Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
post_method_fill_100 | 4128 | fill | msrc_UNKNOWN | Details | |
methodShowFirmwareVersion | 407F | Firmware Version | Display the firmware version. | msrc_UNKNOWN | Details |
methodChangeMode | 4006 | Change Mode | Change mode: Changes the mode to Normal Mode, Manual Mode, or Setup Mode. Normal Mode: The position setpoint follows the input signal. Always return to Normal Mode to return to Control by the Control System. Manual Mode: The position setpoint remains at the last position prior to entering Manual Mode. Position setpoint may adjusted with the local pushbuttons or by HART commands. Setup Mode: The position setpoint remains at the last position prior to entering Setup Mode. Use this mode to change configuration and calibration information. | msrc_UNKNOWN | Details |
methodFindStops | 4023 | Find Stops | Run automatic find stops will establish the calibration position of the valve at actuator pressure vented and at full supply pressure. | msrc_UNKNOWN | Details |
methodAutoTune | 4026 | Autotune | Run PID Autotune will automatically find best dynamic parameters for responsive valve positioning. Always isolate the valve from the process. The valve will move full open and full closed. The valve will continuously change position for about 5 minutes. | msrc_UNKNOWN | Details |
methodSetupWizard | 4007 | Setup Wizard | The setup wizard will guide you through basic steps to setup the positioner on an actuator. You may skip this wizard if the valve and positioner have been factory configured and calibrated. Always isolate the valve from the process. The wizard allows setting Air Action. The valve move full open and full closed. You will be prompted if mode must be changed. The steps are in the following order: 1. Set Air action to Air to Open or Air to Close; 2. Run Find Stops, to set 0% to the valve closed position and to set 100% to full opened position. 3. Run Auto Tune to determine best dynamic parameters for position control. 4. Reset Basic Configuration and Calibration to Factory Defaults. | msrc_UNKNOWN | Details |
methodFactoryConfiguration | 402B | Reset Basic Config and Cal To Defaults | The Reset to Factory Default will set the following list of configuration and calibration parameters to defaults: Air Action is set to ATO; All PID tuning parameters are set to defaults; Input current range is set to 4 to 20 mA; Open stop adjustment is set to 100%; Position error parameters are reset and disabled; Bumpless transfer is disabled; Position limits are disabled; Tight shutoff is set to 0.5% and enabled; Characterization is set to linear; Pressure units and language are set to psi and English; Button Locks = None; Controller = None; | msrc_UNKNOWN | Details |
methodReadFaults | 4031 | Current Faults | Read the device's current faults. | msrc_UNKNOWN | Details |
methodReadClearFaults | 413B | Read/Clear Faults | Read the device's current faults. Optionally, the fault status may also be cleared. | msrc_UNKNOWN | Details |
methodClearFaults | 4032 | Clear Current Faults | Clear the current device status/faults | msrc_UNKNOWN | Details |
methodReadHistoricFaults | 4033 | Historical Faults | Read the device's historical faults. | msrc_UNKNOWN | Details |
methodClearHistoricFaults | 4034 | Clear All Faults | Clear the historic and current device faults/status. | msrc_UNKNOWN | Details |
methodManualSetpoint | 402A | Set Position | Set manual valve setpoint in % or set the position by equivalent input current to imulate non-linear characterization and limits. | msrc_UNKNOWN | Details |
methodFullyOpen | 4028 | Full Open | Fully Open valve | msrc_UNKNOWN | Details |
methodFullyClose | 4029 | Full Closed | Fully Close Valve | msrc_UNKNOWN | Details |
methodConfigureWizard | 402C | Configure Wizard | Change configuration of Limit Override, Tight shutoff, Pressure units, Language, Button Locks, Air Action, and Near Closed Value. Limit Overrideallows Find Stops, Autotune and Diagnostics to override position limits. | msrc_UNKNOWN | Details |
methodCharacterization | 4088 | Custom / Standard Characterization | Control valves are often characterized to give a specific relationship between flow capacity (Cv) and percent opening of the valve. The valve can be characterized with special purpose trim or with the SVI2AP positioner. Selecting Custom Configuration displays an additional screen where the user can enter a custom characterization curve to fit his/her needs. The curve can have up to 9 points and points in between are linearly interpolated. | msrc_UNKNOWN | Details |
methodReadDeviceVariables | 400F | Device Variables | Read the current device variables. | msrc_UNKNOWN | Details |
methodRestoreAONormal | 413E | msrc_UNKNOWN | Details | ||
methodSetAnalogOutput | 4021 | Set Analog Output | User can set a fixed analog output of the position retransmitter.This is used only for checking loop wiring. Select Finished to return to position measurement function. | msrc_UNKNOWN | Details |
methodChangeOutputRange | 4022 | Re-transmitter Range | User can enter the upper and lower range values of valve position corresponding to output current 4 and 20 mA. The values typically are 0 and 100 %. | msrc_UNKNOWN | Details |
methodManualStop | 4025 | Manual Stops | This method is used to set manual stops. | msrc_UNKNOWN | Details |
methodOpenStopAdj | 4024 | Open Stop Adjustment | Open stop adjustment; Allows to adjust travel to less than mechanical limits. Must be between 60% and 100% of mechanical travel set with Find Stops. | msrc_UNKNOWN | Details |
methodTuning | 4027 | Manual Tuning | The user can set tuning PID coefficients. | msrc_UNKNOWN | Details |
methodStrokeTime | 406B | Stroke Time | set stroke time. Stroke time is used to limit rate of change of travel. Stroke time is expressed as sec/100% travel | msrc_UNKNOWN | Details |
methodSetIPCount | 4060 | Set I/P Output | set I/P output. | msrc_UNKNOWN | Details |
methodCalibSignal | 402F | Input crnt snsr. | To calibrate or to check the 4-20mA current sensor. | msrc_UNKNOWN | Details |
methodCalibPressure | 4030 | Pressure Sensor | This operation will change zero calibration of all available pressure sensors . | msrc_UNKNOWN | Details |
methodReadPressures | 4019 | Read Pressures | To read pressures. | msrc_UNKNOWN | Details |
methodResetCalibrationData | 4018 | Reset Cal Factory Defaults | Reset Calibration Data: This will restore all sensor calibration data to factory defaults. If calibrations have been performed they will be lost! | msrc_UNKNOWN | Details |
methodPerformDiagnostics | 401C | Run Diagnostics | Perform valve signature and valve functional analysis. Displays the diagnostic test results. | msrc_UNKNOWN | Details |
methodResetContinuous | 4049 | Reset Historian | Reset valve historian data (stroke count, cycle count, time open, time closed and time near closed ) to 0. The previous data is lost and must be recorded to be used later. | msrc_UNKNOWN | Details |
methodReset | 400E | Reset SVI II AP | This function performs a master reset to the device, causing it to go through its startup routine and re-initializing all of its operating parameters from non volatile memory. | msrc_UNKNOWN | Details |
methodInterruptProcessNoModeChange | 412D | Stop Procedure | msrc_UNKNOWN | Details | |
methodDisableSwitchPositionLimits | 414C | disble the fswitch1value, and fswitch2value | msrc_UNKNOWN | Details | |
TS_limit_check_method | 415F | Tight Shutoff Limit Check | msrc_UNKNOWN | Details | |
pos_limit_check_method | 4160 | Position Limit Check | msrc_UNKNOWN | Details | |
Transfer_Time_check_method | 4161 | Transfer Time Check | msrc_UNKNOWN | Details | |
Near_Pos__check_method | 416B | Near Closed Value Check | msrc_UNKNOWN | Details | |
signal_range_check_method | 416F | Signal Range Check | msrc_UNKNOWN | Details | |
mthdReadCustomCharacterizationData | 41EC | Read Custom Characterization Data | Select characterization. If Custom is selected then continue to set custom points. | msrc_UNKNOWN | Details |
methodDoSaveSignature | 41F0 | Save | Save the signature data. | msrc_UNKNOWN | Details |
methodSaveSignature | 41F1 | Save | save the current signature data | msrc_UNKNOWN | Details |
methodBaselineSignature | 41F2 | Baseline | Baselined the saved signature data. | msrc_UNKNOWN | Details |
methodReadCurrentSignature | 41F3 | Current | Load the current signature curve. | msrc_UNKNOWN | Details |
methodReadSavedSignature | 41F5 | Saved | Load the saved signature curve. | msrc_UNKNOWN | Details |
methodReadBaselinedSignature | 41F6 | Baseline | Load the baselined signature curve. | msrc_UNKNOWN | Details |
methodTransSignatureData | 41F4 | Translate Signature Data | Load the signature data from device | msrc_UNKNOWN | Details |
methodCurrentMode | 426F | What is Current Mode? | What is Current Mode? - To get the current mode of this device | msrc_UNKNOWN | Details |
methodDiagnosDisplay | 4270 | Read Diagnostic Data | Displays CONTINUOUS DIAGNOSTIC DATA including number of full strokes the valve has made,the number of cycles (direction changes),the time the valve has spent open, the time the valve has been closed and the time the valve has spent throttling near the seat. | msrc_UNKNOWN | Details |
methodReadRawData | 4271 | Read Raw Data | Returns information from the SVI2AP that is useful to Masoneilan technicians for diagnostic purposes. The information includes the input current on the auxiliary input channel, the A/D values from the pressure, signal, and position measurements, the D/A value of the signal to the I/P, and the internal SVI2AP temperature. | msrc_UNKNOWN | Details |
mthdCheckCharacterizationData | 41EF | Edit | Control valves are often characterized to give a specific relationship between flow capacity (Cv) and percent opening of the valve. The valve can be characterized with special purpose trim or with the SVI2AP positioner. Selecting Custom Configuration displays an additional screen where the user can enter a custom characterization curve to fit his/her needs. The curve can have up to 9 points and points in between are linearly interpolated. | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |