Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
AbortLoopCal | 4030 | Aborts the loop calibration | msrc_UNKNOWN | Details | |
AO_Cal_method | 4032 | Analog Output | The analog output calibration is only available for positioners that have been supplied with the analog output module installed in the positioner. The Analog output is updated to match the stroke calibration of the positioner automatically every time a stroke calibration is done. This calibration is required if the 4-20 mA signal from the positioner needs to be spanned to something other than 4-20 mA. This option is also used to reverse the output if needed. Once setup properly, this calibration is usually not required for ongoing maintenance. | msrc_UNKNOWN | Details |
BurstCommandMethod | 403A | Command to Burst | Allows you to select the HART command to burst to the host. | msrc_UNKNOWN | Details |
BurstStateMethod | 403B | Burst Mode State | Allows you to enable/disable burst mode. | msrc_UNKNOWN | Details |
Change_Cycle_Limit | 403C | Change Cycle Limit | Changing the Cycle Limit allows you to control the Cycle Limit warning level. | msrc_UNKNOWN | Details |
ChangePressureUnits | 403F | Change Pressure Units | Select units of measure for actuator pressure measurement. | msrc_UNKNOWN | Details |
ClearMainArrays | 4042 | msrc_UNKNOWN | Details | ||
ClearViewArrays | 4043 | msrc_UNKNOWN | Details | ||
cmd_warn | 4044 | msrc_UNKNOWN | Details | ||
EC_Build_meth | 4046 | EC Build Date & Time | Display the date embedded code was built | msrc_UNKNOWN | Details |
GetCharacterization | 404D | msrc_UNKNOWN | Details | ||
Loop_Cal_meth | 404E | Analog Input | The Analog input calibration is updated to match the stroke calibration of the positioner automatically every time a stroke calibration is done. This calibration is required if the 4-20 mA signal to the positioner needs to be spanned to something other than 4-20 mA. Once setup properly this calibration is usually not required for ongoing maintenance. | msrc_UNKNOWN | Details |
Pressure_Cal_method | 4050 | Actuator/Stroke/Friction | Combined calibration that calibrates the internal pressure sensors of the positioner, the travel of the valve position (zero and span); and, if auto tuning is enabled, the gain values for the positioner are also calculated. Finally, a short sequence of movements allows the positioner to update a friction value for the valve assembly. Once set, the friction value will continue to update on it's own during normal operation. | msrc_UNKNOWN | Details |
process_warn | 4053 | The values in the following dialog affect the process control of the valve. | msrc_UNKNOWN | Details | |
Read_Register_meth | 4054 | Read Register | Allows you to read a single register value from positioner. (You will need a variable map to correctly select values to read). | msrc_UNKNOWN | Details |
Reset_Cycle_meth | 4055 | Reset Cycle Count | Use this selection to zero the Cycle Count value. | msrc_UNKNOWN | Details |
Reset_Error_History_meth | 4057 | Reset Event History | This procedure will reset the positioner error history log. | msrc_UNKNOWN | Details |
Reset_Travel_meth | 4059 | Reset Travel Count | Use this selection to zero the Valve Travel value. | msrc_UNKNOWN | Details |
Reset_Valve_Config_meth | 405B | Reset Device Config. | This procedure will set all values for the positioner to factory defaults. | msrc_UNKNOWN | Details |
SelectActSize | 405E | Select Actuator Info. | Allows you to select your actuator manufacturer, model/size. Information is used internally by Professional Diagnostic model for friction calculations. | msrc_UNKNOWN | Details |
SelectCmd33Vars | 4062 | Select Cmd. 33 variables | Allows you to select the individual variables to burst with HART command 33. | msrc_UNKNOWN | Details |
StartPartialStrokeTest | 4063 | Execute Partial Stroke Test | Initiates a partial stroke test. | msrc_UNKNOWN | Details |
Stroke_Cal_meth | 405D | Stroke | Combined calibration that calibrates the travel of the valve position (zero and span); and, if auto tuning is enabled, the gain values for the positioner are also calculated. | msrc_UNKNOWN | Details |
PlotFriction | 406C | msrc_UNKNOWN | Details | ||
POR_Act_Pressure | 406D | Post Read Pressure 1 | msrc_UNKNOWN | Details | |
ReadLongAsFloat | 406E | msrc_UNKNOWN | Details | ||
RunHRL | 406F | HRL Test... | msrc_UNKNOWN | Details | |
Write_Register_meth | 4070 | Write Register | Allows you to change internal variable values directly. (DANGEROUS). | msrc_UNKNOWN | Details |
KeepMask0 | 4115 | KeepMaskBits | msrc_UNKNOWN | Details | |
KeepMask1 | 4117 | KeepMaskBits | msrc_UNKNOWN | Details | |
KeepMask3 | 411A | KeepMaskBits | msrc_UNKNOWN | Details | |
KeepMask5 | 411D | KeepMaskBits | msrc_UNKNOWN | Details | |
KeepMask6 | 411F | KeepMaskBits | msrc_UNKNOWN | Details | |
Change_Travel_Limit | 41C8 | Change Travel Limit | Changing the Travel Limit allows you to control the Travel Limit warning level. | msrc_UNKNOWN | Details |
ChangeAirAction | 41CA | Change Air Action | Use to change air action from/to Air-to-Open/Air-to-Close. | msrc_UNKNOWN | Details |
ChangeCharType | 41CB | Change Characterization | Select characterization for stem movement. Choices are linear, equal %, and custom. | msrc_UNKNOWN | Details |
SelectPressureControl | 41D6 | Enable/Disable pressure control | Allows user to Enable/Disable pressure control. | msrc_UNKNOWN | Details |
ChangeSource | 41D7 | Change Command Source | Use to toggle command source Analog/Digital - Digital/Analog. | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |