Loading…
Loading…
Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
in_service_reminder_abort | 4311 | In Service Reminder | msrc_UNKNOWN | Details | |
inst_mode_method | 4312 | Change Instrument Mode | Select In Service or 'Out of Service' mode. The instrument adjusts its travel as the input changes, when it is In Service. Calibration and configuration require the instrument to be 'Out of Service'. | msrc_UNKNOWN | Details |
inst_mode_wireless_method | 4313 | Change Instrument Mode | Select In Service or 'Out of Service' mode. The instrument adjusts its travel as the input changes, when it is In Service. Calibration and configuration require the instrument to be 'Out of Service'. | msrc_UNKNOWN | Details |
config_protect_method | 4314 | Change Write Protection | Enable Protection to make calibration and setup parameters read only. Note: Removing protection requires pushing a button in the terminal box of the instrument. | msrc_UNKNOWN | Details |
config_protect_abort | 4315 | Change Write Protection | Enable Protection to make calibration and setup parameters read only. Note: Removing protection requires pushing a button in the terminal box of the instrument. | msrc_UNKNOWN | Details |
config_protect_wireless_method | 4316 | Change Write Protection | Enable Protection to make calibration and setup parameters read only. Note: Removing protection requires pushing a button in the terminal box of the instrument. | msrc_UNKNOWN | Details |
ctrl_mode_method | 4317 | Change Control Mode | Select the source for the instrument setpoint. Analog = 4-20 mA loop, Digital = HART link. | msrc_UNKNOWN | Details |
perform_tuner_method | 431A | Performance Tuner | msrc_UNKNOWN | Details | |
perform_tuner_no_tvl_abort | 431C | Performance Tuner | msrc_UNKNOWN | Details | |
perform_tuner_unstable_abort | 431D | Performance Tuner | msrc_UNKNOWN | Details | |
perform_tuner_abort | 431B | Performance Tuner aborted | msrc_UNKNOWN | Details | |
stabilize_opt_method | 431E | Stabilize/Optimize | Select Decrease Response if instrument is unstable. Select Increase Response if instrument is sluggish. Decrease Response reduces tuning by one set. Increase Response raises tuning by one set. | msrc_UNKNOWN | Details |
stabilize_opt_abort | 431F | Stabilize/Optimize | msrc_UNKNOWN | Details | |
SP_rate_open_post_edit | 423A | SP Rate Open post edit | msrc_UNKNOWN | Details | |
SP_rate_close_post_edit | 423B | SP Rate Close post edit | msrc_UNKNOWN | Details | |
restart_method | 4320 | Restart Processor | Follow the prompts to restart the instrument. | msrc_UNKNOWN | Details |
custom_char_method | 4321 | Custom Characterization Table | Enter the Set Point values and Travel Targets for each of the 21 Custom Characterization points. Set Point values are non-characterized travel. | msrc_UNKNOWN | Details |
run_time_method | 4322 | Days Powered Up | msrc_UNKNOWN | Details | |
calib_var_pre_edit | 40EA | Calibration Variable | msrc_UNKNOWN | Details | |
stroke_valve_method | 4323 | Stroke Valve | Select the desired method to stroke the valve. The ramp rate is set to 1.0% per second. Valid entries for the target are 0 to 100%. | msrc_UNKNOWN | Details |
stroke_valve_abort | 4324 | Stroke Valve aborted | msrc_UNKNOWN | Details | |
lag_time_method | 4325 | View/Edit Lag Time | msrc_UNKNOWN | Details | |
leadlag_method | 4326 | View/Edit Lead/Lag | msrc_UNKNOWN | Details | |
tvl_counts_method | 4327 | View Travel Counts | msrc_UNKNOWN | Details | |
actuator_selection_method | 4328 | Actuator Selection | msrc_UNKNOWN | Details | |
EDD_compatability_method | 4329 | Incompatible DD Revision | The DD Revision is not compatible with the firmware in this device. | msrc_UNKNOWN | Details |
instrument_time_method | 432A | Edit Instrument Time | Enter the date and time for the instrument. | msrc_UNKNOWN | Details |
alert_switch_source_method | 432B | Alert Switch Source | msrc_UNKNOWN | Details | |
cycle_counter_method | 432C | Edit Cycle Counts | msrc_UNKNOWN | Details | |
tvl_accum_method | 432D | Edit Travel Accumulator | msrc_UNKNOWN | Details | |
polling_address_method | 432E | Polling Address | The polling address for the instrument. If a point-to-point configuration is used, enter 0. If a multidrop configuration is used, enter 0 to 63. | msrc_UNKNOWN | Details |
switch_HART_version_method | 432F | Change to HART 5 | msrc_UNKNOWN | Details | |
dd_rev_method | 4330 | DD Information | Displays the Device Type, the Device Description Revision | msrc_UNKNOWN | Details |
press_sensor_calib_method | 4331 | Pressure Sensors | Follow the prompts to calibrate the instrument Pressure Sensors. | msrc_UNKNOWN | Details |
analog_in_calib_method | 4333 | Analog Input | Follow the prompts to calibrate the instrument analog input sensor. | msrc_UNKNOWN | Details |
analog_in_abort | 4334 | msrc_UNKNOWN | Details | ||
relay_adjust_method | 4335 | Relay Adjust | msrc_UNKNOWN | Details | |
tvl_sensor_adjust_method | 4337 | Travel Sensor Adjust | msrc_UNKNOWN | Details | |
tvl_sensor_adjust_abort_method | 4338 | Tvl Sensor Adjust Aborted. | msrc_UNKNOWN | Details | |
aux_term_mode_method | 4339 | Edit Auxiliary Terminal Action | msrc_UNKNOWN | Details | |
autotest_interval_method | 433A | Auto Test Interval | msrc_UNKNOWN | Details | |
zero_pwr_cond_method | 433B | Zero Power Condition | msrc_UNKNOWN | Details | |
PST_start_point_method | 433C | PST Start Point | msrc_UNKNOWN | Details | |
act_style_method | 433D | Actuator Style | msrc_UNKNOWN | Details | |
relay_type_method | 433E | Relay Type | msrc_UNKNOWN | Details | |
DVC_powerup_method | 433F | Change Device Power Up | msrc_UNKNOWN | Details | |
reset_valve_stuck_method | 4340 | Reset Valve Stuck Alert | Allows the user to reset the valve stuck alert that occured during a Partial Stroke Test. | msrc_UNKNOWN | Details |
PST_calib_method | 4341 | PST Calibration | msrc_UNKNOWN | Details | |
exit_with_PST_disabled_abort | 4343 | Disable PST | msrc_UNKNOWN | Details | |
set_PST_defaults_abort | 4344 | Exit PST Calibration | msrc_UNKNOWN | Details | |
end_point_control_enab_method | 4345 | Change EPPC Enable | msrc_UNKNOWN | Details | |
PST_enable_method | 4346 | Change PST Enable | Determines if the Partial Stroke test is enabled or disabled. In order for the Partial Stroke to be enabled, the Partial Stroke Start Point. (Initial Setup page) and the Travel Cutoffs (Travel Control page) must be set. | msrc_UNKNOWN | Details |
partial_stroke_vars_method | 4347 | PST Variables | View or Edit the Max Travel Movement, the Test Speed, and the Pause Time for the Partial Stroke Test. | msrc_UNKNOWN | Details |
disable_PST_abort | 4348 | Disable PST | msrc_UNKNOWN | Details | |
partial_stroke_test_method | 4349 | Partial Stroke Test | msrc_UNKNOWN | Details | |
partial_stroke_test_abort | 434A | PST Abort | msrc_UNKNOWN | Details | |
run_PST_cal_and_config_SUBROUTINE | 454C | PST Calibration | msrc_UNKNOWN | Details | |
calib_abort1 | 4332 | Calibration aborted. | msrc_UNKNOWN | Details | |
calib_abort2 | 4336 | Calibration aborted. | msrc_UNKNOWN | Details | |
not_calibrated_abort | 4342 | Not Calibrated | msrc_UNKNOWN | Details | |
last_calib_time_method | 434B | Calibration Time | msrc_UNKNOWN | Details | |
last_calib_time_abort | 434C | Calibration Time | msrc_UNKNOWN | Details | |
tvl_auto_calib_method | 434D | Auto Calibration | Follow the prompts to initiate automatic calibration of the Travel Sensor. | msrc_UNKNOWN | Details |
run_tvl_auto_calib_SUBROUTINE | 454D | Auto Calibration | Follow the prompts to initiate automatic calibration of the Travel Sensor. | msrc_UNKNOWN | Details |
tvl_auto_calib_abort | 434E | Auto Calibration aborted | msrc_UNKNOWN | Details | |
tvl_manual_calib_method | 4350 | Manual Calibration | Follow the prompts to manually calibrate the instrument travel sensor. | msrc_UNKNOWN | Details |
find_travel_sensor_motion_SUBROUTINE | 454E | Device Setup | Prompts the user for pressure information and to select subsequent menu items for instrument setup. Note: All items on the Auto Setup menu must be selected in order for basic setup. | msrc_UNKNOWN | Details |
device_setup_partial_abort | 4353 | Device Setup | msrc_UNKNOWN | Details | |
device_setup_method | 4354 | Device Setup | Prompts the user for pressure information and to select subsequent menu items for instrument setup. Note: All items on the Auto Setup menu must be selected in order for basic setup. | msrc_UNKNOWN | Details |
display_alert_record_method | 4355 | View Alert Records | Displays the Alert Record. | msrc_UNKNOWN | Details |
clear_alert_record_method | 4356 | Clear Records | Clears the Alert Record. | msrc_UNKNOWN | Details |
shutdown_0b0_travel_sensor_method | 4357 | Travel Sensor Failure Shutdown | Shutdown on Travel Travel Sensor Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b1_press_sensor_method | 4358 | Pressure Sensor Failure Shutdown | Shutdown on Travel Pressure Sensor Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b2_temp_sensor_method | 4359 | Temp Sensor Failure Shutdown | Shutdown on Travel Temp Sensor Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b3_critical_NVM_method | 435A | Critical NVM Failure Shutdown | Shutdown on Travel Critical NVM Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b4_drive_current_method | 435B | Drive Current Failure Shutdown | Shutdown on Travel Drive Current Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b5_ref_voltage_method | 435C | Reference Voltage Failure Shutdown | Shutdown on Travel Reference Voltage Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b6_MLFB_sensor_method | 435D | Minor Loop Sensor Failure Shutdown | Shutdown on Travel Minor Loop Sensor Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_0b7_flash_itegrity_method | 435E | Flash Integrity Failure Shutdown | Shutdown on Travel Flash Integrity Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_1b2_SISProgramFlow_method | 435F | Program Flow Failure Shutdown | Shutdown on Travel Program Flow Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_2b6_NonCriticalNVM_method | 4360 | Non-Critical NVM Failure Shutdown | Shutdown on Travel Non-Critical NVM Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
shutdown_2b7_SIS_hardware_method | 4361 | SIS Hardware Failure Shutdown | Shutdown on Travel SIS Hardware Failure Shutdown. Upon shutdown, the instrument attempts to drive its output pressure to the zero input current condition and no longer executes its control functions. | msrc_UNKNOWN | Details |
XStatus1b3_PressControlActiveEnab_method | 4362 | Pressure Fallback Active Enable | Enable or disable the reporting of the Pressure Fallback Active Enable | msrc_UNKNOWN | Details |
XStatus1b6_SIS_TrippedByLCPEnab_method | 4363 | Tripped by the LCP Enable | Enable or disable the reporting of the Tripped by the LCP Enable | msrc_UNKNOWN | Details |
XStatus1b7_AlertRecordNotEmptyEnab_method | 4364 | Alert Record Not Empty Enable | Enable or disable the reporting of the Alert Record Not Empty Enable | msrc_UNKNOWN | Details |
XStatus2b2_AlertRecordFullEnab_method | 4365 | Alert Record Full Enable | Enable or disable the reporting of the Alert Record Full Enable | msrc_UNKNOWN | Details |
XStatus2b3_InstTimeInvalidEnab_method | 4366 | Instrument Time is Approximate Enable | Enable or disable the reporting of the Instrument Time is Approximate Enable | msrc_UNKNOWN | Details |
XStatus2b4_TravelAccumAlertEnab_method | 4367 | Travel Accumulator Alert Enable | Enable or disable the reporting of the Travel Accumulator Alert Enable | msrc_UNKNOWN | Details |
XStatus2b5_CycleCounterAlertEnab_method | 4368 | Cycle Count Alert Enable | Enable or disable the reporting of the Cycle Count Alert Enable | msrc_UNKNOWN | Details |
XStatus3b0_IntegratorSaturatedLoEnab_method | 4369 | Integrator Sat Lo Enable | Enable or disable the reporting of the Integrator Sat Lo Enable | msrc_UNKNOWN | Details |
XStatus3b1_IntegratorSaturatedHiEnab_method | 436A | Integrator Sat Hi Enable | Enable or disable the reporting of the Integrator Sat Hi Enable | msrc_UNKNOWN | Details |
XStatus3b3_SISLockedInSafetyEnab_method | 436B | SIS Locked In Safety Alert Enable | Enable or disable the reporting of the SIS Locked In Safety Alert Enable | msrc_UNKNOWN | Details |
XStatus3b4_EndPtPressDevAlertEnab_method | 436C | EPPC Deviation Alert Enable | Enable or disable the reporting of the EPPC Deviation Alert Enable | msrc_UNKNOWN | Details |
XStatus3b5_SupplyPressureAlertEnab_method | 436D | Supply Pressure Alert Enable | Enable or disable the reporting of the Supply Pressure Alert Enable | msrc_UNKNOWN | Details |
XStatus4b0_DriveSignalAlertEnab_method | 436E | Drive Signal Alert Enable | Enable or disable the reporting of the Drive Signal Alert Enable | msrc_UNKNOWN | Details |
XStatus4b1_TvlLimitOrCutoffLoEnab_method | 436F | Travel Limit/Cutoff Lo Enable | Enable or disable the reporting of the Travel Limit/Cutoff Lo Enable | msrc_UNKNOWN | Details |
XStatus4b2_TvlLimitOrCutoffHiEnab_method | 4370 | Travel Limit/Cutoff Hi Enable | Enable or disable the reporting of the Travel Limit/Cutoff Hi Enable | msrc_UNKNOWN | Details |
XStatus4b3_TvlDeviationAlertEnab_method | 4371 | Travel Deviation Alert Enable | Enable or disable the reporting of the Travel Deviation Alert Enable | msrc_UNKNOWN | Details |
XStatus4b4_TvlAlertHiHiEnab_method | 4372 | Travel Alert Hi Hi Enable | Enable or disable the reporting of the Travel Alert Hi Hi Enable | msrc_UNKNOWN | Details |
XStatus4b5_TvlAlertHiEnab_method | 4373 | Travel Alert Hi Enable | Enable or disable the reporting of the Travel Alert Hi Enable | msrc_UNKNOWN | Details |
XStatus4b6_TvlAlertLoLoEnab_method | 4374 | Travel Alert Lo Lo Enable | Enable or disable the reporting of the Travel Alert Lo Lo Enable | msrc_UNKNOWN | Details |
XStatus4b7_TvlAlertLoEnab_method | 4375 | Travel Alert Lo Enable | Enable or disable the reporting of the Travel Alert Lo Enable | msrc_UNKNOWN | Details |
XStatus5b2_XmiterCommErrorEnab_method | 4376 | Output Circuit Comm Failure Enable | Enable or disable the reporting of the Output Circuit Comm Failure Enable | msrc_UNKNOWN | Details |
XStatus5b3_SISPanelCommErrorEnab_method | 4377 | LCP Communication Failure Enable | Enable or disable the reporting of the LCP Communication Failure Enable | msrc_UNKNOWN | Details |
show_active_alerts_method | 4378 | Device Status | msrc_UNKNOWN | Details | |
pre_send_configuration_method | 03EF | pre_send_configuration_method | msrc_UNKNOWN | Details | |
post_send_configuration_method | 03F0 | post_send_configuration_method | msrc_UNKNOWN | Details | |
warning_message | 1017 | msrc_UNKNOWN | Details | ||
Name | ID | Label | Description | Type | Source |