Loading…
Loading…
Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
dec_self_test_method | 4017 | Self Test | Self test will perform all internal checks immediately and return results in variables xmtr flt 1 & xmtr flt 2. | msrc_UNKNOWN | Details |
dec_self_test_method_ams | 4018 | Self Test | Self test will perform all internal checks immediately and return results in variables xmtr flt 1 & xmtr flt 2. | msrc_UNKNOWN | Details |
dec_abort_response_test | 401D | Abort response test | msrc_UNKNOWN | Details | |
dec_return_to_normal | 401E | return to normal | msrc_UNKNOWN | Details | |
x2200_method_oi_calibration | 4089 | Calibrate Oi | This procedure calibrates the Oi test signal for all three IR sensors. | msrc_UNKNOWN | Details |
x2200_method_start_passive_oi | 407F | Start Passive Oi | Test to check the cleanliness of the detector's optical surfaces and the ability to respond to an IR signal. Relays unaffected. | msrc_UNKNOWN | Details |
x2200_method_start_active_oi | 4080 | Start Active Oi | Test to check the cleanliness of the detector's optical surfaces and the ability to respond to an IR signal. Relays are affected. | msrc_UNKNOWN | Details |
x2200_method_clear_oi_fault | 4081 | Clear Oi Fault | Clear prior Oi faults. If the cause of the fault has not been corrected, subsequent Oi faults will occur. | msrc_UNKNOWN | Details |
x2200_method_reset_latches | 4082 | Reset Latches | Latched relays are reset. LED turns green. | msrc_UNKNOWN | Details |
x2200_method_hardware_reset | 401C | Master Reset | Initiates a hardware reset for both the sensor and the HART interface. Latched relays are reset. | msrc_UNKNOWN | Details |
x2200_method_clear_logs | 4083 | Clear Data Log | Clears data log entries contained on the HART interface board. | msrc_UNKNOWN | Details |
x2200_method_alarm_log | 4091 | Alarm Log | Scroll through 32 Alarm Logs with date, time, and temperature stamp. | msrc_UNKNOWN | Details |
x2200_method_fault_log | 4092 | Fault Log | Scroll through 32 Fault Logs with date, time, and temperature stamp. | msrc_UNKNOWN | Details |
x2200_method_general_log | 4093 | General Log | Scroll through 32 General Logs with date, time, and temperature stamp. | msrc_UNKNOWN | Details |
x2200_method_abort | 4094 | X2200 Abort Method. | msrc_UNKNOWN | Details | |
x2200_method_partnumber | 408B | Part Number | Manufacturer's part number for this device. | msrc_UNKNOWN | Details |
x2200_method_datetime | 408C | Real Time Clock | Current time and date setting of real time clock. Factory set to GMT minus 6 hours. Date: month/day/year Time: Hour:minute:second | msrc_UNKNOWN | Details |
x2200_method_serialnumber | 408A | Serial Number | Serial number of device. | msrc_UNKNOWN | Details |
loop_test | 1002 | Loop test | Loop test- Allows the User to manually manipulate the Analog Output to a selected constant output value | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | Leaving fixed crnt mode | Leaving Fixed Current Mode- Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
dac_trim | 1004 | D/A trim | Digital to Analog Trim- Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output | msrc_UNKNOWN | Details |
Name | ID | Label | Description | Type | Source |