Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
Refresh_History_table | 4001 | Refresh Event History | Displays a history of most recent diagnostic events. For each event, the time when the event occurred and the duration of the event are shown. The table of history events displays the most recent event at the top with successively preceding events in descending order. Use Set Clock (in transmitter) if actual Dates and Times are not shown. Last column displays s = seconds and h = hours. | msrc_UNKNOWN | Details |
HistReset_method | 4002 | Reset Event History | Clears entries in Event History and resets the run time to zero. | msrc_UNKNOWN | Details |
set_rtc_history_method | 4003 | Set Clock | Sets the Real-Time Clock in the device. | msrc_UNKNOWN | Details |
save_datalog_parameters_method | 40E6 | Save Data Log Params | msrc_UNKNOWN | Details | |
save_tank_profile_parameters_method | 40E7 | Save Tank Profile | msrc_UNKNOWN | Details | |
tank_profile_status_refresh_method | 40D4 | Refresh Tank Profile Status | Update status of Upper and Lower limit achievement. | msrc_UNKNOWN | Details |
read_tank_profile_method | 40D5 | Read Tank Profile | msrc_UNKNOWN | Details | |
RefreshEchoRejectionData_method | 46FD | Refresh Echo Data | Click to refresh Echo List and Graph. | msrc_UNKNOWN | Details |
zoom_echo_rejection_graph_method | 47D1 | Zoom | Allows user to zoom in and out of a specific portion of the Echo Curve. | msrc_UNKNOWN | Details |
refresh_echo_graph_method | 4705 | Refresh Echo Curve Graph | Click to refresh Echo Curve. | msrc_UNKNOWN | Details |
clear_curve1_method | 47D3 | clears Curve 1 | msrc_UNKNOWN | Details | |
clear_curve2_method | 47D4 | clears Curve 2 | msrc_UNKNOWN | Details | |
zoom_echo_graph_method | 4706 | Zoom Echo Curve Graph | Allows user to zoom in and out of a specific portion of the Echo Curve. | msrc_UNKNOWN | Details |
refresh_echo_history_graph_method | 471A | Refresh Echo History Graph | Click to refresh Echo Curve. | msrc_UNKNOWN | Details |
zoom_echo_history_graph_method | 471B | Zoom Echo History Graph | Allows user to zoom in and out of a specific portion of the Echo Curve. | msrc_UNKNOWN | Details |
refresh_curve1_method | 47D5 | Refresh Echo Curve Graph | Click to refresh Echo Curve. | msrc_UNKNOWN | Details |
refresh_curve2_method | 47D6 | Refresh Echo Curve Graph | Click to refresh Echo Curve. | msrc_UNKNOWN | Details |
NewRejectionCurve_method | 46F5 | New Rejection Curve | Echo Rejection cancels unwanted echoes by creating a new Echo Rejection curve. Multiple echoes may be offered. Choose the echo that represents the actual media location, closer echoes will be cancelled. Enter the correct echo number when prompted. For an empty vessel, enter '0'. If the correct location is not offered for a partially filled vessel, ensure that the tank dimensional information is correct. If the correct location is not listed, enter '0'. Enter the correct media location when prompted. For an empty vessel, accept the default value presented. | msrc_UNKNOWN | Details |
save_reference_echo_method | 4707 | Save Ref Echo Curve | Method to save a reference echo curve in the device. The reference echo curve will be retained until over-written by a new reference echo curve. | msrc_UNKNOWN | Details |
SelectFMETarget_method | 47D8 | Select FME Target | FME (First Moving Echo) is a Peak Detection algorithm designed to differentiate between a moving vs. stationary echo. It is particularly useful in applications that include large, mixing blades. The blades are difficult to cancel using Echo Rejection since they typically stop in different positions. | msrc_UNKNOWN | Details |
fme_select_abort | 47D9 | fme_select_abort | msrc_UNKNOWN | Details | |
refresh_echo_history_method | 471D | Refresh Echo History Log | Method to re-read the echo history summary. | msrc_UNKNOWN | Details |
delete_echo_history_method | 471F | Delete Echo History Log | Allows the History information to be cleared and reset. | msrc_UNKNOWN | Details |
set_rtc_echo_history_method | 4720 | Set Clock | Sets the Real-Time Clock in the device. | msrc_UNKNOWN | Details |
ModifyRejectionCurve_method | 46F6 | Modify Rejection Curve | Echo Rejection procedure for customizing a Standard Echo Rejection curve. This is particularly useful when rejecting a mixing blade that can stop in a different location yielding a slightly different echo. The goal is to make the Custom Echo Rejection Curve just large enough to surround these possibilities. It can be modified more than once. After making all desired changes to the custom echo rejection curve, select the "Apply/Save" option to put the changes into effect. | msrc_UNKNOWN | Details |
change_to_std_echo_rej | 47E0 | Change to Standard Echo Rejection | msrc_UNKNOWN | Details | |
apply_custom_curve | 47E1 | Apply Custom Curve | msrc_UNKNOWN | Details | |
release_read_sema | 47D2 | Release Read Sema | msrc_UNKNOWN | Details | |
reread_live_echo_list | 47DA | Custom Echo Rejection Curve Modification Cleanup | msrc_UNKNOWN | Details | |
refresh_echo_list_method | 47F5 | msrc_UNKNOWN | Details | ||
sensor_input_method | 4A53 | Sensor Input | msrc_UNKNOWN | Details | |
transmitter_dac_trim_method | 4A70 | Adjust Analog Output | Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output. | msrc_UNKNOWN | Details |
read_dac_trim_values_method | 4AB9 | Read DAC trim values | Reads the values for DAC trim | msrc_UNKNOWN | Details |
TempReset_method | 4A84 | Reset Max/Min Temps | Reset the maximum and minimum temperatures measured in the electronics compartment to the present temperature. | msrc_UNKNOWN | Details |
SZAlarmReset_method | 4A6F | Reset SZ Alarm | Clear a latched Safety Zone Alarm | msrc_UNKNOWN | Details |
TotalizerReset_method | 4A63 | Reset R Totalizer | Reset the flow and time for the resettable totalizer. | msrc_UNKNOWN | Details |
FactoryReset_method | 4A71 | Factory Reset | Reset the device to factory default settings. If using a HART host, disconnect and then reconnect the host after performing the reset. | msrc_UNKNOWN | Details |
ConfigReset_method | 4A6E | Reset Parameters | Reset the device to factory calibrated settings. If using a HART host, disconnect and then reconnect the host after performing the reset. | msrc_UNKNOWN | Details |
reset_config_changed_method | 4A76 | Reset Config Changed | Resets the Configuration Changed bit in the Device Status | msrc_UNKNOWN | Details |
set_rtc_method | 40D1 | Set Clock | Sets the Real-Time Clock in the device. | msrc_UNKNOWN | Details |
clear_time_set | 4ABA | msrc_UNKNOWN | Details | ||
reset_NE107mapping | 4A80 | Reset NE 107 Mapping | Sets the NE 107 mapping to default values. | msrc_UNKNOWN | Details |
warning_message | 1017 | Set loop to manual | msrc_UNKNOWN | Details | |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
leave_fixed_current_mode | 1003 | Leaving fixed current mode | Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input. | msrc_UNKNOWN | Details |
trim_warning | 1081 | Trim warning | msrc_UNKNOWN | Details | |
transmitter_loop_test | 1023 | Analog Output Test | Allows the User to manually manipulate the Analog Output to a selected constant output value. | msrc_UNKNOWN | Details |
setup_wizard | 4A3C | Setup Wizard | msrc_UNKNOWN | Details | |
save_all_values | 4ABD | Saves all values | Saves all values from Setup Wizard values | msrc_UNKNOWN | Details |
optimization_wizard | 4ACA | Optimization Wizard | msrc_UNKNOWN | Details | |
Name | ID | Label | Description | Type | Source |