of specification or a non-functional unit.


  • {