Name | ID | Label | Description | Type | Source |
---|---|---|---|---|---|
get_new_hmi_local_op_enable | 403F | Local Op. Ena. | msrc_UNKNOWN | Details | |
self_test | 400A | Self test | Performs self test on the 261. Reports any errors. | msrc_UNKNOWN | Details |
stuck_in_self_test | 4054 | Stuck in self test | msrc_UNKNOWN | Details | |
self_test_end | 4055 | Self test OK | msrc_UNKNOWN | Details | |
master_reset | 400B | Master reset | Resets the 261 electronic | msrc_UNKNOWN | Details |
master_reset_end | 4056 | Master reset OK | msrc_UNKNOWN | Details | |
reset_factory_data | 4014 | Factory reset | ATTENTION! This will reset all user configured data to factory default values! | msrc_UNKNOWN | Details |
sensor_temperature_trim | 4023 | Snsr temp Trim | Snsr temp Trim- Calibrate the sensor temperature. | msrc_UNKNOWN | Details |
shift_range | 4027 | Shift range | Shift range- Shift the upper and lower range values of the pressure. Pressure- Measured process pressure in relation to a reference pressure. | msrc_UNKNOWN | Details |
leave_shift_range | 4057 | offset sh | msrc_UNKNOWN | Details | |
loop_test | 1002 | Loop test | Loop test- Allows the User to manually manipulate the Analog Output to a selected constant output value | msrc_UNKNOWN | Details |
leave_fixed_current_mode | 1003 | Leaving fixed crnt mode | Leaving Fixed Current Mode- Takes the Analog Output out of a mode where the output was a constant value, and returns the output to a mode where the output tracks the input | msrc_UNKNOWN | Details |
return_to_normal | 1016 | Aborting return to normal | msrc_UNKNOWN | Details | |
burn_eeprom | 100C | Burn EEPROM | Burn Electrically Erasable Read Only Memory- Operation where the Field Device will copy what is in its Random Access Memory into the Electrically Erasable Read Only Memory, thus making changes by the Host permanent | msrc_UNKNOWN | Details |
zero_trim | 1006 | Zero trim | Zero trim- Make the sensor input the new zero input reference | msrc_UNKNOWN | Details |
dac_trim | 1004 | D/A trim | Digital to Analog Trim- Allows the calibration of a selected Analog Output with an external reference at the operating endpoints of the Analog Output | msrc_UNKNOWN | Details |
applied_rerange | 1007 | Apply values | Applied values- Perform a device rerange by applying the desired Upper Range Value and Lower Range Values to the device input | msrc_UNKNOWN | Details |
send_warning | 1399 | Send warning | Send Warning- Yields a units code notice to the User | msrc_UNKNOWN | Details |
sensor_a_lower_sensor_trim | 1787 | Pres lor snsr trim | Pressure Sensor Lower Trim- Calibrate the pressure sensor | msrc_UNKNOWN | Details |
sensor_a_upper_sensor_trim | 1789 | Pres upr snsr trim | Pressure Sensor Upper Trim- Calibrate the pressure sensor | msrc_UNKNOWN | Details |
leave_trim_mode | 1788 | Exit trim mode | Exit Trim Mode- Notifies the User that the trim is finished | msrc_UNKNOWN | Details |