Device ID |
4 |
Poll Address |
5 |
Faults |
6 |
Default Params |
7 |
Default Parameters - The application configuration information has been reset to default values. Please reconfigure the instrument using the Calibration Menu. |
8 |
Loop Failure |
9 |
Loop current differs from commanded value. Check Loop Trim. Consult factory if problem persists. |
10 |
Primary Fault |
11 |
Open condition in LVDT primary circuit has been detected. Consult factory. |
12 |
Core Drop |
13 |
Core has dropped out of the LVDT. Check for broken spring. |
14 |
Secondary Fault Hi |
15 |
A/D readings from LVDT secondary windings not in expected range. Check for missing displacer. |
16 |
Secondary Fault Lo |
17 |
A/D readings from LVDT secondary windings not in expected range. Check for broken spring. |
18 |
Fault 2 |
19 |
General Fault 2 |
20 |
Fault 1 |
21 |
General Fault 1 |
22 |
Warnings |
23 |
Calib Required |
24 |
Default calibration parameters are in use; measured process value may be inaccurate. The module may require re-calibration by the factory. |
25 |
Trim Required |
26 |
Default values for Loop DAC trim parameters are being used; Loop output may be inaccurate. Perform trim loop current operation. |
27 |
Hi Temperature |
28 |
Temperature exceeding +80 C has been measured in the electronics compartment. |
29 |
Lo Temperature |
30 |
Temperature below -40 C has been measured in the electronics compartment. |
31 |
Cal Span Warning |
32 |
Span of sensor calibration points below minimum required for accurate measurement of process value. |
33 |
Initializing |
34 |
Device is initializing. Initialization period persists until measurement compromising faults, if any, are cleared. |
35 |
Warning 2 |
36 |
General Warning 2 |
37 |
Warning 1 |
38 |
General Warning 1 |
39 |
Trim Loop Current |
40 |
Loop Test |
41 |
Capture Values |
42 |
in |
43 |
cm |
44 |
m |
45 |
ft |
46 |
Level Units |
47 |
Units of measurement for level output. |
48 |
sg |
49 |
Density Units |
50 |
Units of measurement for density output. |
51 |
°C |
52 |
°F |
53 |
Temperature Units |
54 |
Temperature units are determined by the selected level units. For metric level units, temperature units will be degrees celsius; For English level units, temperature units will be degrees fahrenheit. |
55 |
Diameter Units |
56 |
Diameter units are determined by the selected level units. For metric level units, diameter units will be centimeters; For English level units, diameter units will be inches. |
57 |
kg |
58 |
oz |
59 |
Weight Units |
60 |
Weight units are determined by the selected level units. For metric level units, weight units will be kilograms; For English level units, weight units will be ounces. |
61 |
.3f |
62 |
.2f |
63 |
Level |
64 |
Level of material in vessel. |
65 |
IfcLvl |
66 |
Level of liquid-liquid interface. |
67 |
Specific Gravity |
68 |
Specific Gravity of material in vessel. |
69 |
Level USL |
70 |
Level LSL |
71 |
Level Min Span |
72 |
Spec Gravity USL |
73 |
Spec Gravity LSL |
74 |
SpecGrav Min Span |
75 |
4.1f |
76 |
Damping |
77 |
5.2f |
78 |
Loop |
79 |
22mA |
80 |
3.6mA |
81 |
Hold |
82 |
System Fault State |
83 |
System Fault State defines how the Analog Output will respond when the transmitter detects a system fault. |
84 |
5.1f |
85 |
% |
86 |
%Range |
87 |
4mA Set Point |
88 |
20mA Set Point |
89 |
.1f |
90 |
Percent of Span |
91 |
Interface Level |
92 |
Density |
93 |
Measurement Type |
94 |
Measurement Type determines the process variable that controls the loop. |
95 |
E3A |
96 |
E3A: Flanged top; Steel Chamber |
97 |
E3B |
98 |
E3B: Flanged top; 316 SS Chamber |
99 |
E3C |
100 |
E3C: Cage side/bottom; Steel Chamber |
101 |
E3D |
102 |
E3D: Cage side/bottom; 316 SS Chamber |
103 |
E3E |
104 |
E3E: Cage side/side; Steel Chamber |
105 |
E3F |
106 |
E3F: Cage side/side; 316 SS Chamber |
107 |
E31 |
108 |
E31: Flanged top; Steel Chamber |
109 |
E32 |
110 |
E32: Flanged top; 316 SS Chamber |
111 |
E33 |
112 |
E33: Cage side/bottom; Steel Chamber |
113 |
E34 |
114 |
E34: Cage side/bottom; 316 SS Chamber |
115 |
E35 |
116 |
E35: Cage side/side; Steel Chamber |
117 |
E36 |
118 |
E36: Cage side/side; 316 SS Chamber |
119 |
Custom |
120 |
Custom configuration |
121 |
Type 14 |
122 |
Type 15 |
123 |
Type 16 |
124 |
Model Number |
125 |
Model Number of device. |
126 |
Displacer Length |
127 |
Level range of displacer. |
128 |
Displacer Diameter |
129 |
Diameter of displacer. |
130 |
Displacer Weight |
131 |
Weight of displacer. |
132 |
Level Offset |
133 |
Desired offset at zero reference point. |
134 |
Trim Level |
135 |
Trim Level is an offset value to be used to force the transmitter to output the exact Level. This should only be used after all parameters have been entered correctly, and it has been confirmed that the transmitter is tracking the correct level. |
136 |
Trim SG |
137 |
Trim SG is an offset value to be used to force the transmitter to output the exact specific gravity. This should only be used after all parameters have been entered correctly, and it has been confirmed that the transmitter is tracking the specific gravity correctly. |
138 |
0.23 - 0.54 |
139 |
0.55 - 1.09 |
140 |
1.10 - 2.20 |
141 |
High Pressure |
142 |
Spring SG Range |
143 |
Specific Gravity range for spring. |
144 |
Spring Rate |
145 |
Force constant or rate of spring in ounces per inch. |
146 |
4i |
147 |
Temperature Limit |
148 |
Maximum process temperature based on configuration. |
149 |
Process SG |
150 |
Specific Gravity of process liquid. |
151 |
Operating Temp |
152 |
Temperature of process under normal operating conditions. |
153 |
New User Password |
154 |
Password required to change user parameter settings from keypad. |
155 |
NSPValue |
156 |
Factory parameter, displayed for diagnostic purposes only. |
157 |
5u |
158 |
Enter Password |
159 |
Password entry is required to modify parameters that should normally not be accessible to the user. |
160 |
Magnetrol S/N |
161 |
Magnetrol S/N - Serial number of this unit. |
162 |
4u |
163 |
4mA Trim Value |
164 |
Displayed for diagnostic purposes only. |
165 |
20mA Trim Value |
166 |
6i |
167 |
Conversion Factor |
168 |
Scale Offset |
169 |
Date/Time/Initials |
170 |
When and by whom calibration was performed. |
171 |
Firmware Version |
172 |
Factory |
173 |
User |
174 |
Calibration Selected |
175 |
Calibration selected to calculate the measured process variable. User can select the Factory Calibration or User Calibration. If User Calibration is selected, refer to User Wet Calib Menu to calibrate the unit under process conditions. |
176 |
% |
177 |
Adj SensorCalLo |
178 |
Adj SensorCalHi |
179 |
LVDT% |
180 |
Channel 0 |
181 |
Channel 1 |
182 |
Lower SG |
183 |
Lower SG is the specific gravity of the lower liquid when measuring the level of the interface between liquids with different specific gravity values. |
184 |
Upper SG |
185 |
Upper SG is the specific gravity of the upper liquid when measuring the level of the interface between liquids with different specific gravity values. |
186 |
Dry Sensor Value |
187 |
Sensor output when displacer is hanging free. |
188 |
Sensor Cal Lo |
189 |
Sensor output at low calibration point. |
190 |
Sensor Cal Hi |
191 |
Sensor output at high calibration point. |
192 |
Level Cal Lo |
193 |
Level value at low calibration point corresponding to Sensor Cal Lo. |
194 |
Level Cal Hi |
195 |
Level value at high calibration point corresponding to Sensor Cal Hi. |
196 |
SG Cal Lo |
197 |
Specific Gravity value at low calibration point corresponding to Sensor Cal Lo. |
198 |
SG Cal Hi |
199 |
Specific Gravity value at high calibration point corresponding to Sensor Cal Hi. |
200 |
Calib SG |
201 |
Specific Gravity corresponding to factory calibration of sensor. |
202 |
Elec Temperature |
203 |
Present temperature measured in the electronics compartment. |
204 |
Max Temperature |
205 |
Maximum temperature measured in the electronics compartment. |
206 |
Min Temperature |
207 |
Minimum temperature measured in the electronics compartment. |
208 |
OK |
209 |
Default Parameters |
210 |
System Warning |
211 |
Surge |
212 |
Unknown Status |
213 |
Status |
214 |
Describes an event that may be associated with a fault or warning. |
215 |
Run Time |
216 |
Elapsed time since power on. Run time is reset to zero when the Status History is cleared. |
217 |
Occurred |
218 |
The elapsed time when fault or warning occurred. |
219 |
Duration |
220 |
When a fault or warning is cleared, the difference between the present elapsed time and the time recorded when the event occurred is recorded as the duration. |
221 |
s |
222 |
h |
223 |
Factory Param 1 |
224 |
Factory Param 2 |
225 |
Measurement Fault exists |
226 |
Not changeable for standard spring |
227 |
No earlier event |
228 |
No later event |
229 |
Main Menu |
230 |
Process Variables |
231 |
Process Input |
232 |
Analog Output |
233 |
Device |
234 |
HART |
235 |
ES 3 Modulevel |
236 |
Configuration |
237 |
Device Setup |
238 |
Calibration |
239 |
Set Point Calib |
240 |
To apply process value to Set Points: |
241 |
For manual entry: |
242 |
Enter values |
243 |
Basic Setup |
244 |
Advanced Setup |
245 |
Model Parameters |
246 |
User Wet Calib |
247 |
Interface Parameters |
248 |
Factory Settings |
249 |
Factory Cal Params |
250 |
Diagnostics |
251 |
Temp Information |
252 |
Device Status |
253 |
Present Status |
254 |
Status History |
255 |
Review |
256 |
Min Span |
257 |
Reset Temperatures |
258 |
Reset the maximum and minimum temperatures measured in the electronics compartment to the present temperature. |
259 |
Reset History |
260 |
Clears entries in Status History and resets the run time to zero. |
261 |
View History |
262 |
Displays current status and run time as well as a history of most recent faults and warnings. For each event, the run time when the event occurred and the duration of the event are shown. The run time is the time since power up or a history reset. |
263 |
Set Dry Point |
264 |
Sets sensor value for Dry Hanging Displacer |
265 |
Set Low Calib Pts |
266 |
Sets sensor value and corresponding process value for low calibration point. |
267 |
Set High Calib Pts |
268 |
Sets sensor value and corresponding process value for high calibration point. |
269 |
FMU860 |
270 |
DT |
271 |
DVC |
272 |
FCX |
273 |
AS800 |
274 |
340T |
275 |
340C |
276 |
344 |
277 |
Siemens Micro K |
278 |
SITRANS L |
279 |
SIPAN PH |
280 |
SITRANS P |
281 |
75SMT |
282 |
UNIDELTA |
283 |
8320 |
284 |
SX5100 |
285 |
TSV175 |
286 |
DMU |
287 |
3780 |
288 |
BM70 |
289 |
8u |
290 |
Are You Sure? |
291 |
No;Yes |
292 |
Current Status:
%{0}
Run Time: %[.0f]{1} %{2} |
293 |
Current Status:
%{0}
Run Time: %[.1f]{1} %{2} |
294 |
No events in Status History. |
295 |
Status Event:
%{0}
Occurred: %[.0f]{3} %{4}
Code: %[.0f]{5} |
296 |
Get earlier event;Get later event |
297 |
Status Event:
%{0}
Occurred: %[.1f]{3} %{4}
Code: %[.0f]{5} |
298 |
Status Event:
%{0}
Occurred: %[.0f]{3} %{4}
Duration: %[.0f]{5} %{6} |
299 |
Status Event:
%{0}
Occurred: %[.0f]{3} %{4}
Duration: %[.1f]{5} %{6} |
300 |
Status Event:
%{0}
Occurred: %[.1f]{3} %{4}
Duration: %[.0f]{5} %{6} |
301 |
Status Event:
%{0}
Occurred: %[.1f]{3} %{4}
Duration: %[.1f]{5} %{6} |
302 |
Set Dry Hanging Displacer Point |
303 |
Set Process at low calibration point. |
304 |
Current Sensor Value: %{0} % |
305 |
Set Low Sensor Calib Value |
306 |
Yes;No |
307 |
Enter SG value for low point |
308 |
Enter level value for low point: |
309 |
Set Process at high calibration point. |
310 |
Set High Sensor Calib Value |
311 |
Enter SG value for high point: |
312 |
Enter level value for high point: |
313 |
4mA;20mA;20mA by %;End |
314 |
Enter percent of span |
315 |
Apply new percent of Span input |
316 |
Set as new % Span;Read new value;Leave as found |