0 |
EJX-MV |
1 |
Write Protect |
2 |
P sensor error |
3 |
CT sensor error |
4 |
Cap EEPROM error |
5 |
AT sensor error |
6 |
Amp EEPROM error |
7 |
CPU board error |
8 |
No device ID |
9 |
P outside limit |
10 |
SP outside limit |
11 |
CT outside limit |
12 |
AT outside limit |
13 |
PLS outside limit |
14 |
OHM outside limit |
15 |
ET outside limit |
16 |
P over range |
17 |
SP over range |
18 |
F over range |
19 |
ET over range |
20 |
ET sensor error |
21 |
A/D Converter error |
22 |
P high alarm |
23 |
P low alarm |
24 |
SP high alarm |
25 |
SP low alarm |
26 |
CT high alarm |
27 |
CT low alarm |
28 |
Simulation mode |
29 |
Illegal P LRV |
30 |
Illegal P URV |
31 |
Illegal P SPAN |
32 |
P SPAN trim err |
33 |
P ZERO trim err |
34 |
Illegal SP LRV |
35 |
Illegal SP URV |
36 |
Illegal SP SPAN |
37 |
SP SPAN trim err |
38 |
SP ZERO trim err |
39 |
ET SPAN trim err |
40 |
ET ZERO trim err |
41 |
ET Fixed Mode |
42 |
PLS set err |
43 |
Illegal ET LRV |
44 |
Illegal ET URV |
45 |
Illegal ET SPAN |
46 |
F set outside Range |
47 |
F high alarm |
48 |
F low alarm |
49 |
ET high alarm |
50 |
ET low alarm |
51 |
FT high alarm |
52 |
FT low alarm |
53 |
ILBD over range |
54 |
Invalid Ref DP |
55 |
Invalid Ref SPL |
56 |
Invalid Ref SPH |
57 |
Invalid Ref F |
58 |
B Blocking |
59 |
H Side Blocking |
60 |
L Side Blocking |
61 |
Large Fluct H |
62 |
Large Fluct L |
63 |
A Blocking |
64 |
Xmtr Variables |
65 |
Four transmitter variables. |
66 |
Xmtr Vars |
67 |
SP |
68 |
ET |
69 |
Total Flow |
70 |
Alert Mode |
71 |
HI/LO Alarm Mode |
72 |
Hi Alert |
73 |
High Alarm Setpoint |
74 |
Lo Alert |
75 |
Low Alarm Setpoint |
76 |
LTP |
77 |
Lower Trim Point |
78 |
UTP |
79 |
Upper Trim Point |
80 |
LTD |
81 |
Lower Trim Deviation |
82 |
UTD |
83 |
Upper Trim Deviation |
84 |
Pres Unit |
85 |
inH2O @ 68degF |
86 |
ftH2O @ 68degF |
87 |
mmH2O @ 68degF |
88 |
g/cm2 |
89 |
kg/cm2 |
90 |
Feet of Water at 4 Degrees Celsius |
91 |
hPa |
92 |
Hectopascals |
93 |
.3f |
94 |
.4f |
95 |
.1f |
96 |
.2f |
97 |
.5f |
98 |
.0f |
99 |
.6f |
100 |
Pres % |
101 |
6.2f |
102 |
Pres Damp |
103 |
Pres Min span |
104 |
Si Oil |
105 |
F Oil |
106 |
Process Conn type |
107 |
Thread |
108 |
Num of RS |
109 |
Two Seals |
110 |
Extension |
111 |
HTV-W |
112 |
HTV-E |
113 |
Pres LTP |
114 |
Pres UTP |
115 |
Pres AO |
116 |
5.2f |
117 |
AO alm typ |
118 |
Process Conn matl |
119 |
Module type |
120 |
DP |
121 |
Pressure |
122 |
Lower Pressure Trim Deviation |
123 |
Pres LTD |
124 |
Upper Pressure Trim Deviation |
125 |
Pres UTD |
126 |
Static Pressure Value |
127 |
SP Unit Code |
128 |
SP Unit |
129 |
Static Pressure Percent of Range |
130 |
SP % |
131 |
Static Pressure Minimum Span |
132 |
SP Min span |
133 |
Static Pressure Lower Range Limit |
134 |
SP LSL |
135 |
Static Pressure Upper Range Limit |
136 |
SP USL |
137 |
Static Pressure Analog Output Value |
138 |
SP AO |
139 |
Lower Static Pressure Trim Point |
140 |
SP LTP |
141 |
Upper Static Pressure Trim Point |
142 |
SP UTP |
143 |
Lower Static Pressure Trim Deviation |
144 |
SP LTD |
145 |
Upper Static Pressure Trim Deviation |
146 |
SP UTD |
147 |
External Temperature Value |
148 |
External Temperature Percent of Range |
149 |
ET % |
150 |
External Temperature Minimum Span |
151 |
ET Min span |
152 |
External Temperature Lower Range Limit |
153 |
ET LSL |
154 |
External Temperature Upper Range Limit |
155 |
ET USL |
156 |
External Temperature Analog Output Value |
157 |
ET AO |
158 |
Lower External Temperature Trim Point |
159 |
ET LTP |
160 |
Upper External Temperature Trim Point |
161 |
ET UTP |
162 |
Lower External Temperature Trim Deviation |
163 |
ET LTD |
164 |
Upper External Temperature Trim Deviation |
165 |
ET UTD |
166 |
Flow Value |
167 |
Flow Percent of Range |
168 |
Flow % |
169 |
Flow Analog Output Value |
170 |
Flow AO |
171 |
Engineer Output |
172 |
Engr Disp |
173 |
Engineer Exponent |
174 |
Engr exp |
175 |
x1 |
176 |
x10 |
177 |
x100 |
178 |
x1000 |
179 |
Engineer Unit Code |
180 |
Engr Unit |
181 |
Total Flow Value |
182 |
Cap Temperature Value |
183 |
Cap temp |
184 |
Amp Temperature Value |
185 |
Amp temp |
186 |
Trim Who |
187 |
Trim Date |
188 |
Trim Location |
189 |
Trim Loc |
190 |
Trim Description |
191 |
Trim Desc |
192 |
Total Flow Unit |
193 |
t |
194 |
oz |
195 |
m3 |
196 |
yd3 |
197 |
ft3 |
198 |
in3 |
199 |
Nm3 |
200 |
NL |
201 |
SCF |
202 |
use to Total Flow user scale |
203 |
Low Cut |
204 |
Low cut |
205 |
Low Cut Mode |
206 |
Low cut mode |
207 |
H/L Swap |
208 |
Static Pressure Absolute/Gauge Selection |
209 |
A/G Select |
210 |
Gauge |
211 |
Absolute |
212 |
Static Pressure H/L Selection Code |
213 |
SP H/L Select |
214 |
Atmospheric Pressure Value |
215 |
Atm. Pres Value |
216 |
Fixed External Temp Code |
217 |
ET Fixed |
218 |
FALL BACK |
219 |
Fixed External Temp Value |
220 |
Fixed ET Val |
221 |
Pulse Rate |
222 |
Pulse rate |
223 |
Digtal Output Frequency at 100% |
224 |
Freq at 100% |
225 |
Total Flow Mode Code |
226 |
Total Flow Mode |
227 |
Start Cyclic |
228 |
Convert Value |
229 |
Cvt Val |
230 |
Digital Output |
231 |
Auto Recover |
232 |
Auto recover |
233 |
Lower Limit of Analog Output |
234 |
AO lower limit |
235 |
Upper Limit of Analog Output |
236 |
AO upper limit |
237 |
Digital Output Select Code |
238 |
DO Select |
239 |
Pres/SP |
240 |
Pres/Temp |
241 |
SP/Temp |
242 |
Pres/SP/Temp |
243 |
Pres/Flow |
244 |
SP/Flow |
245 |
Temp/Flow |
246 |
Pres/SP/Flow |
247 |
Pres/Temp/Flow |
248 |
SP/Temp/Flow |
249 |
Pres/SP/Temp/Flow |
250 |
Diag Alarm |
251 |
All |
252 |
Digital Output Signal Type |
253 |
DO Signal type |
254 |
On When Al. Detect |
255 |
Off When Al. Detect |
256 |
Scaled Pulse |
257 |
Frequency |
258 |
Digtal Output Frequency |
259 |
DO Frequency |
260 |
Display Out 1 |
261 |
Disp1 |
262 |
PV % |
263 |
EXT. TEMP |
264 |
ENGR.PV |
265 |
TOTAL FLOW |
266 |
Display Out 2 |
267 |
Disp2 |
268 |
Display Out 3 |
269 |
Disp3 |
270 |
Display Out 4 |
271 |
Disp4 |
272 |
Display % Resolution |
273 |
Disp % Reso |
274 |
High Resolution |
275 |
Flow Decimal Point |
276 |
Flow disp point |
277 |
0 |
278 |
Integer |
279 |
1 |
280 |
Down to 1 place of decimals |
281 |
2 |
282 |
Down to 2 places of decimals |
283 |
3 |
284 |
Down to 3 places of decimals |
285 |
4 |
286 |
Down to 4 places of decimals |
287 |
Pressure Decimal Point |
288 |
Pres disp point |
289 |
Static Pressure Decimal Point |
290 |
SP disp point |
291 |
External Temp Decimal Point |
292 |
ET disp point |
293 |
Total Flow Decimal Point |
294 |
TF disp point |
295 |
Engineer LRV |
296 |
Engr LRV |
297 |
Engineer URV |
298 |
Engr URV |
299 |
Engineer Decimal Point |
300 |
Engr point |
301 |
Bar Indicator |
302 |
MS Code 1 |
303 |
MS Code 2 |
304 |
MS Code 3 |
305 |
External Zero Adjust Enable |
306 |
Ext SW |
307 |
Disabled |
308 |
Enabled |
309 |
Style Number |
310 |
Style No. |
311 |
Serial Number |
312 |
Serial No. |
313 |
Manufacture Date |
314 |
Mftr Date |
315 |
Extra Number |
316 |
Extra No. |
317 |
PT100 Serial Number |
318 |
PT100 Serial No. |
319 |
Gasket Material- Construction material of a seal that exists between the module and flange. |
320 |
Gasket matl |
321 |
Process Connection Size Code |
322 |
Process Conn size |
323 |
ANSI3, C150 |
324 |
ANSI3, C300 |
325 |
ANSI3, C600 |
326 |
ANSI4, C150 |
327 |
ANSI4, C300 |
328 |
ANSI2, C150 |
329 |
ANSI2, C300 |
330 |
ANSI2, C600 |
331 |
DIN80, PN10/16 |
332 |
DIN80, PN25/40 |
333 |
DIN80, PN64 |
334 |
DIN100, PN10/16 |
335 |
DIN100, PN25/40 |
336 |
DIN50, PN10/16 |
337 |
DIN50, PN25/40 |
338 |
DIN50, PN64 |
339 |
ANSI 150 |
340 |
ANSI 300 |
341 |
ANSI 600 |
342 |
DIN 10/16 |
343 |
DIN 25 |
344 |
DIN 40 |
345 |
1/2NPT Female |
346 |
1/4NPT Female |
347 |
Rc 1/2 Female |
348 |
1/2NPT Male |
349 |
G 1/2 Male |
350 |
M2O * 1.5 Male |
351 |
R 1/2 Male |
352 |
Remote Seal Fill Fluid- Fluid material in the device remote seal. |
353 |
Silicone |
354 |
SH704 |
355 |
SH705 |
356 |
Ethy Gly/H2O |
357 |
Simulation Mode SW |
358 |
Simulation Mode |
359 |
ON:DP |
360 |
DP=ON, SP=OFF,ET=OFF |
361 |
ON: SP |
362 |
DP=OFF,SP=ON, ET=OFF |
363 |
ON:DP SP |
364 |
DP=ON, SP=ON, ET=OFF |
365 |
ON: ET |
366 |
DP=OFF,SP=OFF,ET=ON |
367 |
ON:DP ET |
368 |
DP=ON, SP=OFF,ET=ON |
369 |
ON: SP ET |
370 |
DP=OFF,SP=ON, ET=ON |
371 |
ON:DP SP ET |
372 |
DP=ON, SP=ON, ET=ON |
373 |
Check Flow Calc |
374 |
DP=ON, SP=ON, ET=ON, DP,SP,ET,Flow Filter Off |
375 |
Pres Unit Code for simulation |
376 |
Sim Pres Unit |
377 |
Differential Press Variable for simulation |
378 |
Sim Pres |
379 |
SP Unit Code for simulation |
380 |
Sim SP Unit |
381 |
Static Press Variable for simulation |
382 |
Sim SP |
383 |
Temp Unit Code for simulation |
384 |
Sim Temp Unit |
385 |
External Temp Variable for simulation |
386 |
Sim Temp |
387 |
Flow Calculation Mode |
388 |
Flow Calc Mode |
389 |
Auto Comp. Mode |
390 |
Basic Mode |
391 |
Fluid Type Code |
392 |
Fluid Type |
393 |
not defined |
394 |
Flow Calc Fixed Variable |
395 |
Flow Calc Fixed |
396 |
Reference Static Press |
397 |
Ref SP |
398 |
Reference Temperature |
399 |
Ref Temp |
400 |
Temp K1 For Liquid Variable |
401 |
Temp K1 |
402 |
Software Seal Code |
403 |
Software seal |
404 |
Break |
405 |
Keep |
406 |
SI Option |
407 |
OFF |
408 |
ON |
409 |
Temp Zero Compensation Mode |
410 |
T.Z. Cmp mode |
411 |
Temp Zero Compensation Value |
412 |
Temp Zero |
413 |
%/degC |
414 |
7.3f |
415 |
Temp Ref Fixed Value |
416 |
Temp Ref Fixed |
417 |
Temp 1 Mode |
418 |
Temp1 |
419 |
Ext.Temp |
420 |
Cap.Temp |
421 |
Temp 2 Mode |
422 |
Temp2 |
423 |
Fixed Temp |
424 |
Pressure Value or % Value for Trim |
425 |
Pres for trim |
426 |
Static Pressure Value or % Value for Trim |
427 |
SP for trim |
428 |
Pressure HI/LO Alarm Mode |
429 |
Pres Alert mode |
430 |
Hi. Al Detect |
431 |
Lo. Al Detect |
432 |
Hi/Lo. Al Detect |
433 |
Pressure High Alarm Setpoint |
434 |
Pres Hi Alert Val |
435 |
Pressure Low Alarm Setpoint |
436 |
Pres Lo Alert Val |
437 |
Static Pressure Upper Range Value |
438 |
SP URV |
439 |
Static Pressure Lower Range Value |
440 |
SP LRV |
441 |
Static Pressure Damping Value |
442 |
SP Damp |
443 |
Static Pressure HI/LO Alarm Mode |
444 |
SP Alert Mode |
445 |
Static Pressure High Alarm Setpoint |
446 |
SP Hi Alert Val |
447 |
Static Pressure Low Alarm Setpoint |
448 |
SP Lo Alert Val |
449 |
Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. |
450 |
ET Unit |
451 |
External Temperature Lower Range Value |
452 |
ET LRV |
453 |
External Temperature Upper Range Value |
454 |
ET URV |
455 |
External Temperature Damping Value |
456 |
ET Damp |
457 |
External Temperature HI/LO Alarm Mode |
458 |
ET Alert Mode |
459 |
External Temperature High Alarm Setpoint |
460 |
ET Hi Alert Val |
461 |
External Temperature Low Alarm Setpoint |
462 |
ET Lo Alert Val |
463 |
Flow Unit |
464 |
t/min |
465 |
t/h |
466 |
t/d |
467 |
Short Tons Per Minute |
468 |
Short Tons per Hour |
469 |
Short Tons per Day |
470 |
Long Tons Per Hour |
471 |
Long Tons Per Day |
472 |
CFM |
473 |
GPM |
474 |
m3/h |
475 |
CFS |
476 |
ft3/d |
477 |
m3/s |
478 |
m3/d |
479 |
Nm3/h |
480 |
NL/h |
481 |
SCFM |
482 |
CFH |
483 |
m3/min |
484 |
gal/d |
485 |
SL/h |
486 |
Standard Liter Per Hour |
487 |
SL/min |
488 |
Standard Liter Per Minute |
489 |
SL/s |
490 |
Standard Liter Per Second |
491 |
Nm3/d |
492 |
Normal Cubic Meter Per Day |
493 |
SCFD |
494 |
Standard Cubic Feet Per Day |
495 |
SCFH |
496 |
Standard Cubic Feet Per Hour |
497 |
SCFS |
498 |
Standard Cubic Feet Per Second |
499 |
Sm3/d |
500 |
Standard Cubic Meter Per Day |
501 |
Sm3/h |
502 |
Standard Cubic Meter Per Hour |
503 |
MSCFD |
504 |
Thousand Standard Cubic Feet Per Day |
505 |
MMSCFD |
506 |
Million Thousand Standard Cubic Feet Per Day |
507 |
Flow Upper Range Value |
508 |
Flow URV |
509 |
Flow Lower Range Value |
510 |
Flow LRV |
511 |
Flow Damping Value |
512 |
Flow Damp |
513 |
Flow HI/LO Alarm Mode |
514 |
Flow Alert Mode |
515 |
Flow High Alarm Setpoint |
516 |
Flow Hi Alert Val |
517 |
Flow Low Alarm Setpoint |
518 |
Flow Lo Alert Val |
519 |
Engineer Unit of Capital Letter |
520 |
|
521 |
Small Character of Engineer Unit |
522 |
Engineer Unit Select Code for Easy Setting |
523 |
Select unit |
524 |
psia |
525 |
mmHgA |
526 |
mmAq |
527 |
mmWG |
528 |
Torr |
529 |
inHgA |
530 |
gf/cm2 |
531 |
kgf/cm2 |
532 |
kg/cm2G |
533 |
kg/cm2A |
534 |
l/h |
535 |
l/min |
536 |
kl/h |
537 |
kl/min |
538 |
Nl/h |
539 |
Nl/min |
540 |
Nm3/min |
541 |
ACFH |
542 |
ACFM |
543 |
GPH |
544 |
kg/m3 |
545 |
g/cm3 |
546 |
Trim Clear Code |
547 |
Not Clear |
548 |
ALL |
549 |
Ext Temp |
550 |
Pressure Sensor Range Code |
551 |
P Range code |
552 |
M |
553 |
H |
554 |
L |
555 |
A |
556 |
B |
557 |
C |
558 |
E |
559 |
V |
560 |
D |
561 |
Static Pressure Sensor Range Code |
562 |
SP Range code |
563 |
Standard |
564 |
Keyword for Test Mode |
565 |
Data No. for Test |
566 |
Data1 for Test |
567 |
Data2 for Test |
568 |
Error Record Selection Code |
569 |
Log1 |
570 |
Latest |
571 |
Log2 |
572 |
Log3 |
573 |
Log4 |
574 |
Oldest |
575 |
Error Record 0 |
576 |
Error Rec 0 |
577 |
2X |
578 |
Error Record 1 |
579 |
Error Rec 1 |
580 |
Error Record 2 |
581 |
Error Rec 2 |
582 |
Error Record 3 |
583 |
Error Rec 3 |
584 |
Error Record 4 |
585 |
Error Rec 4 |
586 |
Error Record 5 |
587 |
Error Rec 5 |
588 |
Error Record 6 |
589 |
Error Rec 6 |
590 |
Error Record 7 |
591 |
Error Rec 7 |
592 |
Digital Output Test Code |
593 |
DO Test |
594 |
Status High |
595 |
Status Low |
596 |
Exit DO Test mode |
597 |
Simple Density Base |
598 |
Simple Dens Base |
599 |
Base Total Flow Units Code |
600 |
Base Total Flow Unit |
601 |
Total Flow Character of Engineer Unit |
602 |
Char of Engr. Unit |
603 |
Space for 8 characters |
604 |
Diag Error Status. |
605 |
Diag Error |
606 |
Bit mask for Alarm against Diag Error Status. |
607 |
Diag Option |
608 |
Diag Mode. |
609 |
Diag Mode |
610 |
Stop |
611 |
Calculation |
612 |
Reference |
613 |
Diag Applicable. |
614 |
Diag Applicable |
615 |
Ratio of Root fluct DP for Reference with Compensation Status. |
616 |
Ratio fDP Status |
617 |
Sensor Failure |
618 |
Device Failure |
619 |
Uncertain |
620 |
Invalid Ref |
621 |
Good |
622 |
Ratio of Root fluct DP for Reference. |
623 |
Ratio fDP |
624 |
Ratio of Root fluct SP low side for Reference Status. |
625 |
Ratio fSPl Status |
626 |
Ratio of Root fluct SP low side for Reference. |
627 |
Ratio fSPl |
628 |
Ratio of Root fluct SP high side for Reference Status. |
629 |
Ratio fSPh Status |
630 |
Ratio of Root fluct SP high side for Reference. |
631 |
Ratio fSPh |
632 |
Blocking Factor Status. |
633 |
BlkF Status |
634 |
Blocking Factor. |
635 |
BlkF |
636 |
DPAvg Status. |
637 |
DPAvg Status |
638 |
DPAvg. |
639 |
DPAvg |
640 |
Compensated Ratio of Root fluct DP for Reference Status. |
641 |
CRatio fDP Status |
642 |
Compensated Ratio of Root fluct DP for Reference. |
643 |
CRatio fDP |
644 |
Non-Compensated Ratio of Root fluct DP for Reference Status. |
645 |
NRatio fDP Status |
646 |
Non-Compensated Ratio of Root fluct DP for Reference. |
647 |
NRatio fDP |
648 |
Diag Description. |
649 |
Diag Description |
650 |
Reference fluct DP Status. |
651 |
Ref fDP Status |
652 |
Reference fluct DP. |
653 |
Ref fDP |
654 |
10g |
655 |
.3e |
656 |
Reference fluct SP low side Status. |
657 |
Ref fSPl Status |
658 |
Reference fluct SP low side. |
659 |
Ref fSPl |
660 |
Reference fluct SP high side Status. |
661 |
Ref fSPh Status |
662 |
Reference fluct SP high side. |
663 |
Ref fSPh |
664 |
Reference Blocking Factor Status. |
665 |
Ref BlkF Status |
666 |
Reference Blocking Factor. |
667 |
Ref BlkF |
668 |
10.6f |
669 |
Reference DPAvg Status. |
670 |
Ref DPAvg Status |
671 |
Reference DPAvg. |
672 |
Ref DPAvg |
673 |
fluct DP Status. |
674 |
fDP Status |
675 |
fluct DP. |
676 |
fDP |
677 |
12g |
678 |
.5e |
679 |
fluct SP low side Status. |
680 |
fSPl Status |
681 |
fluct SP low side. |
682 |
fSPl |
683 |
fluct SP high side Status. |
684 |
fSPh Status |
685 |
fluct SP high side. |
686 |
fSPh |
687 |
Test 1 |
688 |
Test 2 |
689 |
Test 3 |
690 |
Test 4 |
691 |
Diag Period. |
692 |
Diag Period |
693 |
Diag Limit fluct DP max. |
694 |
Lim fDPmax |
695 |
Diag Limit fluct DP min. |
696 |
Lim fDPmin |
697 |
Diag Limit fluct SP low side max. |
698 |
Lim fSPlmax |
699 |
Diag Limit fluct SP low side min. |
700 |
Lim fSPlmin |
701 |
Diag Limit fluct SP high side max. |
702 |
Lim fSPhmax |
703 |
Diag Limit fluct SP high side min. |
704 |
Lim fSPhmin |
705 |
Diag Limit Blocking Factor max. |
706 |
Lim BlkFmax |
707 |
Diag Limit Blocking Factor min. |
708 |
Lim BlkFmin |
709 |
Diag Limit DPAvg max. |
710 |
Lim DPAvgmax |
711 |
5.5f |
712 |
Diag Limit DPAvg min. |
713 |
Lim DPAvgmin |
714 |
Diag Alarm Suppression Count. |
715 |
Diag Supp Count |
716 |
.0d |
717 |
Reference Limit fluct DP min. |
718 |
Ref Lim fDPmin |
719 |
Reference Limit fluct SP min. |
720 |
Ref Lim fSPmin |
721 |
Reference Limit Blocking Factor max. |
722 |
Ref Lim BlkFmax |
723 |
Flow Compensation for Ratio of Root fluct DP. |
724 |
Diag DPComp |
725 |
Compensation |
726 |
Non-Compensation |
727 |
Flg temp. |
728 |
Flg temp |
729 |
Flg temp Coef. |
730 |
Flg temp Coef |
731 |
Flg temp Hi Alert Val. |
732 |
Flg temp Hi Alert Val |
733 |
4.0f |
734 |
Flg temp Lo Alert Val. |
735 |
Flg temp Lo Alert Val |
736 |
Diag Analog Output Option. |
737 |
Diag Out Option |
738 |
Off |
739 |
Burnout |
740 |
Fall back |
741 |
Diag Fixed Analog Output Value. |
742 |
Diag Fixed Out Val |
743 |
Test Auto Release Time |
744 |
10 min |
745 |
30 min |
746 |
60 min |
747 |
3 hour |
748 |
6 hour |
749 |
12 hour |
750 |
Activation Key for Optional Function |
751 |
Option Password |
752 |
View fld dev vars |
753 |
Output vars |
754 |
Analog output trim |
755 |
Pres sensor trim |
756 |
SP sensor trim |
757 |
ET sensor trim |
758 |
Trim info. |
759 |
Diag Parameters |
760 |
ILBD Parameters |
761 |
Status |
762 |
Diag Variables |
763 |
Diag Reference |
764 |
Fluct Variables |
765 |
Test |
766 |
Configuration |
767 |
Diag Lim |
768 |
Diag Ref Lim |
769 |
HT Parameters |
770 |
Flg Temp Lim |
771 |
Diag Output |
772 |
Error log |
773 |
Others |
774 |
Sensors |
775 |
Flow Setup |
776 |
DP Setup |
777 |
SP Setup |
778 |
ET Setup |
779 |
Fixed ET |
780 |
Config User Unit |
781 |
Analog output |
782 |
Process Alerts |
783 |
Pres Alert |
784 |
SP Alert |
785 |
ET Alert |
786 |
Flow Alert |
787 |
DO Config |
788 |
Display condition |
789 |
Disp select |
790 |
Disp condition |
791 |
Engr disp range |
792 |
Additional Info |
793 |
Simulation |
794 |
Basic Flow Calc |
795 |
Wrt protect menu |
796 |
Write variables |
797 |
Change PV Assgn |
798 |
Change SV Assgn |
799 |
Change TV Assgn |
800 |
Change 4V Assgn |
801 |
Self Test- Commands the EJX electronics to perform a selftest. Reports any errors that occured. |
802 |
Master Reset- Commands the EJX electronics to reset and perform a selftest. Reports any errors that occured. |
803 |
Clear D/A trim |
804 |
Pres trim |
805 |
Clear P trim |
806 |
SP trim |
807 |
Clear SP trim |
808 |
ET trim |
809 |
Clear ET trim |
810 |
Set Diag Mode |
811 |
Error log view |
812 |
Error log Clear |
813 |
Auto Atm. Pres |
814 |
Set Base Unit |
815 |
Modify Unit |
816 |
Burst Xmtr Vals |
817 |
Set Engr Unit |
818 |
Modify Engr Unit |
819 |
Chg power on info- Change the information displayed when turn on the power.
|
820 |
Chg power on info |
821 |
Abort of the Chg power on info- Display the power on information.
|
822 |
Abort of the Chg power on info |
823 |
Chg universal rev- Change the universal command revision.
|
824 |
Chg universal rev |
825 |
Abort of the Chg universal rev- Display the universal revision.
|
826 |
Abort of the Chg universal rev |
827 |
Test Key |
828 |
Enable wrt 10min |
829 |
New password |
830 |
After DO Test |
831 |
Aborting |
832 |
Exiting |
833 |
Invalid Analog Output Code Number |
834 |
Lowercase conversion not succeeded. |
835 |
Excess Correction Attemped |
836 |
Not write protect mode |
837 |
The First Password Accepted |
838 |
FMU860 |
839 |
DT |
840 |
DVC |
841 |
FCX |
842 |
AS800 |
843 |
340T |
844 |
340C |
845 |
344 |
846 |
Siemens Micro K |
847 |
SITRANS L |
848 |
SIPAN PH |
849 |
SITRANS P |
850 |
75SMT |
851 |
UNIDELTA |
852 |
8320 |
853 |
SX5100 |
854 |
TSV175 |
855 |
DMU |
856 |
3780 |
857 |
BM70 |
858 |
8u |
859 |
low |
860 |
high |
861 |
tmp_av |
862 |
.3g |
863 |
.f |
864 |
% |
865 |
3.2f |
866 |
s |
867 |
4.2f |
868 |
6.4f |
869 |
5.3f |
870 |
Current PV is %{0};
Select new PV |
871 |
Flow;Pres;SP;ET |
872 |
New PV is %{0} |
873 |
Current SV is %{0};
Select new SV |
874 |
Flow;Pres;SP;ET;Total Flow |
875 |
New SV is %{0} |
876 |
Current TV is %{0};
Select new TV |
877 |
New TV is %{0} |
878 |
Current 4V is %{0};
Select new 4V |
879 |
New 4V is %{0} |
880 |
Self test in progress please wait |
881 |
Device maybe stuck in selftest. |
882 |
Self Test OK |
883 |
It will reset the master CPU, OK ? |
884 |
Exit;Execute |
885 |
Master Reset in progress please wait |
886 |
Device maybe stuck in master reset. |
887 |
Master Reset OK |
888 |
Execute OK ? |
889 |
Pres trim mode: |
890 |
Off;Auto, Lower Pt;Auto, Upper Pt;Manual, Lower Pt;Manual, Upper Pt |
891 |
Pres for trim %{0}
Auto, Lower Pt |
892 |
Pres for trim %{0}
Auto, Upper Pt |
893 |
Pres for trim %{0}
Manual, Lower Pt |
894 |
Pres for trim %{0}
Manual, Upper Pt |
895 |
SP trim mode: |
896 |
SP for trim %{0}
Auto, Lower Pt |
897 |
SP for trim %{0}
Auto, Upper Pt |
898 |
SP for trim %{0}
Manual, Lower Pt |
899 |
SP for trim %{0}
Manual, Upper Pt |
900 |
ET trim mode: |
901 |
ET %{0}
Auto, Lower Pt |
902 |
ET %{0}
Auto, Upper Pt |
903 |
ET %{0}
Manual, Lower Pt |
904 |
ET %{0}
Manual, Upper Pt |
905 |
Current Diag Mode is : %{0}
Select Diag Mode |
906 |
Stop;Calculation;Reference |
907 |
Show the: |
908 |
Log1(Latest);Log2;Log3;Log4(Oldest);Exit |
909 |
Advanced Diag Fail. |
910 |
No error |
911 |
Performing log clear |
912 |
Apply atmosphere pressure input to sensor. |
913 |
Succeeded. |
914 |
Enter Unit: |
915 |
Select one: |
916 |
Slot 1;Slot 2;Slot 3;Slot 4;View;Exit |
917 |
Select new Slot %{slot}
%{4} |
918 |
Flow;Pres;SP;ET;Total Flow;Back |
919 |
Slot 1 is %{0}
Slot 2 is %{1}
Slot 3 is %{2}
Slot 4 is %{3} |
920 |
Status High;Status Low;Frequency;Exit |
921 |
Digital Output is fixed to on;
status high |
922 |
Digital Output is fixed to on;
status low |
923 |
Digital Output is fixed to on;
Frequency is %{tmp} Hz |
924 |
;kPa;MPa;mbar;bar;psi;psia;mmH2O;mmHg;mmHgA;mmAq;mmWG;Torr;inH2O;inHg;inHgA;ftH2O;gf/cm2;kgf/cm2;kg/cm2G;kg/cm2A;atm;kg/h;t/h;m3/h;m3/min;l/h;l/min;kl/h;kl/min;Nl/h;Nl/min;Nm3/h;Nm3/min;ACFH;ACFM;CFH;SCFM;GPH;GPM;m;mm;in;ft;kg/m3;g/cm3 |
925 |
;kPa;MPa;mbar;bar;atm;kg/h;t/h;m3/h;m3/min;l/h;l/min;kl/h;kl/min;Nl/h;Nl/min;Nm3/h;Nm3/min;m;mm;kg/m3;g/cm3 |
926 |
Enter Engr Unit: |
927 |
Enter space on the characters to be lowercase: |
928 |
This function is not supported. |
929 |
In write protect mode. |
930 |
Current power on informatin is OFF.
Select status |
931 |
OFF;ON |
932 |
Current power on informatin is ON.
Select status |
933 |
Power on info is changed to OFF |
934 |
Power on info is changed to ON |
935 |
Current power on informatin is OFF. |
936 |
Current power on informatin is ON. |
937 |
Confirm that the configuration tool supports
new universal rev.
After the universal rev is changed,
the following operations are required.
1 Exit the configuration tool.
2 Power OFF and ON the device.
3 Restart the configuration tool.
|
938 |
Current universal rev is %{universal_revision} with fld dev rev %{transmitter_revision}.
New universal rev is %{next_universal_rev} with fld dev rev %{next_device_rev}.
Are you sure to change the universal rev?
|
939 |
Current universal rev is %{universal_revision} with fld dev rev %{transmitter_revision}.
Are you sure to change the universal rev?
|
940 |
Universal rev %{test_key_4_upper1} is not supported!
|
941 |
Enter new rev number.
5: universal rev 5
7: universal rev 7
|
942 |
Number is invalid.
|
943 |
Current universal rev is %{0}.
Universal rev is not changed.
|
944 |
Current universal rev is %{universal_revision} with fld dev rev %{transmitter_revision}.
Are you sure to stay with current universal rev?
|
945 |
New rev is applied only after power OFF and ON the device.
Are you sure to change the universal rev from %{universal_revision} to %{object_universal_rev}? |
946 |
Setting in progress, please wait for several seconds.
|
947 |
Process incompleted.
|
948 |
To complete the change of universal rev:
1 Exit the configuration tool.
2 Power OFF and ON the device.
3 Restart the configuration tool.
|
949 |
Process completed.
|
950 |
Current universal rev is %{universal_revision} with fld dev rev %{transmitter_revision}.
New universal rev will be %{next_universal_rev} with fld dev rev %{next_device_rev}.
|
951 |
Current universal rev is %{universal_revision} with fld dev rev %{transmitter_revision}.
|
952 |
Select case: |
953 |
Write;Read;Coefs Clear;End |
954 |
Test Key 1 |
955 |
Test Key 2 |
956 |
Test Key 3;Test Key 4 |
957 |
Test Key 3 |
958 |
Test Key 4 |
959 |
tmp_data |
960 |
Invalid characters are included. |
961 |
Test Key 3
%{0} |
962 |
Test Key 4
%[04X]{0}%[04X]{1}
%[08X]{2} |
963 |
Now Clearing! |
964 |
Enter current password to enable to write for 10 minutes: |
965 |
Released the write protection for 10 minutes. |
966 |
If you wish to release completely, you have to change password to all of spaces. |
967 |
Enter new password to change state of write protect: |
968 |
Re-enter new password within 30 seconds: |
969 |
Changed to new password. |
970 |
It changed the state of protection related password. |