Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
before_poll | 4000 | Before polling | msrc_UNKNOWN | Details | |
put_in_manual | 406A | Loop in manual | msrc_UNKNOWN | Details | |
back_to_normal | 406B | Back to normal | msrc_UNKNOWN | Details | |
read_max_min | 404A | Read max/min log | Reads the maximum and minimum logged values | msrc_UNKNOWN | Details |
reset_max_min | 404B | Reset max/min log | Resets the maximum and minimum logged values | msrc_UNKNOWN | Details |
write_protect_on | 404D | Write protect | Write protects the device, if correct password is entered | msrc_UNKNOWN | Details |
write_protect_off | 404E | Write enable | Write enables the device, if correct password is previously entered | msrc_UNKNOWN | Details |
set_new_password | 404F | New password | Sets a new password for write protection, if correct password is entered | msrc_UNKNOWN | Details |
enter_sensor_configuration | 4050 | Sensor config | Configures the sensor, sensor type, measurement type, CJC compensation etc. | msrc_UNKNOWN | Details |
enter_cable_resistance | 4052 | Enter value | Enter new value for cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor | msrc_UNKNOWN | Details |
measure_cable_resistance | 4053 | Measure value | Automaticly measures the cable resistance. If the device setup is RTD/Ohm 3 or 4 wire, cable resistance for sensor 1 is the expected max value for the total cable resistance in 2 wires. Otherwise it is the actual total cable resistance for the selected sensor | msrc_UNKNOWN | Details |
restore_configuration | 406C | restoring configuration | msrc_UNKNOWN | Details | |
broken_namur_down | 4062 | NAMUR down | Sets the broken sensor output value to 3.5 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
broken_namur_up | 4063 | NAMUR up | Sets the broken sensor output value to 23 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
shorted_namur_down | 4064 | NAMUR down | Sets the shorted sensor output value to 3.5 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
shorted_namur_up | 4065 | NAMUR up | Sets the shorted sensor output value to 23 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
set_output_limits_namur | 405F | Set limits = NAMUR | Sets the analog output limits to 3.8 mA and 20.5 mA acc. to NAMUR NE43 | msrc_UNKNOWN | Details |
override_dac_trim | 404C | Override D/A trim | Overrides any previously D/A trimming by restoring factory calibration values | msrc_UNKNOWN | Details |
chng_univ_rev_abort_mes | 4076 | msrc_UNKNOWN | Details | ||
change_univ_rev_method | 4075 | Chng universal rev | Chng universal rev- Change the universal command revision. | msrc_UNKNOWN | Details |
loop_test | 1002 | Тест петли | Тест петли - позволяет пользователю вручную управлять выбранным аналоговым выходом для установки нужного значения выхода | msrc_UNKNOWN | Details |
dac_trim | 1004 | Регулировка D/A | Цифровая-аналоговая регулировка - обеспечивает калибровку выбранного аналогового выхода, по внешнему образцовому прибору крайних рабочих точек аналогового выхода | msrc_UNKNOWN | Details |
scaled_dac_trim | 1005 | Регулировка D/A по масштабу | Цифровая-аналоговая регулировка по масштабу - обеспечивает калибровку аналогового выхода, по внешнему образцовому прибору крайних рабочих точек аналогового выхода | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | Выход из режима фикс. тока | Выход из режима фиксированного тока - выводит выбранный аналоговый выход из режима, в котором выход был зафиксирован в постоянное значение, и переводит выход в режим, в котором он соотвествует входным данным | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Отмена возврата в норм. сост. | msrc_UNKNOWN | Details | |
Name | ID | Label | Description | Type | Source |