0 |
Model 705 2.x |
1 |
MAGNETROL |
2 |
Device ID |
3 |
Poll Address |
4 |
Faults |
5 |
Default Paramtrs |
6 |
Default Parameters - Non-volatile memory contents have been overwritten with default values. Please re-enter application parameters through Calibration and Basic Setup menus. |
7 |
No Fiducial |
8 |
No Fiducial Pulse - Check connection between circuit boards in module. |
9 |
No Level Signal |
10 |
Missing Level Signal - Check probe connection and application parameters. |
11 |
Bad Cal Paramtrs |
12 |
Bad Calibration Paramters - Check that the correct probe length has been entered. |
13 |
High Volume |
14 |
High Volume Alarm - The measured level has reached 106% of the last entry in the strapping table. |
15 |
Fault 2 |
16 |
Available for additional fault identification. |
17 |
reserved |
18 |
Not available for fault identification. |
19 |
Warnings |
20 |
Factory Cal Reqd |
21 |
Factory Calibration required - The module requires re-calibration by the factory. The instrument will continue to operate at reduced accuracy. |
22 |
ICF1 State Error |
23 |
Device in unknown state when input capture interrupt occurred. |
24 |
OCF1 State Error |
25 |
Device in unknown state when output compare interrupt occurred. |
26 |
ICF2 Interrupt |
27 |
Spurious input capture interrupt occurred. |
28 |
OCF2 Interrupt |
29 |
Spurious output compare interrupt occurred. |
30 |
Ovrflw Interrupt |
31 |
Unexpected timer overflow interrupt has occurred. |
32 |
Extern Interrupt |
33 |
Unexpected external interrupt has occurred. |
34 |
Sfwr Interrupt |
35 |
Unexpected software interrupt has occurred. |
36 |
PV is |
37 |
Trim 4 and 20 |
38 |
Loop Test |
39 |
Level Units |
40 |
Select units of measurement for level output. |
41 |
6.1f |
42 |
Level of material in vessel |
43 |
5.1f |
44 |
% |
45 |
% Output |
46 |
Minimum Span |
47 |
Upper Range Limit |
48 |
Lower Range Limit |
49 |
4.1f |
50 |
Damping |
51 |
5.2f |
52 |
Loop |
53 |
Analog output loop current |
54 |
Alarms |
55 |
7xA_x |
56 |
7xA: Coaxial Probe (dielectric range >= 1.7) |
57 |
7xB_x |
58 |
7xB: Rigid Twin Rod Probe (dielectric range >= 2.0) |
59 |
7xD_x |
60 |
7xD: High Temperature-High Pressure Coaxial Probe (dielectric range >= 2.0) |
61 |
7xP_x |
62 |
7xP: High Pressure Coaxial Probe (dielectric range >= 1.7) |
63 |
7xR_x |
64 |
7xR: Coaxial Probe for flooding applications (dielectric range >= 1.7) |
65 |
7xS_x |
66 |
7xS: High Temperature-High Pressure Coaxial Probe for steam |
67 |
7xU_x |
68 |
7xU: Coaxial Probe for cryogenic liquids (dielectric range >= 1.7) |
69 |
7x7_x |
70 |
7x7: Flexible Twin Rod Probe (dielectric range >= 2.0) |
71 |
7xK_x |
72 |
7xK: Top In/Bottom Out Coaxial Probe for torque tube replacement |
73 |
7xE_x |
74 |
7xE: High Temperature-High Pressure Twin Rod Probe |
75 |
Type 11 |
76 |
Type 12 |
77 |
Type 13 |
78 |
Type 14 |
79 |
Type 15 |
80 |
Type of probe connected to transmitter |
81 |
Probe Model |
82 |
NPT |
83 |
US National tapered Pipe Thread |
84 |
BSP |
85 |
British Straight Pipe Thread |
86 |
Flange |
87 |
Welded ANSI or DIN Flange |
88 |
Mount 4 |
89 |
Mount 5 |
90 |
Mounting style of probe fitting |
91 |
Probe Mount |
92 |
Distance from face of process seal to end of probe |
93 |
Probe Length |
94 |
Probe Offset |
95 |
Desired level reading when liquid surface is at end of probe |
96 |
1.7 - 3 |
97 |
Dielectric constant of material lies between 1.7 and 3 |
98 |
3 - 10 |
99 |
Dielectric constant of material lies between 3 and 10 |
100 |
10 - 100 |
101 |
Dielectric constant of material lies between 10 and 100 |
102 |
1.4 - 1.7 |
103 |
Dielectric constant of material lies between 1.4 and 1.7 |
104 |
Dielectric |
105 |
Dielectric constant of material in vessel |
106 |
8.1f |
107 |
4mA Set Point |
108 |
20mA Set Point |
109 |
3.6mA |
110 |
22mA |
111 |
Hold |
112 |
Fault State |
113 |
Date/Time/Initials |
114 |
When and by whom calibration was performed |
115 |
3u |
116 |
Enter Password |
117 |
Password is required for adjusting Advanced Setup parameters Magnetrol S/N and Device id, and Factory Settings parameters Nearzone, Window, Range, Gain,Conversion Factor, Scale Offset, and Target Calibration for Steam Probes. |
118 |
Magnetrol S/N |
119 |
Factory parameter, displayed for diagnostic purposes only |
120 |
8u |
121 |
New User Password |
122 |
User password required to change parameter settings from keypad |
123 |
Nearzone |
124 |
Factory parameter: distance along probe where instrument begins sensing level of material in vessel. WARNING: Operation of instrument is undefined if level rises into nearzone region. |
125 |
4u |
126 |
Ticks |
127 |
Fiducial Ticks |
128 |
<Window> |
129 |
Range |
130 |
Gain |
131 |
Conversion Factor |
132 |
4i |
133 |
Scale Offset |
134 |
5d |
135 |
Derating Factor |
136 |
Run |
137 |
Cal |
138 |
Oper Mode |
139 |
Target Ticks |
140 |
Target Ratio |
141 |
Target Gain |
142 |
Targ Cal Tks |
143 |
CFD |
144 |
Fixed |
145 |
Threshold |
146 |
Use 'CFD' except in situation with low dielectric (< 3) material over higher dielectric (> 10) material, e.g., oil over water, in which case use 'Fixed'. |
147 |
# of Ticks |
148 |
Damped time of flight. Factory parameter, displayed for diagnostic purposes only |
149 |
4mA Trim Value |
150 |
20mA Trim Value |
151 |
Firmware Version |
152 |
Main Menu |
153 |
Device Setup |
154 |
Basic Setup |
155 |
Advanced Setup |
156 |
Diagnostics |
157 |
Factory Settings |
158 |
Variable Units |
159 |
Strapping Table |
160 |
Review |
161 |
Target Calib |
162 |
Captures time-of-flight to target on steam probe types at room ambient. |
163 |
Targ Cal Abort |
164 |
No Target detected |
165 |
Elapsed Time |
166 |
04d |
167 |
sec(-ive) hrs(+ive) |
168 |
Elapsed time since most recent significant event. |
169 |
Event status |
170 |
ALL FAULTS CLEARED |
171 |
POWER ON |
172 |
HIGH VOLUME |
173 |
DEFAULT PARAMETERS |
174 |
DEFAULT PARAMETERS+ |
175 |
BAD CAL PARAMETERS |
176 |
BAD CAL PARAMETERS+ |
177 |
DEFAULT PARAMETERS++ |
178 |
NO LEVEL SIGNAL |
179 |
NO LEVEL SIGNAL+ |
180 |
NO LEVEL SIGNAL++ |
181 |
DEFAULT PARAMTERS+++ |
182 |
NO FIDUCIAL SIGNAL |
183 |
NO FIDUCIAL SIGNAL+ |
184 |
NO FIDUCIAL SIGNAL++ |
185 |
NO FIDUCIAL SGNAL+++ |
186 |
DEFAULT PARAMTRS++++ |
187 |
Bit encoded event status stored in log. |
188 |
Event Interval |
189 |
05i |
190 |
Interval associated with a particular event that is the time elapsed since the previous event. |
191 |
No earlier event |
192 |
No later event |
193 |
Display Event Log |
194 |
Displays history of significant events such as Power On, Faults, and All Faults Cleared. The time interval displayed with a particular event is the time elapsed since the previous event. The interval associated with a Power On event is always 0. |
195 |
g |
196 |
l |
197 |
Volume Units |
198 |
Select units of measurement for volume output. |
199 |
Volume of material in vessel |
200 |
1731.2 g |
201 |
17312 g |
202 |
138500 g |
203 |
6553.5 l |
204 |
65535 l |
205 |
524280 l |
206 |
Maximum Volume |
207 |
Select maximum volume for application. |
208 |
Strap Table Length |
209 |
Number of valid level-volume pairs in strapping table. A level-volume pair is valid if both values are greater than the values of the preceding level-volume pair. |
210 |
Pt01Lvl |
211 |
Pt02Lvl |
212 |
Pt03Lvl |
213 |
Pt04Lvl |
214 |
Pt05Lvl |
215 |
Pt06Lvl |
216 |
Pt07Lvl |
217 |
Pt08Lvl |
218 |
Pt09Lvl |
219 |
Pt10Lvl |
220 |
Pt11Lvl |
221 |
Pt12Lvl |
222 |
Pt13Lvl |
223 |
Pt14Lvl |
224 |
Pt15Lvl |
225 |
Pt01Vol |
226 |
Pt02Vol |
227 |
Pt03Vol |
228 |
Pt04Vol |
229 |
Pt05Vol |
230 |
Pt06Vol |
231 |
Pt07Vol |
232 |
Pt08Vol |
233 |
Pt09Vol |
234 |
Pt10Vol |
235 |
Pt11Vol |
236 |
Pt12Vol |
237 |
Pt13Vol |
238 |
Pt14Vol |
239 |
Pt15Vol |
240 |
Level point value too high |
241 |
Level point value too low |
242 |
Volume point value too high |
243 |
Volume point value too low |
244 |
Lvl and Vol values out of range |
245 |
Level |
246 |
Volume |
247 |
|
248 |
% Out |
249 |
|
250 |
FMU860 |
251 |
DT |
252 |
DVC |
253 |
FCX |
254 |
AS800 |
255 |
340T |
256 |
340C |
257 |
344 |
258 |
Siemens Micro K |
259 |
SITRANS L |
260 |
SIPAN PH |
261 |
SITRANS P |
262 |
75SMT |
263 |
UNIDELTA |
264 |
8320 |
265 |
SX5100 |
266 |
TSV175 |
267 |
DMU |
268 |
3780 |
269 |
BM70 |
270 |
Target Ticks =%[4i]{0} |
271 |
Calibration ok
Set Targ Air =%[4i]{0}? |
272 |
Calibration bad
TargTks unstable |
273 |
Interval since most recent event:
%[.4d]{fault_status_age} secs |
274 |
Interval since most recent event:
%[.4d]{fault_status_age} hrs |
275 |
Event log empty |
276 |
Event:
%{0}
Interval:
%[.4d]{interval_secs} secs |
277 |
Get earlier event;Get later event |
278 |
Event:
%{0}
Interval:
%[.4d]{1} hrs |