0 |
YOKOGAWA |
1 |
EJX-DRS |
2 |
Device Status |
3 |
PV out of Limits |
4 |
Non PV out of Limits |
5 |
Loop current Saturated |
6 |
Analog output and its digital representation are outside the operating range limits, and not responding to input |
7 |
Loop current Fixed |
8 |
Analog output and its digital representation are in fixed mode, and not responsive to input changes |
9 |
More Status Available |
10 |
Cold Start |
11 |
Configuration Changed |
12 |
Device Malfunction |
13 |
Maintenance Required |
14 |
Device Variable Alert |
15 |
Critical Power Failure |
16 |
Failure |
17 |
Out of Specification |
18 |
Function Check |
19 |
Field device requires maintenance. |
20 |
Any device variable is in an alarm or warning state. |
21 |
Stored power is becoming critically low. |
22 |
One or more device variables are invalid due to a malfunction in the field device. |
23 |
Deviations from the permissible ambient or process conditions have been detected that may compromise measurement or control accuracy. |
24 |
One or more device variables are temporarily invalid due to ongoing work on the device. |
25 |
Device Variable Simulation Active |
26 |
Non-Volatile Memory Defect |
27 |
Volatile Memory Defect |
28 |
Watchdog Reset Executed |
29 |
Power Supply Conditions Out of Range |
30 |
Environmental Conditions Out of Range |
31 |
Electronic Defect |
32 |
Device Configuration Locked |
33 |
The device is in simulation mode and one or more of its device variables are not representative of the process. |
34 |
The Non-Volatile memory check is invalid or maybe corrupt. |
35 |
The RAM memory check is invalid or maybe corrupt. |
36 |
A watchdog reset has been performed. |
37 |
A voltage condition is outside its allowable range. |
38 |
An internal or environmental condition is beyond acceptable limits. |
39 |
A hardware problem not related to the sensor has been detected. |
40 |
Device is in write-protect or is locked. |
41 |
Status Simulation Active |
42 |
Discrete Variable Simulation Active |
43 |
Event Notification Overflow |
44 |
Status simulation mode has been enabled and the device status and status bits are fixed and may not represent the current state of the device. |
45 |
The device is in simulation mode and one or more of its discrete variables are not representative of the process. |
46 |
The event queue for more event specification overflows resulting in an event not be recorded. |
47 |
Wired HART Enabled |
48 |
Enabled on Wired HART device connection only |
49 |
inH2O @68degF |
50 |
ftH2O @68degF |
51 |
mmH2O @68degF |
52 |
g/cm2 |
53 |
kg/cm2 |
54 |
ftH2O |
55 |
Feet of Water at 4 Degrees Celsius |
56 |
hPa |
57 |
Hectopascals |
58 |
Pres 1 Sensor Failure (AL-01) |
59 |
Module-1: Pressure sensor failed.(AL-01)
[Action]: Contact the nearest sales office or service center. |
60 |
Temp 1 Sensor Failure (AL-01) |
61 |
Module-1: Capsule temperature sensor failed.(AL-01)
[Action]: Contact the nearest sales office or service center. |
62 |
Amp T Sensor Failure (AL-02) |
63 |
Module-1: Amplifier temperature sensor failed.(AL-02)
[Action]: Replace the amplifier. Or contact sales office or service center. |
64 |
Cap 1 EEPROM Failure (AL-01) |
65 |
Module-1: Capsule EEPROM failed.(AL-01)
[Action]: Contact the nearest sales office or service center. |
66 |
Amp 1 EEPROM Failure (AL-02) |
67 |
Module-1: Amplifier EEPROM failed.(AL-02)
[Action]: Replace the amplifier. Or contact sales office or service center. |
68 |
CPU 1 Board Failure (AL-02) |
69 |
Module-1: CPU board failed.(AL-02)
[Action]: Replace the amplifier. Or contact sales office or service center. |
70 |
No Device ID |
71 |
Module-1: No Device ID is found.
[Action]: Replace the amplifier. Or contact sales office or service center. |
72 |
DP outside Limit (AL-10) |
73 |
Differential pressure exceeds limit.(AL-10)
[Action]: Check input or replace capsule when necessary. |
74 |
Pres 1 outside Limit (AL-11) |
75 |
Module-1: Input pressure is outside measurement range limit of capsule.(AL-11)
[Action]: Check input or replace capsule when necessary. |
76 |
Temp 1 outside Limit (AL-12) |
77 |
Module-1: Capsule temperature is outside range (-50 to 130 degC).(AL-12)
[Action]: Use heat insulation or make lagging to keep temperature within range. |
78 |
Amp T outside Limit (AL-13) |
79 |
Module-1: Amplifier temperature is outside range (-50 to 95 degC).(AL-13)
[Action]: Use heat insulation or make lagging to keep temperature within range. |
80 |
DP over Range (AL-30) |
81 |
Differential pressure exceeds specified range.(AL-30)
[Action]: Check input and range setting, and change them as needed. |
82 |
Pres 1 over Range (AL-31) |
83 |
Module-1: Input pressure exceeds specified range.(AL-31)
[Action]: Check input and range setting, and change them as needed. |
84 |
DP High Alarm (AL-35) |
85 |
Differential pressure exceeds specified threshold.(AL-35)
[Action]: Check input. |
86 |
DP Low Alarm (AL-36) |
87 |
Differential pressure exceeds specified threshold.(AL-36)
[Action]: Check input. |
88 |
Pres 1 High Alarm (AL-37) |
89 |
Module-1: Input pressure exceeds specified threshold.(AL-37)
[Action]: Check input. |
90 |
Pres 1 Low Alarm (AL-38) |
91 |
Module-1: Input pressure exceeds specified threshold.(AL-38)
[Action]: Check input. |
92 |
Temp 1 High Alarm (AL-39) |
93 |
Module-1: Capsule temperature exceeds specified threshold.(AL-39)
[Action]: Check input. |
94 |
Temp 1 Low Alarm (AL-40) |
95 |
Module-1: Capsule temperature exceeds specified threshold.(AL-40)
[Action]: Check input. |
96 |
Illegal DP LRV (AL-50) |
97 |
Specified value is outside of setting range.(AL-50)
[Action]: Check settings and change them as needed. |
98 |
Illegal DP URV (AL-51) |
99 |
Specified value is outside of setting range.(AL-51)
[Action]: Check settings and change them as needed. |
100 |
Illegal DP Span (AL-52) |
101 |
Specified value is outside of setting range.(AL-52)
[Action]: Check settings and change them as needed. |
102 |
DP Zero Trim Err (AL-53) |
103 |
Specified value is outside of setting range.(AL-53)
[Action]: Adjust settings and change them as needed. |
104 |
DP Span Trim Err (AL-53) |
105 |
Illegal Pres 1 LRV (AL-54) |
106 |
Module-1: Specified value is outside of setting range.(AL-54)
[Action]: Check settings and change them as needed. |
107 |
Illegal Pres 1 URV (AL-54) |
108 |
Illegal Pres 1 Span (AL-54) |
109 |
Pres 1 Zero Trim Err (AL-55) |
110 |
Module-1: Specified value is outside of setting range.(AL-55)
[Action]: Adjust settings and change them as needed. |
111 |
Pres 1 Span Trim Err (AL-55) |
112 |
S.C. Config Error (AL-60) |
113 |
Set points of signal characterization do not increase monotonically.(AL-60)
[Action]: Check settings and change them. |
114 |
Flg Temp High Alarm (AL-87) |
115 |
Module-1: Flange temperature exceeds specified threshold.(AL-87)
[Action]: 1.Check the heater failure. 2.Check the capsule temp. and amplifier temp. 3.Adjust flange temperature coefficient(Flg temp coef). |
116 |
Flg Temp Low Alarm (AL-87) |
117 |
ILBD over Range (AL-89) |
118 |
Appointed the diagnosis range outside.(AL-89)
[Action]: Check process condition. |
119 |
Invalid Ref DP (AL-88) |
120 |
Differential pressure fluctuation does not reach the reference level required to blockage detection so that no blockage detection is carried out.(AL-88)
[Action]: 1.Check process condition. 2.Obtain the reference fluctuation values again. |
121 |
Invalid Ref Pres 1 (AL-88) |
122 |
Module-1: Pressure fluctuation does not reach the reference level required to blockage detection.(AL-88)
[Action]: 1.Check process condition. 2.Obtain the reference fluctuation values again. |
123 |
Invalid Ref Pres 2 (AL-88) |
124 |
Module-2: Pressure fluctuation does not reach the reference level required to blockage detection.(AL-88)
[Action]: 1.Check process condition. 2.Obtain the reference fluctuation values again. |
125 |
Invalid Ref BlkF (AL-88) |
126 |
Blocking factor can not be used for blockage detection.(AL-88)
[Action]: 1.Check process condition. 2.Obtain the reference fluctuation values again. |
127 |
B Blocking (AL-89) |
128 |
B blocking (both-side blockage) is detected.(AL-89)
[Action]: 1.Check process and impulse line condition(both-side blockage). 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
129 |
Pres 1 Side Blocking (AL-89) |
130 |
Module-1 side blockage is detected.(AL-89)
[Action]: 1.Check process and impulse line condition(Module-1 side). 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
131 |
Pres 2 Side Blocking (AL-89) |
132 |
Module-2 side blockage is detected.(AL-89)
[Action]: 1.Check process and impulse line condition(Module-2 side). 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
133 |
Large Fluct Pres 1 (AL-89) |
134 |
Module-1: Pressure fluctuation amplitude is large.(AL-89)
[Action]: 1.Check process condition. 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
135 |
Large Fluct Pres 2 (AL-89) |
136 |
Module-2: Pressure fluctuation amplitude is large.(AL-89)
[Action]: 1.Check process condition. 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
137 |
A Blocking (AL-89) |
138 |
A blocking (single-side blockage) is detected.(AL-89)
[Action]: 1.Check process and impulse line condition(single-side blockage). 2.If there are large flow change or the change of fluid under the measured process conditions, obtain the reference value again. |
139 |
DP Simulate Mode (AL-91) |
140 |
Under simulation mode for device variable.(AL-91)
[Action]: Check simulation mode. |
141 |
Pres 1 Simulate Mode (AL-91) |
142 |
Pres 2 Simulate Mode (AL-91) |
143 |
Temp 1 Simulate Mode (AL-91) |
144 |
Temp 2 Simulate Mode (AL-91) |
145 |
PV % rnge Sim Mode (AL-91) |
146 |
Loop current Sim Mode (AL-91) |
147 |
Status Sim Mode (AL-92) |
148 |
Under simulation mode for status.(AL-92)
[Action]: Check simulation mode. |
149 |
Pres 2 Sensor Failure (AL-03) |
150 |
Module-2: Pressure sensor failed.(AL-03)
[Action]: Contact the nearest sales office or service center. |
151 |
Temp 2 Sensor Failure (AL-03) |
152 |
Module-2: Capsule temperature sensor failed.(AL-03)
[Action]: Contact the nearest sales office or service center. |
153 |
Cap 2 EEPROM Failure (AL-03) |
154 |
Module-2: Capsule EEPROM failed.(AL-03)
[Action]: Contact the nearest sales office or service center. |
155 |
Amp 2 EEPROM Failure (AL-04) |
156 |
Module-2: Amplifier EEPROM failed.(AL-04)
[Action]: Replace the amplifier. Or contact sales office or service center. |
157 |
CPU 2 Board Failure (AL-04) |
158 |
Module-2: CPU board failed.(AL-04)
[Action]: Replace the amplifier. Or contact sales office or service center. |
159 |
Module 2 Failure (AL-05) |
160 |
Module-2: Start-up sequence, power supply failed.(AL-05)
[Action]: 1.Check the cable and connection. 2.Carry out reduction measures of the communication noise. 3.Replace the amplifier. Or contact sales office or service center. |
161 |
Intercom Failure (AL-06) |
162 |
Module-2: Internal communication failed.(AL-06)
[Action]: 1.Check the cable and connection. 2.Carry out reduction measures of the communication noise. 3.Replace the amplifier. Or contact sales office or service center. |
163 |
Pres 2 outside Limit (AL-14) |
164 |
Module-2: Input pressure is outside measurement range limit of capsule.(AL-14)
[Action]: Check input or replace capsule when necessary. |
165 |
Temp 2 outside Limit (AL-15) |
166 |
Module-2: Capsule temperature is outside range (-50 to 130 degC).(AL-15)
[Action]: Use heat insulation or make lagging to keep temperature within range. |
167 |
Pres 2 over Range (AL-32) |
168 |
Module-2: Input pressure exceeds specified range.(AL-32)
[Action]: Check input and range setting, and change them as needed. |
169 |
Pres 2 High Alarm (AL-41) |
170 |
Module-2: Input pressure exceeds specified threshold.(AL-41)
[Action]: Check input. |
171 |
Pres 2 Low Alarm (AL-42) |
172 |
Module-2: Input pressure exceeds specified threshold.(AL-42)
[Action]: Check input. |
173 |
Temp 2 High Alarm (AL-43) |
174 |
Module-2: Capsule temperature exceeds specified threshold.(AL-43)
[Action]: Check input. |
175 |
Temp 2 Low Alarm (AL-44) |
176 |
Module-2: Capsule temperature exceeds specified threshold.(AL-44)
[Action]: Check input. |
177 |
Illegal Pres 2 LRV (AL-56) |
178 |
Module-2: Specified value is outside of setting range.(AL-56)
[Action]: Check settings and change them as needed. |
179 |
Illegal Pres 2 URV (AL-56) |
180 |
Illegal Pres 2 Span (AL-56) |
181 |
Pres 2 Zero Trim Err (AL-57) |
182 |
Module-2: Specified value is outside of setting range.(AL-57)
[Action]: Adjust settings and change them as needed. |
183 |
Pres 2 Span Trim Err (AL-57) |
184 |
Pres 2 Fixed Mode |
185 |
Module-2: Under pressure and temperature fix mode.
[Action]: Check fixed value mode. |
186 |
.3f |
187 |
5.3f |
188 |
Enumeration May Be Used For Manufacturer Specific Definitions |
189 |
.2f |
190 |
.4f |
191 |
.1f |
192 |
.5f |
193 |
.0f |
194 |
.6f |
195 |
QV |
196 |
Status group 0 Mask |
197 |
Status group 1 Mask |
198 |
Status group 2 Mask |
199 |
Status group 3 Mask |
200 |
Status group 4 Mask |
201 |
Status group 5 Mask |
202 |
Status group 14 Mask |
203 |
Status group 15 Mask |
204 |
Status group 16 Mask |
205 |
Status group 17 Mask |
206 |
Status group 18 Mask |
207 |
Status group 19 Mask |
208 |
Status group 20 Mask |
209 |
Status group 21 Mask |
210 |
Status group 22 Mask |
211 |
Status group 23 Mask |
212 |
Latched Status group 0 |
213 |
Latched Status group 1 |
214 |
Latched Status group 2 |
215 |
Latched Status group 3 |
216 |
Latched Status group 4 |
217 |
Latched Status group 5 |
218 |
Latched Status group 14 |
219 |
Latched Status group 15 |
220 |
Latched Status group 16 |
221 |
Latched Status group 17 |
222 |
Latched Status group 18 |
223 |
Latched Status group 19 |
224 |
Latched Status group 20 |
225 |
Latched Status group 21 |
226 |
Latched Status group 22 |
227 |
Latched Status group 23 |
228 |
Event status |
229 |
Event notification control |
230 |
Time first unack event triggered |
231 |
Event notification retry time |
232 |
Max update time |
233 |
Event debounce interval |
234 |
Device Status Mask |
235 |
Ext dev status Mask |
236 |
Diagnostic Status 0 Mask |
237 |
Diagnostic Status 1 Mask |
238 |
Latched Device Status |
239 |
Latched Ext dev status |
240 |
Latched Diagnostic Status 0 |
241 |
Latched Diagnostic Status 1 |
242 |
Latched Cfg chng count |
243 |
Event |
244 |
Rate-of-Change limit was exceeded |
245 |
Burst condition conflict |
246 |
Invalid Event Specification number |
247 |
Insufficient bandwidth |
248 |
Events |
249 |
Burst Variable Code |
250 |
Burst Variable Slot - Device variable code assigned to the slot to be read in burst mode. |
251 |
DP |
252 |
Pres 1 |
253 |
Pres 2 |
254 |
Temp 1 |
255 |
Temp 2 |
256 |
PV |
257 |
SV |
258 |
TV |
259 |
Burst Command |
260 |
Update Period |
261 |
Update period for burst message |
262 |
Max Update Period |
263 |
Maxium update period for burst message |
264 |
Burst Mode |
265 |
Trigger Mode |
266 |
Burst trigger mode |
267 |
Classification |
268 |
Burst trigger class |
269 |
Trigger Units |
270 |
Burst trigger units |
271 |
Trigger Level |
272 |
Burst trigger level |
273 |
Burst Messages |
274 |
Change PV Assgn |
275 |
Change SV Assgn |
276 |
Change TV Assgn |
277 |
Change QV Assgn |
278 |
|
279 |
Self Test- Commands the device electronics to perform a selftest. Reports any errors that occured. |
280 |
Master Reset- Commands the device electronics to reset and perform a selftest. Reports any errors that occured. |
281 |
Clear D/A trim |
282 |
Clear digital to analog trim- Resets the trim adjustment to the initial calibrated values that were set at factory. |
283 |
DP Zero trim |
284 |
DP trim |
285 |
Differential pressure trim- Executes full sensor trim with zero point adjustment by Lower Pt and span adjustment by Upper Pt. |
286 |
Clear DP trim |
287 |
Clear differential pressure sensor trim- Resets the trim adjustment to the initial calibrated values that were set at factory. |
288 |
Pres 1 trim |
289 |
Pressure 1 trim- Executes full sensor trim with zero point adjustment by Lower Pt and span adjustment by Upper Pt. |
290 |
Clear Pres 1 trim |
291 |
Clear pressure 1 sensor trim- Resets the trim adjustment to the initial calibrated values that were set at factory. |
292 |
Pres 2 trim |
293 |
Pressure 2 trim- Executes full sensor trim with zero point adjustment by Lower Pt and span adjustment by Upper Pt. |
294 |
Clear Pres 2 trim |
295 |
Clear pressure 2 sensor trim- Resets the trim adjustment to the initial calibrated values that were set at factory. |
296 |
Error log view |
297 |
Error log view- Displays the error records from log1(latest) to log4. |
298 |
Error log clear |
299 |
Error log clear- Clears the error records. |
300 |
X Y initialize |
301 |
Initialize the X,Y coordinate point of the special curve. |
302 |
Set Engr unit |
303 |
Set engineering unit- Selects the engineering unit from the list. |
304 |
Modify Engr unit |
305 |
Modify engineering unit- Modifies the engineering unit or sets a customized engineering unit. Enter a series of up to eight alphanumeric characters, spaces, or slashes (only first six characters are shown on LCD). Note that if you already select the unit at 'Set Engineering Unit,' the unit appears as a default. Then re-enter the unit but enter a space instead of a character to display the character in lowercase on LCD. For example, in order to show 'aBCd' on LCD, enter 'ABCD' first, then enter '_BC_'. |
306 |
Test Key |
307 |
Enable wrt 10min |
308 |
Enable parameter change for 10 min.- releases the software write protection for 10 minutes when the password is entered. |
309 |
New password |
310 |
New password- Sets or changes the password for software write protection. |
311 |
Aborting |
312 |
Exiting |
313 |
Set Diag Mode |
314 |
Reset Cfg chng flag |
315 |
Reset Configuration changed flag. |
316 |
Device vars simulate |
317 |
Simulate device variable with status. |
318 |
Set Burst Period |
319 |
Configure Burst Period |
320 |
Set Burst Trigger |
321 |
Configure Burst Trigger |
322 |
Set Event Notification Timing |
323 |
Configure Event Notification Timing |
324 |
Event Number |
325 |
Acknowledge Event Notification |
326 |
Acknowledge the latched event instance that associated with the event specification number. |
327 |
Small Char. did not convert successfully. |
328 |
Excess Correction Attemped |
329 |
Not write protect mode |
330 |
The First Password Accepted |
331 |
Offline |
332 |
Upload variables |
333 |
Maintenance |
334 |
View device vars |
335 |
Output vars |
336 |
PV is |
337 |
SV is |
338 |
TV is |
339 |
QV is |
340 |
Device vars and Status |
341 |
Time Stamp |
342 |
Error log |
343 |
Analog output trim |
344 |
Trim info |
345 |
Diag Parameters |
346 |
ILBD Parameters |
347 |
Status |
348 |
Diag Variables |
349 |
Diag Reference |
350 |
Fluct Variables |
351 |
Configuration |
352 |
Diag Lim |
353 |
Diag Ref Lim |
354 |
HT Parameters |
355 |
Diag Output |
356 |
PV keypad input |
357 |
DP signal setup |
358 |
When PV is Differential Pressure, output signal setting is effective. |
359 |
DP setup |
360 |
Pres 1 setup |
361 |
Pres 2 setup |
362 |
Temp setup |
363 |
T.Z. Cmp menu |
364 |
Fixed value |
365 |
A/G Setup |
366 |
S.C. menu |
367 |
Signal Characterization menu |
368 |
X Y values |
369 |
Xn & Yn values (n= 1 to 30) |
370 |
Process Alerts |
371 |
DP Alert |
372 |
Pres 1 Alert |
373 |
Pres 2 Alert |
374 |
Temp 1 Alert |
375 |
Temp 2 Alert |
376 |
Display condition |
377 |
Disp select |
378 |
Disp condition |
379 |
Engr disp range |
380 |
Others |
381 |
Revision numbers |
382 |
Additional info |
383 |
Additional information |
384 |
Module 1 info |
385 |
Module 2 info |
386 |
Module 1 sensor information |
387 |
Module 2 sensor information |
388 |
Wrt protect menu |
389 |
Update period |
390 |
Burst Condition |
391 |
Burst Message 1 |
392 |
Burst Message 2 |
393 |
Burst Message 3 |
394 |
Burst Variables |
395 |
Burst device variables |
396 |
Event Notification |
397 |
Event Condition |
398 |
Event Mask |
399 |
Acknowledge |
400 |
Function control |
401 |
DP unit |
402 |
Differential Pressure - Calculated value from Pressure 1 and Pressure 2 |
403 |
DP Data Quality |
404 |
DP Limit Status |
405 |
DP Family status |
406 |
Not supported |
407 |
DP Classification |
408 |
DP update time period |
409 |
Differential Pressure update time period |
410 |
0 ms |
411 |
45 ms |
412 |
90 ms |
413 |
180 ms |
414 |
360 ms |
415 |
1 s |
416 |
DP Family |
417 |
DP damp |
418 |
6.2f |
419 |
DP write dev var code |
420 |
Write Device Variable Code |
421 |
DP Property |
422 |
Device variable properties |
423 |
Device Variable is being simulated |
424 |
Device Variable is not calculated by Field Device |
425 |
Device Variable is calculated by Field Device |
426 |
Data Quality |
427 |
Limit Status |
428 |
Update time period |
429 |
Update time period help |
430 |
Write dev var code |
431 |
Properties |
432 |
Alert Mode |
433 |
HI/LO Alarm Mode |
434 |
Hi Alert |
435 |
High Alarm Setpoint |
436 |
Lo Alert |
437 |
Low Alarm Setpoint |
438 |
LTP |
439 |
Lower Trim Point |
440 |
UTP |
441 |
Upper Trim Point |
442 |
LTD |
443 |
Lower Trim Deviation |
444 |
UTD |
445 |
Upper Trim Deviation |
446 |
Pres 1 URV |
447 |
Pressure 1 Upper Range Value- Defines the operational endpoint from which the 100% point of the Percent Range are derived. |
448 |
Pres 1 LRV |
449 |
Pressure 1 Lower Range Value- Defines the operational endpoint from which the 0% point of the Percent Range are derived. |
450 |
Pres 1 unit |
451 |
Pressure 1 Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Pressure of Module 1. |
452 |
Pressure 1 - Measured pressure value of Module 1 |
453 |
Pres 1 Data Quality |
454 |
Pres 1 Limit Status |
455 |
Pressure Family status |
456 |
Pressure Classification |
457 |
Pres update time period |
458 |
Pressure update time period |
459 |
Pressure Family |
460 |
Pres 1 USL |
461 |
Pressure 1 Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value for the pressure of Module 1. |
462 |
Pres 1 LSL |
463 |
Pressure 1 Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value for the pressure of Module 1. |
464 |
Pres 1 Min span |
465 |
Pressure 1 Minimum Span- Defines the minimum usable span for the pressure of Module 1. |
466 |
Pres 1 damp |
467 |
Pressure 1 Damping Value- Damping time constant applied to the Digital Value representation for the pressure of Module 1. The units of this variable are always in seconds. |
468 |
Pres 1 snsr s/n |
469 |
Pressure 1 sensor s/n |
470 |
7d |
471 |
Pres 1 write dev var code |
472 |
Pres 1 Property |
473 |
Pres 2 URV |
474 |
Pressure 2 Upper Range Value- Defines the operational endpoint from which the 100% point of the Percent Range are derived. |
475 |
Pres 2 LRV |
476 |
Pressure 2 Lower Range Value- Defines the operational endpoint from which the 0% point of the Percent Range are derived. |
477 |
Pres 2 unit |
478 |
Pressure 2 Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Pressure of Module 2. |
479 |
Pressure 2 - Measured pressure value of Module 2 |
480 |
Pres 2 Data Quality |
481 |
Pres 2 Limit Status |
482 |
Pres 2 USL |
483 |
Pressure 2 Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value for the pressure of Module 2. |
484 |
Pres 2 LSL |
485 |
Pressure 2 Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value for the pressure of Module 2. |
486 |
Pres 2 Min span |
487 |
Pressure 2 Minimum Span- Defines the minimum usable span for the pressure of Module 2. |
488 |
Pres 2 damp |
489 |
Pressure 2 Damping Value- Damping time constant applied to the Digital Value representation for the pressure of Module 2. The units of this variable are always in seconds. |
490 |
Pres 2 snsr s/n |
491 |
Pres 2 write dev var code |
492 |
Pres 2 Property |
493 |
Temp unit |
494 |
Field Device Variable Unit- Digital unit that the variable will be displayed with. Capsule Temperature- Temperature associated with the sensor that is responsible for a process measurement. |
495 |
Temperature 1 - Capsule temperature of Module 1. Temperature measured at sensor capsule. |
496 |
Temp 1 Data Quality |
497 |
Temp 1 Limit Status |
498 |
Temp family status |
499 |
Temp Classification |
500 |
Temp update time period |
501 |
Temperature update time period |
502 |
Temp Family |
503 |
Temp USL |
504 |
Temp LSL |
505 |
Temp min span |
506 |
Temp snsr s/n |
507 |
Temp write dev var code |
508 |
Temp Property |
509 |
Temperature 2 - Capsule temperature of Module 2. Temperature measured at sensor capsule. |
510 |
Temp 2 Data Quality |
511 |
Temp 2 Limit Status |
512 |
Amp temp |
513 |
Amplifier temperature of Module 1 |
514 |
Loop current unit |
515 |
Loop current Data Quality |
516 |
Loop current Limit Status |
517 |
Loop current Family status |
518 |
Loop current Classification |
519 |
Loop current update time period |
520 |
Loop current Family |
521 |
Loop current USL |
522 |
Loop current LSL |
523 |
Loop current min span |
524 |
Loop current damp |
525 |
Loop current s/n |
526 |
Loop current write dev var code |
527 |
Loop current Property |
528 |
PV % rnge Unit |
529 |
PV % rnge Data Quality |
530 |
PV % rnge Limit Status |
531 |
PV % rnge Family status |
532 |
PV % rnge Classification |
533 |
PV % rnge update time period |
534 |
PV % rnge Family |
535 |
PV % rnge USL |
536 |
PV % rnge LSL |
537 |
PV % rnge min span |
538 |
PV % rnge damp |
539 |
PV % rnge s/n |
540 |
PV % rnge write dev var code |
541 |
PV % rnge Property |
542 |
DP LTP |
543 |
Lower differential pressure trim point- Applied pressure at which the last lower differential pressure trim was performed. |
544 |
DP UTP |
545 |
Upper differential pressure trim point- Applied pressure at which the last upper differential pressure trim was performed. |
546 |
DP LTD |
547 |
Lower differential pressure trim deviation- Deviation from the original value. |
548 |
DP UTD |
549 |
Upper differential pressure trim deviation- Deviation from the original value. |
550 |
Pres 1 LTP |
551 |
Lower pressure 1 trim point- Applied pressure at which the last lower pressure trim was performed. |
552 |
Pres 1 UTP |
553 |
Upper pressure 1 trim point- Applied pressure at which the last upper pressure trim was performed. |
554 |
Pres 1 LTD |
555 |
Lower pressure 1 trim deviation- Deviation from the original value. |
556 |
Pres 1 UTD |
557 |
Upper pressure 1 trim deviation- Deviation from the original value. |
558 |
Pres 2 LTP |
559 |
Lower pressure 2 trim point- Applied pressure at which the last lower pressure trim was performed. |
560 |
Pres 2 UTP |
561 |
Upper pressure 2 trim point- Applied pressure at which the last upper pressure trim was performed. |
562 |
Pres 2 LTD |
563 |
Lower pressure 2 trim deviation- Deviation from the original value. |
564 |
Pres 2 UTD |
565 |
Upper pressure 2 trim deviation- Deviation from the original value. |
566 |
Trim Who |
567 |
Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record who to trim the device. |
568 |
Trim Date |
569 |
Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record when the latest trim is done for the device. |
570 |
Trim Loc |
571 |
Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record where the latest trim is done for the device. |
572 |
Trim Desc |
573 |
Trim information- Text that is associated with the trim information. This text can be used by the user in any way, and there is no recommended use. |
574 |
DP for trim |
575 |
Differential Pressure value or % value for Trim |
576 |
Pres1 for trim |
577 |
Pressure value or % value for Trim of Module 1 |
578 |
Pres2 for trim |
579 |
Pressure value or % value for Trim of Module 2 |
580 |
Trim Clear Code |
581 |
Not Clear |
582 |
ALL |
583 |
Low cut |
584 |
Low cut- Sets the range in vicinity of 0% within which the low cut function is activated according to the selected low cut mode. |
585 |
5.2f |
586 |
Low cut mode |
587 |
Low cut mode- Selects the type of the low cut function to be used; LINEAR or ZERO. |
588 |
Pres 1/2 Swap |
589 |
Pres 1/Pres 2 swap- Reverses the high pressure side and low pressure side of the transmitter. |
590 |
A/G select |
591 |
Absolute/gauge selection- Type of Static pressure variable. |
592 |
Gauge |
593 |
Absolute |
594 |
Atm. Pres val |
595 |
Atmospheric Pressure Value- Sets the coefficient value used for the conversion of the measured absolute pressure value into gauge pressure value. |
596 |
Bi-dir mode |
597 |
Bi-directional flow measurement setup- Enables/disables bi-directional flow measurement mode. In this mode, when the pressure equivalent to 0% is applied, the device outputs 50%. Applicable only for differential pressure transmitters. |
598 |
Normal Mode |
599 |
Bi-Direction Mode |
600 |
Input filter mode |
601 |
T.Z. Cmp mode 1 |
602 |
Temperature 1 Zero compensation mode- Enables/disables temperature zero compensation. |
603 |
T.Z. Cmp mode 2 |
604 |
Temperature 2 Zero compensation mode- Enables/disables temperature zero compensation. |
605 |
Temp 1 zero |
606 |
Temperature 1 Zero shift compensation- Defines the value to be used for temperature zero shift compensation. |
607 |
7.3f |
608 |
%/degC |
609 |
Temp 2 zero |
610 |
Temperature 2 Zero shift compensation- Defines the value to be used for temperature zero shift compensation. |
611 |
Pressure and Temperature values of Module 2 are set to the fixed values. |
612 |
Fall Back |
613 |
Pres 2 fixed val |
614 |
Pressure value of Module 2 in the fixed mode |
615 |
Temp 2 fixed val |
616 |
Temperature value of Module 2 in the fixed mode |
617 |
Num of points |
618 |
Number of break points- Sets the number of points for special curve. |
619 |
2u |
620 |
X Start |
621 |
Displays the start point of X. |
622 |
Y Start |
623 |
Displays the start point of Y. |
624 |
X End |
625 |
Displays the end point of X. |
626 |
Y End |
627 |
Displays the end point of Y. |
628 |
X1 |
629 |
X1 Value |
630 |
6.3f |
631 |
X2 |
632 |
X2 Value |
633 |
X3 |
634 |
X3 Value |
635 |
X4 |
636 |
X4 Value |
637 |
X5 |
638 |
X5 Value |
639 |
X6 |
640 |
X6 Value |
641 |
X7 |
642 |
X7 Value |
643 |
X8 |
644 |
X8 Value |
645 |
X9 |
646 |
X9 Value |
647 |
X10 |
648 |
X10 Value |
649 |
X11 |
650 |
X11 Value |
651 |
X12 |
652 |
X12 Value |
653 |
X13 |
654 |
X13 Value |
655 |
X14 |
656 |
X14 Value |
657 |
X15 |
658 |
X15 Value |
659 |
X16 |
660 |
X16 Value |
661 |
X17 |
662 |
X17 Value |
663 |
X18 |
664 |
X18 Value |
665 |
X19 |
666 |
X19 Value |
667 |
X20 |
668 |
X20 Value |
669 |
X21 |
670 |
X21 Value |
671 |
X22 |
672 |
X22 Value |
673 |
X23 |
674 |
X23 Value |
675 |
X24 |
676 |
X24 Value |
677 |
X25 |
678 |
X25 Value |
679 |
X26 |
680 |
X26 Value |
681 |
X27 |
682 |
X27 Value |
683 |
X28 |
684 |
X28 Value |
685 |
X29 |
686 |
X29 Value |
687 |
X30 |
688 |
X30 Value |
689 |
Y1 |
690 |
Y1 Value |
691 |
Y2 |
692 |
Y2 Value |
693 |
Y3 |
694 |
Y3 Value |
695 |
Y4 |
696 |
Y4 Value |
697 |
Y5 |
698 |
Y5 Value |
699 |
Y6 |
700 |
Y6 Value |
701 |
Y7 |
702 |
Y7 Value |
703 |
Y8 |
704 |
Y8 Value |
705 |
Y9 |
706 |
Y9 Value |
707 |
Y10 |
708 |
Y10 Value |
709 |
Y11 |
710 |
Y11 Value |
711 |
Y12 |
712 |
Y12 Value |
713 |
Y13 |
714 |
Y13 Value |
715 |
Y14 |
716 |
Y14 Value |
717 |
Y15 |
718 |
Y15 Value |
719 |
Y16 |
720 |
Y16 Value |
721 |
Y17 |
722 |
Y17 Value |
723 |
Y18 |
724 |
Y18 Value |
725 |
Y19 |
726 |
Y19 Value |
727 |
Y20 |
728 |
Y20 Value |
729 |
Y21 |
730 |
Y21 Value |
731 |
Y22 |
732 |
Y22 Value |
733 |
Y23 |
734 |
Y23 Value |
735 |
Y24 |
736 |
Y24 Value |
737 |
Y25 |
738 |
Y25 Value |
739 |
Y26 |
740 |
Y26 Value |
741 |
Y27 |
742 |
Y27 Value |
743 |
Y28 |
744 |
Y28 Value |
745 |
Y29 |
746 |
Y29 Value |
747 |
Y30 |
748 |
Y30 Value |
749 |
Tank memo |
750 |
Memorandum of the Tank. |
751 |
Auto recover |
752 |
Automatic recover- Defines if the device automatically returns to normal operation without restarting or not, once after it recovers from the sensor error status. |
753 |
AO lower limit |
754 |
Analog output lower limit- Sets the lower limit value for analog output. |
755 |
AO upper limit |
756 |
Analog output upper limit- Sets the upper limit value for analog output. |
757 |
DP alert mode |
758 |
Selects alert mode for differential pressure alarm. |
759 |
Hi. Al Detect |
760 |
Lo. Al Detect |
761 |
Hi/Lo. Al Detect |
762 |
DP Hi alert val |
763 |
Sets threshold value for differential pressure high alarm. |
764 |
DP Lo alert val |
765 |
Sets threshold value for differential pressure low alarm. |
766 |
Pres 1 alert mode |
767 |
Selects alert mode for pressure 1 alarm. |
768 |
Pres 1 Hi alert val |
769 |
Sets threshold value for pressure 1 high alarm. |
770 |
Pres 1 Lo alert val |
771 |
Sets threshold value for pressure 1 low alarm. |
772 |
Pres 2 alert mode |
773 |
Selects alert mode for pressure 2 alarm. |
774 |
Pres 2 Hi alert val |
775 |
Sets threshold value for pressure 2 high alarm. |
776 |
Pres 2 Lo alert val |
777 |
Sets threshold value for pressure 2 low alarm. |
778 |
Temp 1 alert mode |
779 |
Selects alert mode for capsule temperature 1 alarm. |
780 |
Temp 1 Hi alert val |
781 |
Sets threshold value for capsule temperature 1 high alarm. Process temperature limit is -40 to 120 degC. |
782 |
4.0f |
783 |
Temp 1 Lo alert val |
784 |
Sets threshold value for capsule temperature 1 low alarm. Process temperature limit is -40 to 120 degC. |
785 |
Temp 2 alert mode |
786 |
Selects alert mode for capsule temperature 2 alarm. |
787 |
Temp 2 Hi alert val |
788 |
Sets threshold value for capsule temperature 2 high alarm. Process temperature limit is -40 to 120 degC. |
789 |
Temp 2 Lo alert val |
790 |
Sets threshold value for capsule temperature 2 low alarm. Process temperature limit is -40 to 120 degC. |
791 |
Squawk control codes |
792 |
Off |
793 |
On |
794 |
Once |
795 |
Bar indicator |
796 |
Bar indicator for PV %- Defines to show/hide bar indicator on LCD. |
797 |
Power on info |
798 |
Power on information- Display device information on LCD in power on. |
799 |
Disp Out 1 |
800 |
LCD output 1- Defines the variable to be shown on LCD. |
801 |
PV % |
802 |
Engr |
803 |
Disp Out 2 |
804 |
LCD output 2- Defines the variable to be shown on LCD. |
805 |
Disp Out 3 |
806 |
LCD output 3- Defines the variable to be shown on LCD. |
807 |
Disp Out 4 |
808 |
LCD output 4- Defines the variable to be shown on LCD. |
809 |
Disp DP % fnctn |
810 |
Display DP % function- Defines the display mode for differential pressure variable in %; Linear or Squareroot. |
811 |
Disp PV % reso |
812 |
Display PV % resolution- Defines the display resolution level for PV % rnge; normal or high resolution. |
813 |
High Resolution |
814 |
DP disp point |
815 |
DP display decimal position- Defines the decimal point position for the differential pressure variable display. |
816 |
0 |
817 |
1 |
818 |
2 |
819 |
3 |
820 |
4 |
821 |
Pres 1 disp point |
822 |
Pressure 1 display decimal point position- Defines the decimal point position for the pressure 1 variable display. |
823 |
Pres 2 disp point |
824 |
Pressure 2 display decimal point position- Defines the decimal point position for the pressure 2 variable display. |
825 |
Engr disp |
826 |
Engineering display- Process variable displayed in user scale and unit. |
827 |
Engr exp |
828 |
Engineering display exponents- Exponents for user scale display. |
829 |
x1 |
830 |
x10 |
831 |
x100 |
832 |
x1000 |
833 |
Engr unit |
834 |
Engineering unit- Engineering unit for user scale display. |
835 |
Engr LRV |
836 |
Engineering display lower range value- Sets the lower range value equivalent to 0% for user scale display. |
837 |
Engr URV |
838 |
Engineering display upper range value- Sets the upper range value equivalent to 100% for user scale display. |
839 |
Engr point |
840 |
Engineering display decimal position- Defines the decimal point position for user scale display. |
841 |
Engineer Unit Select Code for Easy Setting |
842 |
psia |
843 |
mmHgA |
844 |
mmAq |
845 |
mmWG |
846 |
Torr |
847 |
inHgA |
848 |
gf/cm2 |
849 |
kgf/cm2 |
850 |
kg/cm2G |
851 |
kg/cm2A |
852 |
t/h |
853 |
m3/h |
854 |
m3/min |
855 |
l/h |
856 |
l/min |
857 |
kl/h |
858 |
kl/min |
859 |
Nl/h |
860 |
Nl/min |
861 |
Nm3/h |
862 |
Nm3/min |
863 |
ACFH |
864 |
ACFM |
865 |
SCFH |
866 |
SCFM |
867 |
GPH |
868 |
GPM |
869 |
kg/m3 |
870 |
g/cm3 |
871 |
Engineer Unit of Capital Letter |
872 |
Small Character of Engineer Unit |
873 |
Product code 1 |
874 |
Product MS code |
875 |
Product code 2 |
876 |
Ext SW |
877 |
External zero-adjustment permission- Enables/disables external zero adjustment. |
878 |
Disabled |
879 |
Enabled |
880 |
SI Option |
881 |
OFF |
882 |
ON |
883 |
Option Password |
884 |
Activation Key for Optional Function. |
885 |
MS code 1 -1 |
886 |
Module 1, MS code 1- Model and Suffix codes. |
887 |
MS code 1 -2 |
888 |
Module 1, MS code 2- Part of the suffix codes, following code 1. |
889 |
MS code 1 -3 |
890 |
Module 1, MS code 3- For memo. Combination product codes, etc. |
891 |
Serial No. |
892 |
Serial number- Displays the serial number of the device. |
893 |
Extra No. |
894 |
Extra number- Reference number for special customization. |
895 |
Mftr Date |
896 |
Manufacturing date- Displays the date of manufacturing the device. |
897 |
Style No. |
898 |
Style code- Displays the style code of the device. |
899 |
Software rev |
900 |
Module type |
901 |
Pressure |
902 |
Range code |
903 |
Pressure Sensor Range Code |
904 |
M |
905 |
H |
906 |
L |
907 |
A |
908 |
B |
909 |
C |
910 |
E |
911 |
V |
912 |
D |
913 |
Isoltr matl 1 |
914 |
Fill fluid 1 |
915 |
Si Oil |
916 |
F Oil |
917 |
Gasket matl 1 |
918 |
Gasket Material- Construction material of a seal that exists between the module and flange. |
919 |
Drain vent matl 1 |
920 |
Duplex SST |
921 |
Process Conn matl 1 |
922 |
Process Connector Material- Construction material of the process connector. |
923 |
Process Conn type 1 |
924 |
Process Connector Type- Hardware, adjacent to the sensor, that physically connects the process to the sensor. |
925 |
Thread |
926 |
Process Conn size 1 |
927 |
Process Connector Size- Size and standard of the process connector. |
928 |
ANSI3, C150 |
929 |
ANSI3, C300 |
930 |
ANSI3, C600 |
931 |
ANSI4, C150 |
932 |
ANSI4, C300 |
933 |
ANSI2, C150 |
934 |
ANSI2, C300 |
935 |
ANSI2, C600 |
936 |
DIN80, PN10/16 |
937 |
DIN80, PN25/40 |
938 |
DIN80, PN64 |
939 |
DIN100, PN10/16 |
940 |
DIN100, PN25/40 |
941 |
DIN50, PN10/16 |
942 |
DIN50, PN25/40 |
943 |
DIN50, PN64 |
944 |
ANSI 150 |
945 |
ANSI 300 |
946 |
ANSI 600 |
947 |
DIN 10/16 |
948 |
DIN 25 |
949 |
DIN 40 |
950 |
1/2NPT Female |
951 |
1/4NPT Female |
952 |
Rc 1/2 Female |
953 |
1/2NPT Male |
954 |
G 1/2 Male |
955 |
M2O * 1.5 Male |
956 |
R 1/2 Male |
957 |
Num of RS 1 |
958 |
RS type 1 |
959 |
Extension |
960 |
HTV-W |
961 |
HTV-E |
962 |
RS isoltr matl 1 |
963 |
RS fill fluid 1 |
964 |
Remote Seal Fill Fluid- Fluid material in the device remote seal. |
965 |
Silicone |
966 |
SH704 |
967 |
SH705 |
968 |
Ethy Gly/H2O |
969 |
Prop Gly/H2O |
970 |
MS code 2 -1 |
971 |
Module 2, MS code 1- Model and Suffix codes. |
972 |
MS code 2 -2 |
973 |
Module 2, MS code 2- Part of the suffix codes, following code 1. |
974 |
MS code 2 -3 |
975 |
Module 2, MS code 3- For memo. Combination product codes, etc. |
976 |
Module rev |
977 |
Isoltr matl 2 |
978 |
Fill fluid 2 |
979 |
Gasket matl 2 |
980 |
Drain vent matl 2 |
981 |
Process Conn matl 2 |
982 |
Process Conn type 2 |
983 |
Process Conn size 2 |
984 |
Num of RS 2 |
985 |
RS type 2 |
986 |
RS isoltr matl 2 |
987 |
RS fill fluid 2 |
988 |
Keyword for Test Mode |
989 |
Data No. for Test |
990 |
Data1 for Test |
991 |
Data2 for Test |
992 |
04X |
993 |
08X |
994 |
Error Record Selection Code |
995 |
Log1 |
996 |
Latest |
997 |
Log2 |
998 |
Log3 |
999 |
Log4 |
1000 |
Oldest |
1001 |
Error Rec 0 |
1002 |
Error Record 0 |
1003 |
2X |
1004 |
Error Rec 1 |
1005 |
Error Record 1 |
1006 |
Error Rec 2 |
1007 |
Error Record 2 |
1008 |
Error Rec 3 |
1009 |
Error Record 3 |
1010 |
Error Rec 4 |
1011 |
Error Record 4 |
1012 |
Error Rec 5 |
1013 |
Error Record 5 |
1014 |
Error Rec 6 |
1015 |
Error Record 6 |
1016 |
Error Rec 7 |
1017 |
Error Record 7 |
1018 |
Error Rec 8 |
1019 |
Error Record 8 |
1020 |
Error Rec 9 |
1021 |
Error Record 9 |
1022 |
Error Rec 10 |
1023 |
Error Record 10 |
1024 |
Error Rec 11 |
1025 |
Error Record 11 |
1026 |
Error Rec 12 |
1027 |
Error Record 12 |
1028 |
Error Rec 13 |
1029 |
Error Record 13 |
1030 |
Error Rec 14 |
1031 |
Error Record 14 |
1032 |
Error Rec 15 |
1033 |
Error Record 15 |
1034 |
Data Selection Code |
1035 |
VALUE 1 |
1036 |
Value 1 |
1037 |
VALUE 2 |
1038 |
Value 2 |
1039 |
Space for 8 characters |
1040 |
Software seal |
1041 |
Software seal- Displays whether or not a master password was used (Break). |
1042 |
Break |
1043 |
Keep |
1044 |
Test Auto Release Time |
1045 |
10 min |
1046 |
30 min |
1047 |
60 min |
1048 |
3 hour |
1049 |
6 hour |
1050 |
12 hour |
1051 |
Diag Error |
1052 |
Diag Error Status. |
1053 |
Flg Temp High Alarm |
1054 |
Flg Temp Low Alarm |
1055 |
ILBD over Range |
1056 |
Invalid Ref DP |
1057 |
Invalid Ref Pres 1 |
1058 |
Invalid Ref Pres 2 |
1059 |
Invalid Ref BlkF |
1060 |
B Blocking |
1061 |
Pres 1 Side Blocking |
1062 |
Pres 2 Side Blocking |
1063 |
Large Fluct Pres 1 |
1064 |
Large Fluct Pres 2 |
1065 |
A Blocking |
1066 |
Diag Option |
1067 |
Bit mask for Alarm against Diag Error Status. |
1068 |
Diag Applicable |
1069 |
Diag Applicable. |
1070 |
Diag Mode |
1071 |
Diag Mode. |
1072 |
Stop |
1073 |
Calculation |
1074 |
Reference |
1075 |
Diag Period |
1076 |
Diag Period. |
1077 |
.0d |
1078 |
Diag Supp Count |
1079 |
Diag Alarm Suppression Count. |
1080 |
Diag DPComp |
1081 |
Flow Compensation for Ratio of Root fluct DP. |
1082 |
Compensation |
1083 |
Non-Compensation |
1084 |
Diag Description |
1085 |
Diag Description. |
1086 |
Ratio fDP Status |
1087 |
Ratio of Root fluct DP for Reference with Compensation Status. |
1088 |
Sensor Failure |
1089 |
Device Failure |
1090 |
Uncertain |
1091 |
Invalid Ref |
1092 |
Good |
1093 |
Ratio fDP |
1094 |
Ratio of Root fluct DP for Reference with Compensation. |
1095 |
Ratio fP2 Status |
1096 |
Ratio of Root fluct Pres 2 for Reference Status. |
1097 |
Ratio fP2 |
1098 |
Ratio of Root fluct Pres 2 for Reference. |
1099 |
Ratio fP1 Status |
1100 |
Ratio of Root fluct Pres 1 for Reference Status. |
1101 |
Ratio fP1 |
1102 |
Ratio of Root fluct Pres 1 for Reference. |
1103 |
CRatio fDP Status |
1104 |
Compensated Ratio of Root fluct DP for Reference Status. |
1105 |
CRatio fDP |
1106 |
Compensated Ratio of Root fluct DP for Reference. |
1107 |
NRatio fDP Status |
1108 |
Non-Compensated Ratio of Root fluct DP for Reference Status. |
1109 |
NRatio fDP |
1110 |
Non-Compensated Ratio of Root fluct DP for Reference. |
1111 |
fDP Status |
1112 |
fluct DP Status. |
1113 |
fDP |
1114 |
fluct DP - Differential Pressure fluctuation. |
1115 |
.3e |
1116 |
fP2 Status |
1117 |
fluct Pres 2 Status. |
1118 |
fP2 |
1119 |
fluct Pres 2 - Pressure 2 fluctuation. |
1120 |
fP1 Status |
1121 |
fluct Pres 1 Status. |
1122 |
fP1 |
1123 |
fluct Pres 1 - Pressure 1 fluctuation. |
1124 |
BlkF Status |
1125 |
Blocking Factor Status. |
1126 |
BlkF |
1127 |
Blocking Factor (Blocked Degree) - Degree to which either impulse line is being blocked. |
1128 |
DPAvg Status |
1129 |
DPAvg Status. |
1130 |
DPAvg |
1131 |
Average Value of Differential Pressure. |
1132 |
Ref fDP Status |
1133 |
Reference fluct DP Status. |
1134 |
Ref fDP |
1135 |
Reference fluct DP. |
1136 |
10g |
1137 |
Ref fP2 Status |
1138 |
Reference fluct Pres 2 Status. |
1139 |
Ref fP2 |
1140 |
Reference fluct Pres 2. |
1141 |
Ref fP1 Status |
1142 |
Reference fluct Pres 1 Status. |
1143 |
Ref fP1 |
1144 |
Reference fluct Pres 1. |
1145 |
Ref BlkF Status |
1146 |
Reference Blocking Factor Status. |
1147 |
Ref BlkF |
1148 |
Reference Blocking Factor. |
1149 |
Ref DPAvg Status |
1150 |
Reference DPAvg Status. |
1151 |
Ref DPAvg |
1152 |
Reference DPAvg. |
1153 |
Lim fDPmax |
1154 |
Diag Limit fluct DP max. |
1155 |
Lim fDPmin |
1156 |
Diag Limit fluct DP min. |
1157 |
Lim fP2max |
1158 |
Diag Limit fluct Pres 2 max. |
1159 |
Lim fP2min |
1160 |
Diag Limit fluct Pres 2 min. |
1161 |
Lim fP1max |
1162 |
Diag Limit fluct Pres 1 max. |
1163 |
Lim fP1min |
1164 |
Diag Limit fluct Pres 1 min. |
1165 |
Lim BlkFmax |
1166 |
Diag Limit Blocking Factor max. |
1167 |
Lim BlkFmin |
1168 |
Diag Limit Blocking Factor min. |
1169 |
Lim DPAvgmax |
1170 |
Diag Limit DPAvg max. |
1171 |
Lim DPAvgmin |
1172 |
Diag Limit DPAvg min. |
1173 |
Ref Lim fDPmin |
1174 |
Reference Limit fluct DP min. |
1175 |
Ref Lim fPmin |
1176 |
Reference Limit fluct Pres min. |
1177 |
Ref Lim BlkFmax |
1178 |
Reference Limit Blocking Factor max. |
1179 |
Flg temp |
1180 |
Flange Temperature - Calculated value from Amplifire temperature and Capsule temperature of Module 1. |
1181 |
Flg temp coef |
1182 |
Flange Temperature Coefficient |
1183 |
Flg temp Hi alert val |
1184 |
Flange Temperature Hi Alert Value. |
1185 |
Flg temp Lo alert val |
1186 |
Flange Temperature Lo Alert Value. |
1187 |
Diag Out Option |
1188 |
Diag Analog Output Option. |
1189 |
Burnout |
1190 |
Fall back |
1191 |
Diag Fixed Out Val |
1192 |
Diag Fixed Analog Output Value. |
1193 |
Reset condensed status map |
1194 |
Reset the Condensed Status Map to the default values. |
1195 |
Condensed status map |
1196 |
Field Device Status |
1197 |
Status group 0 |
1198 |
Device Specific Status 0 [Hardware Failure] |
1199 |
Status group 1 |
1200 |
Device Specific Status 1 [Hardware Failure] |
1201 |
Status group 2 |
1202 |
Device Specific Status 2 [Transducer Status] |
1203 |
Status group 3 |
1204 |
Device Specific Status 3 [Transducer Status] |
1205 |
Status group 4 |
1206 |
Device Specific Status 4 [Transducer Status] |
1207 |
Status group 5 |
1208 |
Device Specific Status 5 [Configuration] |
1209 |
Ext dev status |
1210 |
Extended Field Device Status |
1211 |
Device Diagnostic Status 0 |
1212 |
Standardized Status 0 |
1213 |
Device Diagnostic Status 1 |
1214 |
Standardized Status 1 |
1215 |
Status group 14 |
1216 |
Device Specific Status 14 [Configuration] |
1217 |
Status group 15 |
1218 |
Device Specific Status 15 [Diagnostics] |
1219 |
Status group 16 |
1220 |
Device Specific Status 16 [Diagnostics] |
1221 |
Status group 17 |
1222 |
Device Specific Status 17 [Diagnostics] |
1223 |
Status group 18 |
1224 |
Device Specific Status 18 [Hardware Failure] |
1225 |
Status group 19 |
1226 |
Device Specific Status 19 [Transducer Status] |
1227 |
Status group 20 |
1228 |
Device Specific Status 20 [Transducer Status] |
1229 |
Status group 21 |
1230 |
Device Specific Status 21 [Transducer Status] |
1231 |
Status group 22 |
1232 |
Device Specific Status 22 [Configuration] |
1233 |
Status group 23 |
1234 |
Device Specific Status 23 [Configuration] |
1235 |
Status Bit Not Supported |
1236 |
No Effect |
1237 |
Used to map a status condition to a severity level. |
1238 |
Reserved |
1239 |
Secondary Analog Channel Saturated |
1240 |
Tertiary Analog Channel Saturated |
1241 |
Quaternary Analog Channel Saturated |
1242 |
Quinary Analog Channel Saturated |
1243 |
Sub-Device List Changed |
1244 |
The I/O system has detected a change in the sub-device list. A device has either been added or removed. |
1245 |
Duplicate Master Detected |
1246 |
The I/O system has detected another master with the same address. |
1247 |
Sub-Device Mismatch |
1248 |
The I/O system has detected that one or more sub-devices do not match the stored value. |
1249 |
Sub-Devices with Duplicate IDs Found |
1250 |
The I/O system has detected that more than one sub-device has the same identification. |
1251 |
Stale Data Notice |
1252 |
The I/O system has detected that one or more sub-devices has exceeded the stale data limit. |
1253 |
Capacity Denied |
1254 |
The device was unable to acquire the communication bandwidth required to support the burst messaging specified. |
1255 |
Bandwidth Allocation Pending |
1256 |
The device has asked for bandwidth from the network manager but has not yet received a response. |
1257 |
Block Transfer Pending |
1258 |
The device has a data set that is awaiting transfer. |
1259 |
Radio Failure |
1260 |
The radio or radio module within the device has failed. |
1261 |
Secondary Analog Channel Fixed |
1262 |
Tertiary Analog Channel Fixed |
1263 |
Quaternary Analog Channel Fixed |
1264 |
Quinary Analog Channel Fixed |
1265 |
Starting Status Map Index must be even value. |
1266 |
Condensed status simulation |
1267 |
Allows simulation of different status conditions. |
1268 |
Reset |
1269 |
Set |
1270 |
Condensed status value |
1271 |
Bit Index |
1272 |
3d |
1273 |
Status simulate |
1274 |
Status Simulation allows a Field Device Status bit or a bit in the Command 48 response to be manipulated. |
1275 |
Device image |
1276 |
EJX Digital Remote Sensor (with flange) |
1277 |
X Y grid |
1278 |
Index |
1279 |
Start |
1280 |
5 |
1281 |
6 |
1282 |
7 |
1283 |
8 |
1284 |
9 |
1285 |
10 |
1286 |
11 |
1287 |
12 |
1288 |
13 |
1289 |
14 |
1290 |
15 |
1291 |
16 |
1292 |
17 |
1293 |
18 |
1294 |
19 |
1295 |
20 |
1296 |
21 |
1297 |
22 |
1298 |
23 |
1299 |
24 |
1300 |
25 |
1301 |
26 |
1302 |
27 |
1303 |
28 |
1304 |
29 |
1305 |
30 |
1306 |
End |
1307 |
X-Value(%) |
1308 |
Y-Value(%) |
1309 |
X Y graph |
1310 |
Special curve |
1311 |
X-Value |
1312 |
% |
1313 |
Y-Value |
1314 |
PV chart |
1315 |
Engr disp chart |
1316 |
PV Analog Channel Saturated |
1317 |
PV Analog Channel Fixed |
1318 |
Wireless |
1319 |
WirelessHART Device |
1320 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
1321 |
Primary |
1322 |
Primary Analog Channel |
1323 |
Secondary |
1324 |
Secondary Analog Channel |
1325 |
Tertiary |
1326 |
Tertiary Analog Channel |
1327 |
Quaternary |
1328 |
Quaternary Analog Channel |
1329 |
Quinary |
1330 |
Quinary Analog Channel |
1331 |
Lock all |
1332 |
Trim not supported |
1333 |
Configuration cannot be changed |
1334 |
Locked by gateway |
1335 |
Analog Input Channel |
1336 |
Analog Output Channel |
1337 |
Simulation active |
1338 |
The device is in simulation mode and the level output is not representative of the process. |
1339 |
Non-Volatile memory failure |
1340 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
1341 |
Volatile memory error |
1342 |
The RAM memory check is invalid or maybe corrupt |
1343 |
Watchdog reset executed |
1344 |
A watchdog reset has been performed |
1345 |
Voltage conditions out of range |
1346 |
A voltage condition is outside its allowable range |
1347 |
Environmental conditions out of range |
1348 |
Electronic failure |
1349 |
Subdevice list changed |
1350 |
Duplicate master detected |
1351 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
1352 |
Bandwidth allocation pending |
1353 |
Block transfer pending |
1354 |
Battery life |
1355 |
Percent range |
1356 |
Loop current |
1357 |
Primary variable |
1358 |
Secondary variable |
1359 |
Tertiary variable |
1360 |
Quaternary variable |
1361 |
Read receive time |
1362 |
Write date and time |
1363 |
Non-Volatile Clock |
1364 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
1365 |
Clock Uninitialized |
1366 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
1367 |
None |
1368 |
No restrictions |
1369 |
SI Only |
1370 |
Restricted to SI Unit codes only |
1371 |
Process automation device |
1372 |
Discrete device |
1373 |
Hybrid:Process automation+discrete |
1374 |
I/O System |
1375 |
WirelessHART Process automation device |
1376 |
WirelessHART Discrete device |
1377 |
WirelessHART Process automation+discrete |
1378 |
WirelessHART Gateway |
1379 |
WirelessHART Access point |
1380 |
WirelessHART Process adapter |
1381 |
WirelessHART Discrete adapter |
1382 |
WirelessHART enabled handheld/portable maintenance tool |
1383 |
Device Profile |
1384 |
US |
1385 |
United States of America |
1386 |
JP |
1387 |
Japan |
1388 |
DE |
1389 |
Germany |
1390 |
FR |
1391 |
France |
1392 |
ES |
1393 |
Spain |
1394 |
RU |
1395 |
Russian Federation |
1396 |
CN |
1397 |
People's Republic of China |
1398 |
Secondary Master |
1399 |
Primary Master |
1400 |
I/O and Subdevice Status |
1401 |
WirelessHART Status |
1402 |
Time Set Option |
1403 |
Real Time Clock Flags |
1404 |
Country |
1405 |
Country of intended device installation |
1406 |
SI Unit Control |
1407 |
Indicates if device should only display SI unit codes |
1408 |
Burst Trigger Units |
1409 |
Enable on token-passing data link layer only |
1410 |
Enable on TDMA data link layer only |
1411 |
Enable on both TDMA and token-passing data link layer |
1412 |
Burst Trigger Class |
1413 |
Continuous |
1414 |
The Burst Message is published continuously at (worst case) the Minimum Update Period. |
1415 |
Window |
1416 |
The Burst Message is triggered when the source value deviates more than the specified trigger value |
1417 |
Rising |
1418 |
The Burst Message is triggered when source value Rises Above the specified trigger value. |
1419 |
Falling |
1420 |
The Burst Message is triggered when the source value Falls Below the specified trigger value. |
1421 |
On-change |
1422 |
The Burst Message is triggered when any value in the message changes. |
1423 |
Enable event notification on token-passing data link layer |
1424 |
Enable event notification on TDMA data link layer |
1425 |
Enable event notification on TDMA and token-passing data link layer |
1426 |
Configuration changed event pending |
1427 |
Device status event pending |
1428 |
More status available event pending |
1429 |
Wireless HART Enabled |
1430 |
Enabled on WirelessHART device connection only |
1431 |
Both Wired and WirelessHart Enabled |
1432 |
Enabled on both Wired and WirelessHART connections |
1433 |
Burst Msg Trigger Mode |
1434 |
Event Status |
1435 |
Event Notification Control |
1436 |
Device Diagnostic Status 0 Mask |
1437 |
Device Diagnostic Status 1 Mask |
1438 |
Device Diagnostic Status 2 Mask |
1439 |
Device Diagnostic Status 3 Mask |
1440 |
AO saturated Mask |
1441 |
AO fixed Mask |
1442 |
Operate mode Mask |
1443 |
Not Defined |
1444 |
Latched Device Diagnostic Status 0 |
1445 |
Latched Device Diagnostic Status 1 |
1446 |
Latched Device Diagnostic Status 2 |
1447 |
Latched Device Diagnostic Status 3 |
1448 |
Latched AO saturated |
1449 |
Latched AO fixed |
1450 |
Latched Operate Mode |
1451 |
Relative time value on network |
1452 |
8u |
1453 |
Dynamic Variables Returned for Device Variables |
1454 |
Command Response Truncated |
1455 |
Configuration Change Counter Mismatch |
1456 |
Status bytes mismatch |
1457 |
8.3f |
1458 |
Update time adjusted |
1459 |
Invalid burst message |
1460 |
Invalid device variable classification |
1461 |
Invalid burst trigger mode selection code |
1462 |
Update period increased |
1463 |
Update period or debounce interval adjusted |
1464 |
Update times adjusted |
1465 |
Update rate uncertain |
1466 |
Not all events cleared |
1467 |
Current Date |
1468 |
Current Date based upon the real-time clock in the field device |
1469 |
Current Time |
1470 |
Current Time based upon the real-time clock in the field device |
1471 |
Set Clock Date |
1472 |
Date to set the real-time clock in the field device to, or date that the real-time clock was last set |
1473 |
Set Clock Time |
1474 |
Time to set the real time clock in the field device to, or time that the real-time clock was last set |
1475 |
Device Variable |
1476 |
Cmd 48: Read Additional Device Status |
1477 |
Read Additional Device - This command reads additional device status information |
1478 |
Burst Trigger Level |
1479 |
Burst Message Number |
1480 |
Total Burst Msgs |
1481 |
Total number of burst messages supported by this device |
1482 |
Device Specific Status 0 Mask |
1483 |
Device Specific Status 1 Mask |
1484 |
Device Specific Status 2 Mask |
1485 |
Device Specific Status 3 Mask |
1486 |
Device Specific Status 4 Mask |
1487 |
Device Specific Status 5 Mask |
1488 |
Device Specific Status 14 Mask |
1489 |
Device Specific Status 15 Mask |
1490 |
Device Specific Status 16 Mask |
1491 |
Device Specific Status 17 Mask |
1492 |
Device Specific Status 18 Mask |
1493 |
Device Specific Status 19 Mask |
1494 |
Device Specific Status 20 Mask |
1495 |
Device Specific Status 21 Mask |
1496 |
Device Specific Status 22 Mask |
1497 |
Device Specific Status 23 Mask |
1498 |
Latched Device Specific Status 0 |
1499 |
Latched Device Specific Status 1 |
1500 |
Latched Device Specific Status 2 |
1501 |
Latched Device Specific Status 3 |
1502 |
Latched Device Specific Status 4 |
1503 |
Latched Device Specific Status 5 |
1504 |
Latched Device Specific Status 14 |
1505 |
Latched Device Specific Status 15 |
1506 |
Latched Device Specific Status 16 |
1507 |
Latched Device Specific Status 17 |
1508 |
Latched Device Specific Status 18 |
1509 |
Latched Device Specific Status 19 |
1510 |
Latched Device Specific Status 20 |
1511 |
Latched Device Specific Status 21 |
1512 |
Latched Device Specific Status 22 |
1513 |
Latched Device Specific Status 23 |
1514 |
Number of Events Supported |
1515 |
Time First Unack Event Triggered |
1516 |
The time when the first unacknowledged event was triggered |
1517 |
Event Notification Retry Time |
1518 |
Max Update Time |
1519 |
Event Debounce Interval |
1520 |
Current PV is %{0}
Select new PV |
1521 |
DP;Pres 1;Pres 2 |
1522 |
New PV is %{0} |
1523 |
Current SV is %{0}
Select new SV |
1524 |
DP;Pres 1;Pres 2;Temp 1;Temp 2 |
1525 |
New SV is %{0} |
1526 |
Current TV is %{0}
Select new TV |
1527 |
New TV is %{0} |
1528 |
Current QV is %{0}
Select new QV |
1529 |
New QV is %{0} |
1530 |
Device maybe stuck in selftest. |
1531 |
Self Test OK |
1532 |
Self test in progress please wait |
1533 |
Device maybe stuck in master reset. |
1534 |
Master Reset OK |
1535 |
It will reset the master CPU, OK ? |
1536 |
Exit;Execute |
1537 |
Master Reset in progress please wait |
1538 |
low |
1539 |
high |
1540 |
Execute OK ? |
1541 |
DP trim mode: |
1542 |
Off;Auto, Lower Pt;Auto, Upper Pt;Manual, Lower Pt;Manual, Upper Pt |
1543 |
Pres for trim %{0}
Auto, Lower Pt |
1544 |
Pres for trim %{0}
Auto, Upper Pt |
1545 |
Pres for trim %{0}
Manual, Lower Pt |
1546 |
Pres for trim %{0}
Manual, Upper Pt |
1547 |
Pres 1 trim mode: |
1548 |
Pres 2 trim mode: |
1549 |
Show the: |
1550 |
Log1(Latest);Log2;Log3;Log4(Oldest);Exit |
1551 |
Advanced diag error |
1552 |
Status simulated |
1553 |
Device vars simulated |
1554 |
No error |
1555 |
Performing log clear |
1556 |
Select operation |
1557 |
Set all X,Y in 0%;Divide X,Y into 20 (5%/div);Exit |
1558 |
It will set S.C. to be disabled, OK? |
1559 |
No;Yes |
1560 |
Set S.C. to be disabled... |
1561 |
X Y initialize in progress please wait |
1562 |
Select unit |
1563 |
;kPa;MPa;mbar;bar;psi;psia;mmH2O;mmHg;mmHgA;mmAq;mmWG;Torr;inH2O;inHg;inHgA;ftH2O;gf/cm2;kgf/cm2;kg/cm2G;kg/cm2A;atm;kg/h;t/h;m3/h;m3/min;l/h;l/min;kl/h;kl/min;Nl/h;Nl/min;Nm3/h;Nm3/min;ACFH;ACFM;SCFH;SCFM;GPH;GPM;m;mm;in;ft;kg/m3;g/cm3 |
1564 |
;kPa;MPa;mbar;bar;atm;kg/h;t/h;m3/h;m3/min;l/h;l/min;kl/h;kl/min;Nl/h;Nl/min;Nm3/h;Nm3/min;m;mm;kg/m3;g/cm3 |
1565 |
Enter Engr Unit: |
1566 |
Enter a space for the character to display it in lowercase: |
1567 |
Select case: |
1568 |
Write;Read;Coefs Clear;End |
1569 |
Test Key 1 |
1570 |
Test Key 2 |
1571 |
Select one: |
1572 |
Test Key 3;Test Key 4 |
1573 |
Test Key 3 |
1574 |
Test Key 4 |
1575 |
tmp |
1576 |
Test Key 3
%{0} |
1577 |
Test Key 4
%{0}%{1}
%{2} |
1578 |
Now Clearing! |
1579 |
Enter current password to enable to write for 10 minutes: |
1580 |
Released the write protection for 10 minutes. |
1581 |
If you wish to release completely, you have to change password to all of spaces. |
1582 |
Enter new password to change state of write protect: |
1583 |
Re-enter new password within 30 seconds: |
1584 |
Aborting method due to last error |
1585 |
Changed to new password. |
1586 |
It changed the state of protection related password. |
1587 |
Current Diag Mode is %{diag_mode}
Select Diag Mode |
1588 |
Stop;Calculation;Reference |
1589 |
Configuration changed flag was reset. |
1590 |
Select Squawk mode |
1591 |
Off;Continuous;Once |
1592 |
Squawking is in process |
1593 |
Squawking is in process, finish? |
1594 |
Select Device variable |
1595 |
Off;DP;Pres 1;Pres 2;Temp 1;Temp 2;PV % rnge;Loop current |
1596 |
Input Digital value [ %{ejx_lvar_sim_unit_code} ] |
1597 |
Select Data quality |
1598 |
Bad;Poor accuracy;Manual / Fixed;Good |
1599 |
Select Limit status |
1600 |
Not limited;Low limited;High limited;Constant |
1601 |
Choose update period |
1602 |
0.5s |
1603 |
0.5s;1s;2s;4s;8s;16s;32s;1min;5min;10min;15min;30min;45min;60min |
1604 |
Choose max update period |
1605 |
Error - Update period is larger than max update period.
Please select update period again. |
1606 |
Choose burst trigger mode |
1607 |
Continuous;On-change |
1608 |
Continuous;Window;Rising;Falling;On-change |
1609 |
Set Burst Trigger Level
for |
1610 |
[ %{compat_burst_messages[0].BURST_UNIT} ] |
1611 |
tmp_burst_trigger_level |
1612 |
[ %{compat_burst_messages[1].BURST_UNIT} ] |
1613 |
[ %{compat_burst_messages[2].BURST_UNIT} ] |
1614 |
select update period |
1615 |
select max update period |
1616 |
Choose event debounce interval |
1617 |
Off;0.5s;1s;2s;4s;8s;16s;32s;1min;5min;10min;15min;30min;45min;60min |
1618 |
This function is not supported. |
1619 |
Select transaction |
1620 |
Read Event Notification;Send Acknowledge;Exit |
1621 |
Current number: %{current_num}
Enter Event Number (0 is to get latest number) |
1622 |
ack_number |
1623 |
Invalid number (Enter 0 to 255)
Corrected to latest number |
1624 |
Event acknowledge in progress please wait |
1625 |
All events have already acknowledged |
1626 |
Latest Event Number is %{current_num}
Events have acknowledged |
1627 |
Event Number: %{current_num}
Latched status: refer to the followings .. |
1628 |
Config change count: %{config_change_counter_latched_value}
.. End of status |
1629 |
WARN-Condensed status values will be reset to default values |
1630 |
Are you sure you want to change the parameters? |
1631 |
Condensed status values were reset |
1632 |
Status sim mode: %{sts_sim_mode}
Select transaction |
1633 |
Mode set;Status simulation;Exit |
1634 |
Select mode |
1635 |
Disabled;Enabled |
1636 |
Select status |
1637 |
Device status;Ext dev status;Device Diagnostic Status 0;Device Diagnostic Status 1;Status group 0;Status group 1;Status group 2;Status group 3;Status group 4;Status group 5;Status group 14;Status group 15;Status group 16;Status group 17;Status group 18;Status group 19;Status group 20;Status group 21;Status group 22;Status group 23 |
1638 |
Select bit |
1639 |
PV out of Limits;Non PV out of Limits;Loop current Saturated;Loop current Fixed;Cold Start;Configuration Changed;Device Malfunction |
1640 |
Device Variable Alert;Critical Power Failure |
1641 |
Device Variable Simulation Active;Non-Volatile Memory Defect;Volatile Memory Defect;Watchdog Reset Executed;Power Supply Conditions Out of Range;Environmental Conditions Out of Range;Electronic Defect;Device Configuration Locked |
1642 |
Discrete Variable Simulation Active;Event Notification Overflow |
1643 |
Pres 1 Sensor Failure (AL-01);Temp 1 Sensor Failure (AL-01);Amp T Sensor Failure (AL-02);Cap 1 EEPROM Failure (AL-01);Amp 1 EEPROM Failure (AL-02) |
1644 |
CPU 1 Board Failure (AL-02);No Device ID |
1645 |
DP outside Limit (AL-10);Pres 1 outside Limit (AL-11);Temp 1 outside Limit (AL-12);Amp T outside Limit (AL-13) |
1646 |
DP over Range (AL-30);Pres 1 over Range (AL-31) |
1647 |
DP High Alarm (AL-35);DP Low Alarm (AL-36);Pres 1 High Alarm (AL-37);Pres 1 Low Alarm (AL-38);Temp 1 High Alarm (AL-39);Temp 1 Low Alarm (AL-40) |
1648 |
Illegal DP LRV (AL-50);Illegal DP URV (AL-51);Illegal DP Span (AL-52);DP Zero Trim Err (AL-53);DP Span Trim Err (AL-53);Illegal Pres 1 LRV (AL-54);Illegal Pres 1 URV (AL-54);Illegal Pres 1 Span (AL-54) |
1649 |
Pres 1 Zero Trim Err (AL-55);Pres 1 Span Trim Err (AL-55);S.C. Config Error (AL-60) |
1650 |
Flg Temp High Alarm (AL-87);Flg Temp Low Alarm (AL-87);ILBD over Range (AL-89);Invalid Ref DP (AL-88);Invalid Ref Pres 1 (AL-88);Invalid Ref Pres 2 (AL-88);Invalid Ref BlkF (AL-88) |
1651 |
B Blocking (AL-89);Pres 1 Side Blocking (AL-89);Pres 2 Side Blocking (AL-89);Large Fluct Pres 1 (AL-89);Large Fluct Pres 2 (AL-89);A Blocking (AL-89) |
1652 |
DP Simulate Mode (AL-91);Pres 1 Simulate Mode (AL-91);Pres 2 Simulate Mode (AL-91);Temp 1 Simulate Mode (AL-91);Temp 2 Simulate Mode (AL-91);PV % rnge Sim Mode (AL-91);Loop current Sim Mode (AL-91) |
1653 |
Pres 2 Sensor Failure (AL-03);Temp 2 Sensor Failure (AL-03);Cap 2 EEPROM Failure (AL-03);Amp 2 EEPROM Failure (AL-04);CPU 2 Board Failure (AL-04);Module 2 Failure (AL-05);Intercom Failure (AL-06) |
1654 |
Pres 2 outside Limit (AL-14);Temp 2 outside Limit (AL-15) |
1655 |
Pres 2 High Alarm (AL-41);Pres 2 Low Alarm (AL-42);Temp 2 High Alarm (AL-43);Temp 2 Low Alarm (AL-44) |
1656 |
Illegal Pres 2 LRV (AL-56);Illegal Pres 2 URV (AL-56);Illegal Pres 2 Span (AL-56) |
1657 |
Pres 2 Zero Trim Err (AL-57);Pres 2 Span Trim Err (AL-57);Pres 2 Fixed Mode |
1658 |
Select condition |
1659 |
Reset;Set |