Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
methodReadSlot | 40CD | Select the slot | To load the tuning parameters stored in the specific slot | msrc_UNKNOWN | Details |
post_method_fill_100 | 410A | fill | msrc_UNKNOWN | Details | |
methodShowFirmwareVersion | 410B | Firmware Version | Display the firmware version. | msrc_UNKNOWN | Details |
methodChangeMode | 407E | Change Mode | Change mode: Changes the mode to Normal Mode, Manual Mode, or Setup Mode. Normal Mode: The position setpoint follows the input signal. Always return to Normal Mode to return to Control by the Control System. Manual Mode: The position setpoint remains at the last position prior to entering Manual Mode. Position setpoint may adjusted with the local pushbuttons or by HART commands. Setup Mode: The position setpoint remains at the last position prior to entering Setup Mode. Use this mode to change configuration and calibration information. | msrc_UNKNOWN | Details |
methodFindStops | 4098 | Find Stops | Run automatic find stops will establish the calibration position of the valve at actuator pressure vented and at full supply pressure. | msrc_UNKNOWN | Details |
methodAutoTune | 409C | Autotune | Run PID Autotune will automatically find best dynamic parameters for responsive valve positioning. Always isolate the valve from the process. The valve will move full open and full closed. The valve will continuously change position for about 5 minutes. To SVi1000 device, this operation need the device should be set PID selector to slot 0/ATO or slot 8/ATC | msrc_UNKNOWN | Details |
methodSetupWizard | 407F | Setup Wizard | The setup wizard will guide you through basic steps to setup the positioner on an actuator. You may skip this wizard if the valve and positioner have been factory configured and calibrated. Always isolate the valve from the process. The wizard allows setting Air Action. The valve move full open and full closed. You will be prompted if mode must be changed. The steps are in the following order: 1. Run Find Stops, to set 0% to the valve closed position and to set 100% to full opened position. 2. Run Auto Tune to determine best dynamic parameters for position control. 3. Reset Basic Configuration and Calibration to Factory Defaults. | msrc_UNKNOWN | Details |
methodFactoryConfiguration | 40A2 | Reset Basic Config and Cal To Defaults | The Reset to Factory Default will set the following list of configuration and calibration parameters to defaults: The PID tunning parameters in slot 0 are set to defaults; Input current range is set to 4 to 20 mA; Open stop adjustment is set to 100%; Position error parameters are reset and disabled; Bumpless transfer is disabled; Position limits are disabled; Position rate limits are disabled; Tight shutoff is set to 0 and enabled; Characterization is set to linear; | msrc_UNKNOWN | Details |
methodReadFaults | 40A4 | Current Faults | Read the device's current faults. | msrc_UNKNOWN | Details |
methodReadClearFaults | 4118 | Read/Clear Faults | Read the device's current faults. Optionally, the fault status may also be cleared. | msrc_UNKNOWN | Details |
methodClearFaults | 40A5 | Clear Current Faults | Clear the current device status/faults | msrc_UNKNOWN | Details |
methodReadHistoricFaults | 40A6 | Historical Faults | Read the device's historical faults. | msrc_UNKNOWN | Details |
methodClearHistoricFaults | 40A7 | Clear All Faults | Clear the historic and current device faults/status. | msrc_UNKNOWN | Details |
methodReadDeviceVariables | 4086 | Device Variables | Read the current device variables. | msrc_UNKNOWN | Details |
methodManualSetpoint | 40A0 | Set Position | Set manual valve setpoint in % or set the position by equivalent input current to simulate non-linear characterization and limits. | msrc_UNKNOWN | Details |
methodFullyOpen | 409E | Full Open | Fully Open valve | msrc_UNKNOWN | Details |
methodFullyClose | 409F | Full Closed | Fully Close Valve | msrc_UNKNOWN | Details |
methodConfigureWizard | 411B | Configure Wizard | Change configuration of Tight shutoff. | msrc_UNKNOWN | Details |
methodCharacterization | 40FA | Custom / Standard Characterization | Control valves are often characterized to give a specific relationship between flow capacity (Cv) and percent opening of the valve. The valve can be characterized with special purpose trim or with the SVi1000 positioner. Selecting Custom Configuration displays an additional screen where the user can enter a custom characterization curve to fit his/her needs. The curve can have up to 9 points and points in between are linearly interpolated. | msrc_UNKNOWN | Details |
methodManualStop | 4099 | Manual Stops | This method is used to set manual stops. | msrc_UNKNOWN | Details |
methodOpenStopAdj | 409B | Open Stop Adjustment | Open stop adjustment; Allows to adjust travel to less than mechanical limits. Must be between 60% and 100% of mechanical travel set with Find Stops. | msrc_UNKNOWN | Details |
methodTuning | 409D | Manual Tuning | The user can set tuning PID parameters for slot 0, even though the current selector was selected for the other slot. To SVi1000 device, The only slot 0 PID parameters can be updated. | msrc_UNKNOWN | Details |
restore_original_PIDs | 411D | abort restore | msrc_UNKNOWN | Details | |
methodSetIPCount | 40C5 | Set I/P Output | Set IP Value. A value of 0 resets the device to allow the control task to set the I/P (changing modes or a reset also switches back to normal control modes). | msrc_UNKNOWN | Details |
methodCalibSignal | 40A3 | Input crnt snsr. | To calibrate or to check the 4-20mA current sensor. | msrc_UNKNOWN | Details |
methodResetCalibrationData | 408E | Reset Cal Factory Defaults | Reset Calibration Data: This will restore all sensor calibration data to factory defaults. If calibrations have been performed they will be lost! | msrc_UNKNOWN | Details |
methodResetContinuous | 40C2 | Reset Historian | Reset valve historian data (stroke count, cycle count, time open, time closed and time near closed ) to 0. The previous data is lost and must be recorded to be used later. | msrc_UNKNOWN | Details |
methodReset | 4085 | Reset SVi1000 | This function performs a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory. | msrc_UNKNOWN | Details |
range_error_warning | 412A | Range error warning | msrc_UNKNOWN | Details | |
methodInterruptProcessNoModeChange | 4110 | Stop Procedure | msrc_UNKNOWN | Details | |
methodRestoreAONormal | 412B | msrc_UNKNOWN | Details | ||
methodSetAnalogOutput | 4107 | Set Analog Output | User can set a fixed analog output of the position retransmitter.This is used only for checking loop wiring. Select Finished to return to position measurement function. | msrc_UNKNOWN | Details |
methodChangeOutputRange | 4108 | Re-transmitter Range | User can enter the upper and lower range values of valve position corresponding to output current 4 and 20 mA. The values typically are 0 and 100 %. | msrc_UNKNOWN | Details |
method_serial_number | 40F0 | Read Device S/N | Read device and terminal board serial number. | msrc_UNKNOWN | Details |
save_position_limits_value | 414C | save current parameters | save current parameters | msrc_UNKNOWN | Details |
set_position_limits | 40FF | Set Position Limits | Set the valve position low/high limits | msrc_UNKNOWN | Details |
pos_limit_check_method | 414D | Check signal range | Check signal range. | msrc_UNKNOWN | Details |
save_signal_range_value | 415F | save current parameters | save current parameters | msrc_UNKNOWN | Details |
signal_range_check_method | 4160 | Check signal range | Check signal range. | msrc_UNKNOWN | Details |
set_signal_range | 4097 | Set the signal range | Set the low/high input signal | msrc_UNKNOWN | Details |
mthdReadCustomCharacterizationData | 41BC | Read Custom Characterization Data | Select characterization. If Custom is selected then continue to set custom points. | msrc_UNKNOWN | Details |
methodCurrentMode | 4216 | What is Current Mode? | What is Current Mode? - To get the current mode of this device | msrc_UNKNOWN | Details |
mthdCheckCharacterizationData | 41BD | Edit | Control valves are often characterized to give a specific relationship between flow capacity (Cv) and percent opening of the valve. The valve can be characterized with special purpose trim or with the SVi1000 positioner. Selecting Custom Configuration displays an additional screen where the user can enter a custom characterization curve to fit his/her needs. The curve can have up to 9 points and points in between are linearly interpolated. | msrc_UNKNOWN | Details |