0 |
FLOWSERVE |
1 |
Model |
2 |
Logix520MD |
3 |
Universal Revision- Revision of the Universal Device Description, that the Field Device conforms to. Entered at the factory. |
4 |
Universal Revision |
5 |
DD Rev |
6 |
Field Device Revision- Revision of the Field Device Specific Device Description, that the Field Device conforms to. Entered at the factory. |
7 |
Field Device Software Revision- This revision corresponds to the software or firmware, that is embedded in the positioner. Entered at the factory. |
8 |
Hardware Revision- Revision that corresponds to the electronics hardware of positioner entered at the factory. |
9 |
Hardware Revision |
10 |
Final Assembly No. |
11 |
Positioner Final Assembly Number- Number that is used for identification purposes. Entered at the factory. |
12 |
Device Tag |
13 |
Tag- Text that is associated with the positioner installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label: a plant drawing, or on a Control System. This variable is also used to address the device when communicating with HART. Enter up to 8 characters. |
14 |
Message- Text that is associated with the positioner. This text can be used by the user in any way. There is no recommended use. Enter up to 32 characters. |
15 |
Descriptor- Text that is associated with the positioner. This text can be used by the user in any way. There is no specific recommended use. Enter up to 16 characters. |
16 |
Date- Gregorian calendar date that is stored in the positioner. This date can be used by the user in any way. There is no specific recommended use. Right and left arrow keys navigate between the month/day/year sub-fields. (Handheld: Edit values in place.) Up and down arrow keys adjust individual values. |
17 |
Field Device Identification- Uniquely identifies the positioner when combined with the Manufacturer Identification and Device Type. Entered at the factory. |
18 |
Device ID |
19 |
Mode |
20 |
Initializing |
21 |
Displays a blink sequence 3 times when the unit is powering up. Wait for power up to complete. |
22 |
Factory Reset State |
23 |
Indicates the unit has had a factory reset and has not yet been calibrated. The unit will not respond to commands and will remain in the failsafe position until a calibration is successfully completed. Proper operation will require stroke, actuator, and friction calibration to be completed. This indicator can be disabled. |
24 |
Digital Command Mode |
25 |
Indicates a HART signal is needed to change the position command and the analog 4-20 mA input signal is ignored. A manual Command Source Reset is provided to change the command back to analog control mode from the local interface if a PC or hand held configurator is not available. This is done while a QUICK-CAL is in progress by holding down both the Jog buttons (up and down) while briefly pressing the QUICK-CAL button. A new QUICK-CAL must be done after resetting. |
26 |
Squawk Mode |
27 |
When ON, this indicates a user has set the positioner to flash a special sequence so that it can be visually located. This mode is canceled if the Quick-cal button is briefly pressed, the Squawk mode is selected again remotely, or more than one hour has passed since the command was issued. |
28 |
Jog Command Mode |
29 |
Indicates the unit has been placed in a local override mode where the valve can only be stroked using the two local jog buttons. Control the valve using the jog buttons. This mode may be canceled by briefly pushing the quick-cal button. |
30 |
Signature In Progress |
31 |
Indicates that a test has been initiated by Flowserve supplied software. Signatures can only be cancelled by Flowserve supplied software. |
32 |
Positioner Status |
33 |
Position Deviation |
34 |
Indicates the difference between the command and the actual position has been greater than the user-set limit for longer than a user-set time. Review active alarms and warnings to find root causes of this alarm. |
35 |
Soft Stop Upper Limit |
36 |
Indicates the unit is being commanded to exceed a user defined upper position limit and the internal software is holding the position at the limit. The function is similar to a mechanical limit stop except it is not active if the unit is un-powered. Reset the limit (Goto: Configuration/Soft Limits & Cutoff/Limits) if more travel is needed or adjust the command signal back in the specified range. |
37 |
Soft Stop Lower Limit |
38 |
Indicates the unit is being commanded to exceed a user defined lower position limit and the internal software is holding the position at the limit. The function is similar to a mechanical limit stop except it is not active if the unit is un-powered. Reset the limit (Goto: Configuration/Soft Limits & Cutoff/Limits) if more travel is needed or adjust the command signal back in the specified range. |
39 |
Position Upper Limit |
40 |
The position has reached or is exceeding a user defined upper position indicator similar to a limit switch indicator. Reset the indicator (Goto: Configuration/User Preferences/Position Alerts) if more travel is needed or adjust the command signal back in the specified range. This indicator can be disabled. |
41 |
Position Lower Limit |
42 |
Indicates the position has reached or is exceeding a user defined lower position indicator similar to a limit switch indicator. Reset the indicator (Goto: Configuration/User Preferences/Position Alerts) if more travel is needed or adjust the command signal back in the specified range. This indicator can be disabled. |
43 |
MPC Active |
44 |
Indicates that tight shutoff (MPC) is active. The command is beyond the user set limit for tight shutoff feature. This is a normal condition for all valves when closed. The factory default setting triggers this at command signals below 1%. This indication may also occur on 3 way valves at both ends of travel if the high MPC value has been set. If tight shutoff is not desired reset the tight shutoff limits (Goto: Configuration/Soft Limits & Cutoff/Limits) to correct values or adjust the command signal inside of the specified MPC value. |
45 |
Local Interface Disabled |
46 |
When DISABLED, indicates PC software has been used to disable the local interface. This code is only present for a short time when the Quick Cal button is pressed. If local control is desired, then the local interface must be re-enabled (Goto: Configuration/Device Config/Local Interface) from the remote software. |
47 |
Error History Reset |
48 |
Momentarily indicates that a flag has been set for the positioner to clear its internal history. The positioner will automatically reset the flag once the history has been cleared. |
49 |
Mechanical |
50 |
Actuation Ratio Warning |
51 |
Indicates a decreased ability of the system to actuate the valve. It is based on the ratio of available force to required force to actuate. It is affected by the process load, friction, spring force, and available supply pressure. Increase the supply pressure. Reduce the friction. Check the actuator spring. Resize the actuator. Adjust user set limits. This indicator can be disabled. |
52 |
Pneumatic Inability to Fail Safe |
53 |
Indicates that upon loss of air supply, the valve may move to the fail-safe position. The spring alone is not adequate to overcome the friction and process load in the system. The system is relying on pneumatic force to actuate in the direction the spring is pushing. The failsafe spring may have failed, or it was not sized properly for the application. Friction or process load may have increased. Check for high friction. Repair or replace actuator spring. Reduce process load. This indicator can be disabled |
54 |
Friction High Warning |
55 |
Indicates the valve/actuator friction has passed the user set limit. High friction can cause loop oscillations, poor position control, jerky motion, or valve sticking. It can be caused by build-up from the process on the stem, trim or seat, by a failing bearing or guides in the valve and actuator, galling of the trim or stem, excessively tightened packing, linkages, or other valve/actuator mechanical issues. Consider the following to reduce friction: Stroke the valve to clear off build-up. Clear any external mechanical obstruction, loosen the packing, clean the stem, repair or replace the actuator. Highly localized friction or very jerky travel can indicate internal galling. Repair or replace internal valve components. This indicator can be disabled. |
56 |
Friction Low Warning |
57 |
Indicates the friction has passed below the user set limit. Check for packing leak. Tighten or replace the valve packing. This indicator can be disabled. |
58 |
Friction High Alarm |
59 |
Indicates the valve/actuator friction has passed the user set limit. The alarm indicates a more severe condition than the warning. High friction can cause loop oscillations, poor position control, jerky motion, or valve sticking. It can be caused by build-up from the process on the stem, trim or seat, by a failing bearing or guides in the valve and actuator, galling of the trim or stem, excessively tightened packing, linkages, or other valve/actuator mechanical issues. Determine if the friction is significantly interfering with the valve control. If not, consider increasing the friction warning limit. Consider the following to reduce friction: Stroke the valve to clear off build-up. Clear any external mechanical obstruction, loosen the packing, clean the stem, repair or replace the actuator. Highly localized friction or very jerky travel can indicate internal galling. Repair or replace internal valve components. This indicator can be disabled. |
60 |
Friction Low Alarm |
61 |
Indicates the friction has passed below the user set limit. The alarm indicates a more severe condition than the warning. Check for a packing leak. Tighten or replace the valve packing. This indicator can be disabled. |
62 |
Valve Cycles Warning |
63 |
Indicates that the cycle limit has been exceeded. The cycle counting criterion and count limit are set by the user to track the usage of the valve. Follow routine procedures for maintenance when the limit is reached such as checking the packing tightness, and checking linkages for wear, misalignment, and tightness. After maintenance, reset the cycle accumulator (Goto: Configuration/User Preferences/Valve Cycle/Travel). This indicator can be disabled. |
64 |
Valve Travel Warning |
65 |
Indicates that the total accumulated travel limit has been exceeded. The cycle counting criterion and count limit are set by the user to track the usage of the valve. Follow routine procedures for maintenance when the limit is reached such as checking the packing tightness, and checking linkages for wear, misalignment, and tightness. After maintenance, reset the travel accumulator (Goto: Configuration/User Preferences/Valve Cycle/Travel). This indicator can be disabled. |
66 |
Calibration |
67 |
Stroke Cal in Progress |
68 |
Indicates that the calibration sequence started either by using the local Quick-Cal button or by Flowserve supplied software. The calibration may be canceled by briefly pushing the quick-cal button. This indicator can be disabled. |
69 |
Loop Cal in Progress |
70 |
Indicates the command calibration sequence started by using Flowserve supplied software. The command calibration can only be cancelled by the software. This indicator can be disabled. |
71 |
Pressure Cal in Progress |
72 |
Indicates a pressure calibration sequence controlled by Flowserve supplied software. The pressure calibration can only be cancelled by the software. This indicator can be disabled. |
73 |
Analog Output Cal in Progress |
74 |
Indicates the analog output calibration sequence started, controlled by Flowserve supplied software. The analog output calibration can only be cancelled by the software. This indicator can be disabled. |
75 |
Setting Inner Loop Offset |
76 |
Indicates an automatic step in the calibration process that is done with the valve at 50% position. This must be completed for proper calibration. |
77 |
Electronic |
78 |
Temp High Warning |
79 |
Indicates the internal electronics have exceeded the user set limit. The maximum limit of the electronics and default setting is 185°F (85°C). High temperature may limit the life of the positioner. Regulate the temperature of the positioner. If the temperature reading is in error, replace the main board. This indicator can be disabled. |
80 |
Temp Low Warning |
81 |
Indicates the internal electronics have exceeded the user set limit. The minimum limit of the electronics and the default setting is -40°F (-40°C). Low temperature may inhibit responsiveness and accuracy. Regulate the temperature of the positioner. If the temperature reading is in error, replace the main board. This indicator can be disabled. |
82 |
Shunt Voltage Error |
83 |
Indicates that the circuit board is drawing too much power. Check internal wiring and connectors for electrical shorts. If no shorts are found and alarm persists, replace the main circuit board. This indicator can be disabled. |
84 |
Piezo Voltage Error |
85 |
Indicates the portion of the circuit board that drives the piezo is bad, or piezo valve itself is bad. If the unit is functioning and controlling replace the piezo, if it does not operate replace the main circuit board. This indicator can be disabled. |
86 |
Watch Dog Timeout |
87 |
Indicates that functions in the firmware took longer than expected. This can be caused when intermittent operation occurs when connecting power. Remove power and then reconnect to clear this alarm. If the alarm persists replace the main circuit board. This indicator can be disabled. |
88 |
NVRam Checksum Error |
89 |
Indicates the checksum of the internal data was not updated correctly. This may affect the function of the positioner in various ways or not at all. Error may clear with time. If error persists, cycle power and complete a Quick-Cal. If the error still persists, replace the main circuit board. This indicator can be disabled. |
90 |
Pressure |
91 |
Supply Press Low Alarm |
92 |
Indicates that the supply pressure is below the user set alarm limit. Low supply pressure can cause poor valve response or positioner failure. The minimum recommended supply pressure is 30 PSI (2.1 bar) for proper operation. The unit will fail at less than approximately 17 PSI (1.2 bars). Low supply pressure indications can also be caused by pneumatic leak. Regulate the supply pressure at the positioner above 30 PSI (2.1 bar). Recalibrate pressure sensors. Ensure system air/gas supply is adequate. Repair kinked supply tubing. Check the pressure sensor board connections and replace pressure sensor board if necessary. Check for pneumatic leaks in the actuator and actuator tubing. This indicator can be disabled. |
93 |
Supply Press High Alarm |
94 |
Indicates the positioner has determined that the supply pressure is above the user set warning limit. Regulate the supply pressure at the positioner below the maximum limit recommended for your actuator. Recalibrate pressure sensors. Check the pressure sensor board connections. Replace pressure sensor board if necessary. This indicator can be disabled. |
95 |
Supply Press Low Warn |
96 |
Indicates that the supply pressure is below the user set warning limit. Low supply pressure can cause poor valve response or positioner failure. The minimum recommended supply pressure is 30 PSI (2.1 bar) for proper operation. The unit will fail at less than approximately 17 PSI (1.2 bars). Low supply pressure indications can also be caused by pneumatic leak. Regulate the supply pressure at the positioner above 30 PSI (2.1 bar). Recalibrate pressure sensors. Ensure system air/gas supply is adequate. Repair kinked supply tubing. Check the pressure sensor board connections and replace pressure sensor board if necessary. Check for pneumatic leaks in the actuator and actuator tubing. This indicator can be disabled. |
97 |
Port 1 OORange |
98 |
Indicates the internal pressure sensor at port 1 is either saturated with a pressure over 150 PSI (10.3 bar) or the sensor or sensor connection has failed. Check the supply pressure. Calibrate pressure sensors. Check the pressure sensor board connections and replace pressure sensor board if necessary. This indicator can be disabled. |
99 |
Supply OORange |
100 |
Indicates the internal pressure sensor at supply is either saturated with a pressure over 150 PSI (10.3 bar) or the sensor or sensor connection has failed. Check the supply pressure. Calibrate pressure sensors. Check the pressure sensor board connections and replace pressure sensor board if necessary. This indicator can be disabled. |
101 |
Port 1 Range < Min |
102 |
Indicates that during a pressure sensor calibration, the range of applied pressures to port 1 was too small for optimum performance. Adjust the supply pressure to a higher value so the positioner can properly span the sensors. Then recalibrate. Briefly push the quick-cal button to acknowledge this condition and the positioner will operate using the current short stroke calibration values if valid. |
103 |
Supply Range < Min |
104 |
Indicates that during a pressure sensor calibration, the range of applied pressures to supply was too small for optimum performance. Adjust the supply pressure to a higher value so the positioner can properly span the sensors. Then recalibrate. Briefly push the quick-cal button to acknowledge this condition and the positioner will operate using the current short stroke calibration values if valid. |
105 |
Pneumatic Leak Warning |
106 |
Indicates that the positioner has detected a leak in the actuation assembly. Leakage from the actuator can cause decreased responsiveness and excessive air/gas consumption. Low supply pressure can also trigger this warning. Repair pneumatic leaks at the tubing junctions and actuator seals. Ensure proper supply pressure. This indicator can be disabled. |
107 |
Inner Loop |
108 |
Pilot Relay Warning |
109 |
Indicates that the pilot relay is sticking or slow to respond. This affects the responsiveness, increases the chance of limit cycling and excessive air consumption. The pilot relay is part of the inner loop and consists of the driver module assembly with piezo (I-P relay) which is coupled to the pilot relay valve. The value of this indicator corresponds with inner loop lag. Delayed response can be caused by a partially clogged piezo or debris, oil, corrosion, or ice on the pilot relay, or low supply pressure. Check response of the valve. If OK, adjust Pilot Relay Response limits. Check supply pressure. Check the pilot relay for debris, oil, corrosion, ice on the pilot relay. Clean or replace the pilot relay assembly. Replace the piezo or driver module assembly. Maintain a clean, water-free air/gas supply. This indicator can be disabled. |
110 |
Pilot Relay Alarm |
111 |
Indicates that the pilot relay is sticking or extremely slow to respond. This affects the responsiveness, increases the chance of limit cycling and excessive air consumption. The pilot relay consists of the driver module assembly with piezo (I-P relay) which is coupled to the pilot relay valve. Delayed response can be caused by a partially clogged piezo or debris, oil, corrosion, or ice on the pilot relay, or low supply pressure. Check response of the valve. If OK, adjust Pilot Relay Response limits. Check the supply pressure. Check the pilot relay for debris, oil, corrosion, ice on the pilot relay. Clean or replace the pilot relay assembly. Replace the piezo or driver module assembly. Maintain a clean, water-free air/gas supply. This indicator can be disabled. |
112 |
Pilot Relay Cycles Warning |
113 |
Indicates the pilot relay cycle limit set by the user has been exceeded. The pilot relay cycles indicate the activity level of the pilot relay as it maintains a valve's position. Excessive cycles can contribute to a worn pilot relay which can lead to high air consumption. Inspect for high air consumption and signs of wear. This indicator can be disabled. |
114 |
Pilot Relay Travel Warning |
115 |
Indicates the total accumulated pilot relay travel (% of full pilot relay span) set by the user has been exceeded. The pilot relay travel indicates the activity level of the pilot relay as it maintains a valve's position. Excessive travel can contribute to a worn pilot relay which can lead to high air consumption. Inspect for high air consumption and signs of wear. This indicator can be disabled. |
116 |
Hall Sensor Upper Pos |
117 |
Indicates the pilot relay appears to be fixed at the upper (pressurized) limit and is not responding. This could be due to a hall sensor that is out of calibration, a broken piezo, stuck pilot relay, or a wire connection problem. A hall sensor problem may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last valid calibration. Check the internal wiring harnesses for good connections. Check the pilot relay valve for sticking problems. If the positioner still does not operate replace the piezo, driver module assembly, and/or pilot relay assembly. This indicator can be disabled. |
118 |
Hall Sensor Lower Pos |
119 |
Indicates the pilot relay appears to be fixed at the lower (depressurized) limit and is not responding. This could be due to low supply pressure, a hall sensor that is out of calibration, a broken piezo, stuck pilot relay, or a wire connection problem. Check for adequate supply pressure. A hall sensor problem may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last valid calibration. Check the internal wiring harnesses for good connections. Check the pilot relay valve for sticking problems. If the positioner still does not operate replace the piezo, driver module assembly, and/or pilot relay assembly. This indicator can be disabled. |
120 |
Aborts the loop calibration |
121 |
|
122 |
Analog Output |
123 |
The analog output calibration is only available for positioners that have been supplied with the analog output module installed in the positioner. The Analog output is updated to match the stroke calibration of the positioner automatically every time a stroke calibration is done. This calibration is required if the 4-20 mA signal from the positioner needs to be spanned to something other than 4-20 mA. This option is also used to reverse the output if needed. Once setup properly, this calibration is usually not required for ongoing maintenance. |
124 |
Command to Burst |
125 |
Allows you to select the HART command to burst to the host. |
126 |
Burst Mode State |
127 |
Allows you to enable/disable burst mode. |
128 |
Change Cycle Limit |
129 |
Changing the Cycle Limit allows you to control the Cycle Limit warning level. |
130 |
Change Pressure Units |
131 |
Select units of measure for actuator pressure measurement. |
132 |
EC Build Date & Time |
133 |
Display the date embedded code was built |
134 |
Analog Input |
135 |
The Analog input calibration is updated to match the stroke calibration of the positioner automatically every time a stroke calibration is done. This calibration is required if the 4-20 mA signal to the positioner needs to be spanned to something other than 4-20 mA. Once setup properly this calibration is usually not required for ongoing maintenance. |
136 |
Actuator/Stroke/Friction |
137 |
Combined calibration that calibrates the internal pressure sensors of the positioner, the travel of the valve position (zero and span); and, if auto tuning is enabled, the gain values for the positioner are also calculated. Finally, a short sequence of movements allows the positioner to update a friction value for the valve assembly. Once set, the friction value will continue to update on it's own during normal operation. |
138 |
The values in the following dialog affect the process control of the valve. |
139 |
Read Register |
140 |
Allows you to read a single register value from positioner. (You will need a variable map to correctly select values to read). |
141 |
Reset Cycle Count |
142 |
Use this selection to zero the Cycle Count value. |
143 |
Reset Event History |
144 |
This procedure will reset the positioner error history log. |
145 |
Reset Travel Count |
146 |
Use this selection to zero the Valve Travel value. |
147 |
Reset Device Config. |
148 |
This procedure will set all values for the positioner to factory defaults. |
149 |
Select Actuator Info. |
150 |
Allows you to select your actuator manufacturer, model/size. Information is used internally by Professional Diagnostic model for friction calculations. |
151 |
Select Cmd. 33 variables |
152 |
Allows you to select the individual variables to burst with HART command 33. |
153 |
Execute Partial Stroke Test |
154 |
Initiates a partial stroke test. |
155 |
Stroke |
156 |
Combined calibration that calibrates the travel of the valve position (zero and span); and, if auto tuning is enabled, the gain values for the positioner are also calculated. |
157 |
Post Read Pressure 1 |
158 |
HRL Test... |
159 |
Write Register |
160 |
Allows you to change internal variable values directly. (DANGEROUS). |
161 |
Displays actuator manufacturer. |
162 |
Manufacturer |
163 |
Valtek (Piston) |
164 |
Kämmer |
165 |
Valtek (Diaphragm Rotary) |
166 |
Automax |
167 |
NAF |
168 |
Valtek (Diaphragm Linear |
169 |
Fisher |
170 |
Other |
171 |
Displays Actuator model. |
172 |
25 |
173 |
50 |
174 |
100 |
175 |
100C |
176 |
150C |
177 |
200 |
178 |
200C |
179 |
300 |
180 |
400 |
181 |
500 |
182 |
600 |
183 |
37 |
184 |
38 |
185 |
39 |
186 |
3D |
187 |
47 |
188 |
48 |
189 |
49 |
190 |
4D |
191 |
P0 |
192 |
P1 |
193 |
P2 |
194 |
P3 |
195 |
P4 |
196 |
P5 |
197 |
P6 |
198 |
P7 |
199 |
NR1 |
200 |
NR2 |
201 |
NR3 |
202 |
B050D |
203 |
B063D |
204 |
B085D |
205 |
B100D |
206 |
B115D |
207 |
B125D |
208 |
B150D |
209 |
B175D |
210 |
B200D |
211 |
SNA250 |
212 |
SNA300 |
213 |
R205 |
214 |
R206 |
215 |
R207 |
216 |
R208 |
217 |
R310 |
218 |
R312 |
219 |
R314 |
220 |
R316 |
221 |
R414 |
222 |
R416 |
223 |
R418 |
224 |
R420 |
225 |
R422 |
226 |
R514 |
227 |
R516 |
228 |
R518 |
229 |
R520 |
230 |
R522 |
231 |
R524 |
232 |
-02 |
233 |
-11 |
234 |
-12 |
235 |
-21 |
236 |
-22 |
237 |
-31 |
238 |
-32 |
239 |
-41 |
240 |
-42 |
241 |
-51 |
242 |
-52 |
243 |
127 |
244 |
252 |
245 |
502 |
246 |
700 |
247 |
1502 |
248 |
3002 |
249 |
657-30 |
250 |
657-34 |
251 |
657-40 |
252 |
657-45 |
253 |
657-46 |
254 |
657-50 |
255 |
657-60 |
256 |
657-70 |
257 |
657-80 |
258 |
657-87 |
259 |
657-100 |
260 |
667-30 |
261 |
667-34 |
262 |
667-40 |
263 |
667-45 |
264 |
667-46 |
265 |
667-50 |
266 |
667-60 |
267 |
667-70 |
268 |
667-80 |
269 |
667-87 |
270 |
667-100 |
271 |
Actuator area |
272 |
Actuator type i.e. linear or rotary; piston or diaphragm etc. |
273 |
Type |
274 |
Linear (piston) |
275 |
Linear (diaphragm) |
276 |
Rotary (piston) |
277 |
Rotary (diaphragm) |
278 |
Rotary (Rack & Pinion) |
279 |
Spring type i.e. single or heavy duty etc. |
280 |
Spring |
281 |
Single |
282 |
Heavy duty |
283 |
Dual |
284 |
Multi |
285 |
None |
286 |
Standard |
287 |
Current being sent to the positioner on the 4 to 20mA loop. |
288 |
Loop Crnt |
289 |
5.2f |
290 |
AO Detected |
291 |
Indicates the positioner is analog output capable. |
292 |
No |
293 |
Yes |
294 |
Auto Tune |
295 |
The positioner will calculate new tuning parameter values when stroke calibrated with Auto selected. Manual setting causes positioner to use current tuning values. |
296 |
Manual |
297 |
Auto |
298 |
This variable shows the state of the positioner during calibration. Each value of Calibrate corresponds to a specific stage in the calibration process. The most common states: Calibrate=0, Normal operation, calibration OFF, position control enabled; Calibrate=1, Automatically calibrate stroke; Calibrate=2, Automatically calibrate actuator pressure sensors; Calibrate=3, acquire command counts with loop current at 0%; Calibrate=4, command counts with loop current at 100%; Calibrate=5, Moving valve to closed position, get Stem position at 0%; Calibrate=6, moving valve to open position, get stem position at 100%; Calibrate=7, Calibrating supply sensor; Calibrate=8, Calibrating Actuator Sensor, closing valve; Calibrate=9, Calibrating Actuator sensor, opening valve; Calibrate=11, quick-cal button has been pressed; Calibrate=12,Error occurred during Calibration. |
299 |
Calbration Mode |
300 |
3d |
301 |
Date of calibration and initials of person who performed calibration. These should be entered at the time of calibration. |
302 |
Analog Input Cal Date |
303 |
Strk Cal Date |
304 |
TheMonthString |
305 |
Character register Number. |
306 |
Char Register Num |
307 |
Character Register Value |
308 |
Char Value |
309 |
Zero is only valid entry. |
310 |
00% Signal |
311 |
.2f |
312 |
What percent open do you want at this signal %? |
313 |
05% Signal |
314 |
10% Signal |
315 |
15% Signal |
316 |
20% Signal |
317 |
25% Signal |
318 |
30% Signal |
319 |
35% Signal |
320 |
40% Signal |
321 |
45% Signal |
322 |
50% Signal |
323 |
55% Signal |
324 |
60% Signal |
325 |
65% Signal |
326 |
70% Signal |
327 |
75% Signal |
328 |
80% Signal |
329 |
85% Signal |
330 |
90% Signal |
331 |
95% Signal |
332 |
99% Signal |
333 |
Close Speed Limit |
334 |
Time it takes to move the stem to the closed position. |
335 |
sec. |
336 |
5.0f |
337 |
Signal at Closed |
338 |
4-20 mA signal to close the valve. |
339 |
20mA |
340 |
20mA will completely close the valve. |
341 |
4mA |
342 |
4mA will completely close the valve. |
343 |
Command Out |
344 |
Command Perc |
345 |
Command Units |
346 |
Continuous Friction |
347 |
Is the Continuous Friction Hunting active or disabled? |
348 |
Off |
349 |
Active |
350 |
Value of the Valve Cycle Counter. The Valve Cycle Counter counts the number of cycles of the valve stem since the last reset. Cycle Deadband defines how large a stem movement is allowed before a cycle is counted. Valve Cycle Counter can be reset to zero from the Reset Cycle Count method. |
351 |
Cycle Count |
352 |
10d |
353 |
Enter the desired Valve Cycle Deadband in percent of full stroke. Valve Cycle Deadband defines how large a stem movement is allowed before a cycle is counted in the Valve Cycle Counter. A cycle is counted when the stem has moved more than the amount of the deadband in either direction. Enter this variable as an absolute number. For example, if a deadband of +/-10% is desired. Cycle Deadband should be entered as 10. |
354 |
Cycle Deadband |
355 |
The number of cycles defined by the Valve Cycle Deadband that, if exceeded, will activate the Valve Cycle Limit alarm. Use Change Cycle Limit to increase or decrease Cycle Limit level. |
356 |
Cycle Limit |
357 |
Enter the desired Valve Travel Deadband in percent of full stroke. Valve Travel Deadband defines how large a stem movement is allowed before travel is accumulated in the Valve Travel Accumulator. Enter this variable as an absolute number. For example, if a deadband of +/- 10% is desired, Travel Deadband should be entered as 10. |
358 |
Travel Deadband |
359 |
Value considered to be full stroke. Usually set to 100% |
360 |
Travel Length |
361 |
6.2f |
362 |
The amount of travel defined by the Travel Deadband that if exceeded will activate the Travel Limit alert. Use Change Travel Limit to increase or decrease the Travel Limit level. |
363 |
Travel Limit |
364 |
Cutoff Hysteresis |
365 |
DataPoints |
366 |
Displays the air action of the valve (air to open (ATO) or air to close (ATC)). |
367 |
Air Action |
368 |
ATC |
369 |
ATO |
370 |
Select the position to which the valve will fail (open or closed as determined by the spring position). |
371 |
Fail Position |
372 |
Closed |
373 |
Open |
374 |
View whether the positioner has pressure sensors. 520 = No presure sensors, 521 = Has pressure sensors. |
375 |
Positioner Model |
376 |
520 |
377 |
521 |
378 |
Select the positioner action (single or double acting). |
379 |
Positioner Action |
380 |
Double |
381 |
Select the type of valve the positioner is controlling (linear or rotary). |
382 |
Motion |
383 |
Linear |
384 |
Rotary |
385 |
D-Gain anticipates overshoot based on the current velocity and dynamically adjusts movement so that overshoot does not occur. |
386 |
D-Gain |
387 |
Input 4-20mA command expressed in percent of full scale input. |
388 |
4-20 Command |
389 |
Enter the digital command value, in percent of full stroke. This variable is available only when the valve is being positioned by a digital command (digital source) rather than the 4-20mA analog signal (analog source). |
390 |
Digital Command |
391 |
Displays the source of the command signal (analog or digital). |
392 |
Command Source |
393 |
Analog |
394 |
Digital |
395 |
Unused |
396 |
Displays state of Position Cut-off as defined in the Soft Limit / Characterization Menu. |
397 |
Position Cutoff |
398 |
Dormant |
399 |
The modified command signal, in percent of full stroke, which actually sets the controlled position of the valve. Control Command is generated after custom characterization, soft limits, and minimum position cutoff parameters are evaluated. 4-20 mA command and Control Command can differ if custom characterization, soft limits, or minimum position cutoff are active. |
400 |
Control Command |
401 |
The difference between the modified position command (Control Command) signal and the stem position signal expressed in percent of full stroke. Deviation = Control Command - Position. |
402 |
Deviation |
403 |
Actual stem position in percent of full stroke, as measured by the position stem position transducer. |
404 |
Position |
405 |
E. Code Build Day |
406 |
E. Code. Build Hour |
407 |
2d |
408 |
E. Code Build Min. |
409 |
E. Code Build Mo. |
410 |
E. Code Build Sec. |
411 |
E. Code Build Yr. |
412 |
E. Code Major |
413 |
Embedded code major version number. |
414 |
E. Code Minor |
415 |
Embedded code minor version number. |
416 |
Number of events since reset or power-up. |
417 |
Event count |
418 |
Current event pointer on the Logix 520MD. |
419 |
Event pointer |
420 |
This is the most recent event encountered. |
421 |
Most Recent Event |
422 |
Reserved |
423 |
Pneumatic unable to Fail Safe |
424 |
Loss of Inter-PCB Comm |
425 |
Elect. Unable to Failsafe |
426 |
Feedback Range < Min |
427 |
0% Position OORange |
428 |
100% Position OORange |
429 |
No Motion Time Out |
430 |
Non-Settle Time Out |
431 |
ILO Time Out |
432 |
Jog Cal-Set 100% Pos |
433 |
Command Loop Range < Min |
434 |
Command Loop OORange 100% |
435 |
Command Loop OORange 0% |
436 |
Analog Output Range < Min |
437 |
Pressure Sensor Board Present |
438 |
Analog Output Board Present |
439 |
Pressure Control Locked |
440 |
Pot Rotation Reversed |
441 |
This is the second most recent event encountered. |
442 |
2nd |
443 |
This is the third most recent event encountered. |
444 |
3rd |
445 |
This is the fourth most recent event encountered. |
446 |
4th |
447 |
This is the fifth most recent event encountered. |
448 |
5th |
449 |
This is the sixth most recent event encountered. |
450 |
6th |
451 |
This is the seventh most recent event encountered. |
452 |
7th |
453 |
This is the eighth most recent event encountered. |
454 |
8th |
455 |
Diagnostics Level |
456 |
Indicates whether positioner is Standard, Advanced, or Professional. |
457 |
Pressure sensors are used for control only. |
458 |
Pro |
459 |
Full diagostic features are available including friction and partial stroke testing. |
460 |
Advanced |
461 |
Pressure values and alarms are available. |
462 |
Pressure Port 1 |
463 |
Port 1 Pressure after Calculation. |
464 |
Pressure Port 2 |
465 |
Port 2 Pressure after Calculation. |
466 |
Supply Pressure |
467 |
Valve Stability |
468 |
High friction automatically switches to pressure control. Low friction uses calculated tuning values. |
469 |
High Friction |
470 |
High friction setting uses pressure control for stability. |
471 |
Low Friction |
472 |
Low friction setting will use standard control for stability. |
473 |
Future Variable |
474 |
Future |
475 |
FutureVar |
476 |
Future var |
477 |
This value indicates the setting that is used to remove any long-term deviation at a slower rate. A larger value would remove the long-term deviation at a faster rate. |
478 |
I-Gain |
479 |
Inner Loop Offset is in percent (0-100). This will normally only be entered at the factory. This is adjusted to place the pilot relay in the balanced (null) position with zero deviation signal. |
480 |
IL offset |
481 |
% |
482 |
Integer register Number. |
483 |
Register Number |
484 |
Integer Register Value |
485 |
Int Value |
486 |
Lifetime |
487 |
Number of hours positioner has been in operation. |
488 |
Local Interface |
489 |
Enable or disable the Logix local interface. (Quick-cal and dip switches) |
490 |
Enabled |
491 |
Disabled |
492 |
Long register Number. |
493 |
Long Reg Number |
494 |
Long Register Value |
495 |
Long Value |
496 |
Upper Pos. Cutoff |
497 |
Point at which the stem will go to the full open position regardless of command value. |
498 |
Maximum Lifetime |
499 |
Maximum temperature reached since startup |
500 |
Lower Pos. Cutoff |
501 |
Point at which the stem will go to the full closed position regardless of command value. |
502 |
Minimum Lifetime |
503 |
Minimum temperature reached since startup |
504 |
Calibrated |
505 |
Indicates whether the positioner has been calibrated after a reset or on initial startup. |
506 |
Open Speed Limit |
507 |
Time it takes to move the stem to the open position. |
508 |
Enter the maximum outer loop proportional gain. Max Prop Gain is used along with Min Prop Gain and the Gain Multiplier to calculate total outer loop proportional gain. Max Prop Gain is used when deviation is small. Setting Max Prop Gain equal to Min Prop Gain with Gain Mult equal to zero sets gain to conventional proportional control. |
509 |
P-Gain |
510 |
Position Deviation Time is the amount of time, entered in seconds, that the position deviation can exceed the Position Deviation Deadband before a Position Deviation Alert is generated. |
511 |
Posn. Dev. Time |
512 |
Position Deviation Deadband entered in percent determines the minimum steady state difference which generates a Position Deviation Alert This is entered as an absolute value. For example, if a deadband of +/- 2% is desired a value of 2 should be entered. |
513 |
Posn. Dev. Deadband |
514 |
Enter the Upper Position Alert set point in percent of full stroke. If the valve stroke exceeds this value, Upper Position Alert is activated. |
515 |
Posn. Upper Alert |
516 |
Enter the Lower Position Alert set point in percent of full stroke. If the valve stroke falls below this value, Lower Position Alert is activated. |
517 |
Posn. Low Alert |
518 |
Position damping value |
519 |
Lower position limit |
520 |
5.1f |
521 |
Position minimum span |
522 |
.1f |
523 |
Position upper limit |
524 |
Power Up |
525 |
Number of hours positioner has been powered up. |
526 |
Maximum Power Up |
527 |
Maximum temperature reached since last power up |
528 |
Minimum Power Up |
529 |
Minimum temperature reached since last power up |
530 |
Port 1 (% of Calibrated Supply) |
531 |
Port 1 pressure value in percent of calibrated supply maximum. |
532 |
Port 2 (% of Calibrated Supply) |
533 |
Port 2 pressure value in percent of calibrated supply maximum. |
534 |
Supply (% of Calibrated Supply) |
535 |
Supply pressure value in percent of calibrated supply maximum. |
536 |
Place holder |
537 |
Reset |
538 |
Number of hours positioner has been in operation since last reset. |
539 |
Maximum Reset |
540 |
Maximum temperature reached since last reset |
541 |
Minimum Reset |
542 |
Minimum temperature reached since last reset |
543 |
Signature status |
544 |
Signature in process |
545 |
End of signature |
546 |
Xmit in process |
547 |
Ramp sig (Step= 0) |
548 |
Initialized |
549 |
Last frame |
550 |
Signature format |
551 |
Default |
552 |
DD Standard |
553 |
Custom |
554 |
Signature hold |
555 |
SigILCmd |
556 |
SigILCmdValue |
557 |
SigILPos |
558 |
SigILPosValue |
559 |
SigPort1 |
560 |
SigPort2 |
561 |
SigPos |
562 |
Starting position |
563 |
Stopping position |
564 |
Signature time |
565 |
Displays the position characterization (linear, equal %, or custom) |
566 |
Characterization |
567 |
Equal % |
568 |
Enter the Upper Soft Limit in percent of full stroke. The Modified Command Signal will not go above this limit. Upper Soft Limit must be greater than Lower Soft Limit for proper operation. |
569 |
High Soft Limit |
570 |
Enter the Lower Soft Limit in percent of full stroke. The Modified Command Signal will not go below this limit. Lower Soft Limit must be less than Upper Soft Limit for proper operation. |
571 |
Low Soft Limit |
572 |
Pressure Control State |
573 |
Use Pressure Control function to control stem position in some high friction applications. |
574 |
Pressure Lock |
575 |
Indicates that the current position is within the pressure control window. |
576 |
Window |
577 |
Size of the pressure control window. |
578 |
Quick Calibration |
579 |
Set positioner to use the local interface to manually calibrate stroke. (Jog) |
580 |
Jog |
581 |
You must be at the local interface to set the span. |
582 |
Standard automatic stroke calibration will be used. |
583 |
Final command |
584 |
Serial Number of the electronics control board. |
585 |
Electronic SN |
586 |
Engineering units being used for ambient main board temperature measurement. |
587 |
Temperature Units |
588 |
Circuit board ambient temperature. |
589 |
Temperature |
590 |
TheDate |
591 |
Value of the Valve Travel Accumulator. The Valve Travel Accumulator measures the distance the valve stem has traveled since the last reset. Valve Travel Deadband defines how large a stem movement is allowed before travel accumulator increases. The Valve Travel Accumulator can be reset to zero from the Reset travel Count method. |
592 |
Travel Count |
593 |
Travel Units |
594 |
Units for travel measurements. |
595 |
in. |
596 |
mm |
597 |
deg |
598 |
Tertiary units |
599 |
Displays the current engineering units for pressure. |
600 |
Press. Units |
601 |
Select valve body material. |
602 |
Body Material |
603 |
Alloy 20 |
604 |
Aluminum |
605 |
Bronze |
606 |
Carbon steel |
607 |
Special Alloy |
608 |
Hastelloy |
609 |
Inconel |
610 |
Monel 400 |
611 |
Nickel |
612 |
Titanium |
613 |
Type 304 |
614 |
Type 316 |
615 |
Select valve body size in inches. |
616 |
Body Size |
617 |
.25 INCH / DN 6 |
618 |
.5 INCH / DN 15 |
619 |
.75 INCH / DN 20 |
620 |
1.0 INCH / DN 25 |
621 |
1.25 INCH / DN 32 |
622 |
1.5 INCH / DN 40 |
623 |
2.0 INCH / DN 50 |
624 |
2.5 INCH / DN 65 |
625 |
3.0 INCH / DN 80 |
626 |
4.0 INCH / DN 100 |
627 |
5.0 INCH / DN 125 |
628 |
6.0 INCH / DN 150 |
629 |
8.0 INCH / DN 200 |
630 |
10.0 INCH / DN 250 |
631 |
12.0 INCH / DN 300 |
632 |
14.0 INCH / DN 350 |
633 |
16.0 INCH / DN 400 |
634 |
18.0 INCH / DN 450 |
635 |
20 INCH / DN 500 |
636 |
24.0 INCH / DN 600 |
637 |
28.0 INCH / DN 700 |
638 |
32.0 INCH / DN 800 |
639 |
36.0 INCH / DN 900 |
640 |
40.0 INCH / DN 1000 |
641 |
Select valve end connections. |
642 |
End Connection |
643 |
Sep. Flange |
644 |
Integral Flange |
645 |
Weld End |
646 |
Flangeless / Wafer |
647 |
Clamped |
648 |
Screwed |
649 |
Flow under plug or flow over plug (linear), shaft upstream or shaft downstream (rotary). |
650 |
Flow Direction |
651 |
Flow Over |
652 |
Flow Under |
653 |
Pressure rating for the inlet of the valve. |
654 |
Inlet Press |
655 |
Select ANSI shutoff leakage class. |
656 |
Leak Class |
657 |
Class I |
658 |
Class II |
659 |
Class III |
660 |
Class IV |
661 |
Class V |
662 |
Class VI |
663 |
Select valve manufacturer. |
664 |
Valtek |
665 |
Select valve type or model. |
666 |
Valtek Mark One |
667 |
Valtek Mark One-X |
668 |
Valtek Mark 100 |
669 |
Valtek Mark Two |
670 |
Valtek Mark Six |
671 |
Valtek Mark Eight |
672 |
Valtek Mark Ten (Survivor) |
673 |
Valtek ShearStream SB |
674 |
Valtek ShearStream HP |
675 |
Valtek MaxFlo 3 |
676 |
Valtek Valdisk BX |
677 |
Valtek FlowTop |
678 |
Valtek FlowPak |
679 |
Valtek FlowPro |
680 |
Valtek VariCool |
681 |
Kämmer HpFlow |
682 |
Kämmer LinedFlow |
683 |
Kämmer TotalFlow |
684 |
Kämmer ColdFlow |
685 |
Kämmer DrainFlow |
686 |
Kämmer SmallFlow |
687 |
Kämmer CleanFlow |
688 |
Kämmer Multi-Z |
689 |
Kämmer 020000 |
690 |
Kämmer 025000 |
691 |
Kämmer 030000 |
692 |
Kämmer 185000 |
693 |
NAF Setball |
694 |
NAF Duball |
695 |
NAF Trunnball |
696 |
NAF Torex |
697 |
NAF Unex |
698 |
Pressure rating for the outlet of the valve. |
699 |
Outlet Press |
700 |
Select valve packing type. |
701 |
Pack Type |
702 |
Single Packing PTFE |
703 |
Single Packing Graphite |
704 |
Double Packing PTFE |
705 |
Double Packing Graphite |
706 |
Spring loaded |
707 |
Select valve body ANSI Pressure Rating (class). |
708 |
Press Class |
709 |
CL 150 |
710 |
CL 300 |
711 |
CL 600 |
712 |
CL 900 |
713 |
CL 1500 |
714 |
CL 2500 |
715 |
CL 4000 |
716 |
PN 10 |
717 |
PN 16 |
718 |
PN 25 |
719 |
PN 40 |
720 |
PN 63 |
721 |
PN 100 |
722 |
PN 160 |
723 |
PN 250 |
724 |
PN 400 |
725 |
PN 4000 |
726 |
Travel for which this unit is rated. |
727 |
Rated Travel |
728 |
Valve serial number in the format, xxxxxx.xxx. Contains sales order number plus the page. |
729 |
Valve Ser. No. |
730 |
Stem/shaft diameter in inches. |
731 |
Stem Diameter |
732 |
Stroke Length |
733 |
Stroke length in percent. |
734 |
Velocity |
735 |
Time it takes to move the stem from one extreme to the other during stroke calibtration. |
736 |
Select valve trim characteristics. (Informational use only) |
737 |
Quick Open |
738 |
Bi-Linear |
739 |
Select valve trim material. |
740 |
Trim Material |
741 |
Stainless Steel |
742 |
Stainless Steel (hardened) |
743 |
Alloy 6 |
744 |
Soft Seated |
745 |
Special Alloys |
746 |
Select Valve Trim Size. |
747 |
Size |
748 |
0.10 - 0.12 in (2.5 - 3.0 mm) |
749 |
0.13 - 0.15 in (3.1 - 3.8 mm) |
750 |
0.16 - 0.19 in (3.9 - 4.8 mm) |
751 |
0.20 - 0.24 in (4.9 - 6.1 mm) |
752 |
0.25 - 0.30 in (6.2 - 7.6 mm) |
753 |
0.31 - 0.37 in (7.7 - 9.4 mm) |
754 |
0.38 - 0.45 in (9.5 - 11.4 mm) |
755 |
0.46 - 0.55 in (11.5 - 14.0 mm) |
756 |
0.56 - 0.67 in (14.1 - 17.0 mm) |
757 |
0.68 - 0.81 in (17.1 - 20.6 mm) |
758 |
0.82 - 0.98 in (20.7 - 24.9 mm) |
759 |
0.99 - 1.18 in (25.0 - 30.0 mm) |
760 |
1.19 - 1.42 in (30.1 - 36.1 mm) |
761 |
1.43 - 1.7 in (36.2 - 43 mm) |
762 |
1.8 - 2.1 in (44 - 54 mm) |
763 |
2.2 - 2.7 in (55 - 68 mm) |
764 |
2.8 - 3.3 in (69 - 84 mm) |
765 |
3.4 - 4.1 in (85 - 103 mm) |
766 |
4.2 - 4.9 in (104 - 125 mm) |
767 |
5.0 - 6.0 in (126 - 152 mm) |
768 |
6.1 - 7.3 in (153 - 184 mm) |
769 |
7.4 - 8.8 in (185 - 223 mm) |
770 |
8.9 - 10.5 in (224 - 268 mm) |
771 |
10.6 - 12.7 in (269 - 322 mm) |
772 |
12.8 - 15.2 in (323 - 386 mm) |
773 |
15.3 - 18.2 in (387 - 462 mm) |
774 |
18.3 - 21.8 in (463 - 552 mm) |
775 |
Select valve trim (standard, CavControl, MegaStream, etc.). |
776 |
CavControl |
777 |
ChannelStream |
778 |
MegaStream |
779 |
Tiger-Tooth |
780 |
Stealth |
781 |
MicroCav |
782 |
CavStream |
783 |
MultiStream |
784 |
SilentPack |
785 |
Kämmer Type I-III |
786 |
Z-Trim |
787 |
Multi-stage |
788 |
X1 |
789 |
AFileType |
790 |
Average |
791 |
EndPoint |
792 |
InputValue |
793 |
+/- |
794 |
Maximum |
795 |
MaxXValue |
796 |
MinXValue |
797 |
Count of files |
798 |
MyFileList |
799 |
OutputValue |
800 |
Port1Value |
801 |
Port2Value |
802 |
Settling Time |
803 |
B value |
804 |
M value |
805 |
StartPoint |
806 |
ThrustValue |
807 |
KeepMaskBits |
808 |
Modes Mask |
809 |
Clear the check mark or set the value to OFF to mask off notifications of positioner modes. |
810 |
Not used |
811 |
Positioner Status Mask |
812 |
Clear the check mark or set the value to OFF to mask off Positioner status indicators. |
813 |
Mechanical Mask |
814 |
Clear the check mark or set the value to OFF to mask off Mechanical status indicators. |
815 |
Pneumatic Inability to Failsafe |
816 |
Calibration Mask |
817 |
Clear the check mark or set the value to OFF to mask off Calibration status indicators. |
818 |
Stroke Cal. in Progress |
819 |
Loop Cal. in Progress |
820 |
Pressure Cal. in Progress |
821 |
Analog Output Cal. in Progress |
822 |
Electronic Mask |
823 |
Clear the check mark or set the value to OFF to mask off Electronic status indicators. |
824 |
Temp. High Warning |
825 |
Temp. Low Warning |
826 |
Electronic Inability to Failsafe |
827 |
Pressure Mask |
828 |
Clear the check mark or set the value to OFF to mask off Pressure status indicators. |
829 |
Supply Press. Low Alarm |
830 |
Supply Press. High Warn |
831 |
Supply Press. Low Warn |
832 |
Port 1 Out of Range |
833 |
Supply Out of Range |
834 |
Inner Loop Mask |
835 |
Clear the check mark or set the value to OFF to mask off Inner Loop status indicators. |
836 |
Outer Loop Mask |
837 |
Clear the check mark or set the value to OFF to mask off Outer Loop status indicators. |
838 |
0% Posn. Out of Range |
839 |
100% Posn. Out of Range |
840 |
Command Loop Mask |
841 |
Clear the check mark or set the value to OFF to mask off Command Loop status indicators. |
842 |
Command Loop Out of Range 100% |
843 |
Command Loop Out of Range 0% |
844 |
Configuration Mask |
845 |
Clear the check mark or set the value to OFF to mask off Configuration indicators. |
846 |
Too Few Data Bytes |
847 |
Device is Busy |
848 |
Command not implemented |
849 |
Modes |
850 |
Positioner mode indicators |
851 |
Indicates that a test has been initiated by Flowserve supplied software. Signatures can only be cancelled by Flowserve supplied software. This indicator can be disabled. |
852 |
Positioner status indicators |
853 |
Indicates the difference between the command and the actual position has been greater than the user-set limit for longer than a user-set time. Review active alarms and warnings to find root causes of this alarm. This indicator can be disabled. |
854 |
Mechanical Status |
855 |
Mechanical status |
856 |
Calibration modes |
857 |
Stroke Calibration in Progress |
858 |
Loop Calibration in Progress |
859 |
Pressure Calibration in Progress |
860 |
Analog Output Calibration in Progress |
861 |
Electronic Status |
862 |
Electronic status |
863 |
Indicates that upon loss of air supply, the valve may move to the fail-safe position. The spring alone is not adequate to overcome the friction and process load in the system. The system is relying on pneumatic force to actuate in the direction the spring is pushing. The failsafe spring may have failed, or it was not sized properly for the application. Friction or process load may have increased. If alarm persists for more than 30 minutes, the Piezo assembly is damaged and should be replaced. This indicator can be disabled. |
864 |
Pressure Status |
865 |
Pressure status |
866 |
Supply Press. High Alarm |
867 |
Port 1 Range < Min. |
868 |
Supply Range < Min. |
869 |
Inner Loop Status |
870 |
Inner Loop status |
871 |
Hall Sensor Upper Posn. |
872 |
Hall Sensor Lower Posn. |
873 |
Outer Loop Status |
874 |
Outer Loop status |
875 |
Indicates that during calibration, the range of motion of the position feedback arm was too small for optimum performance. Check for loose linkages and/or adjust the feedback pin to a position closer to the follower arm pivot to create a larger angle of rotation and recalibrate. Briefly pushing the quick-cal button acknowledges this condition and the positioner will operate using the current short stroke calibration if otherwise a good calibration. |
876 |
Indicates that during calibration, the feedback sensor moved beyond its range of operation at the 0% (closed) position. Adjust the positioner mounting, linkage or feedback potentiometer to move the position sensor back into range then restart the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration. |
877 |
Indicates that during calibration, the feedback sensor moved beyond its range of operation at the 100% (open) position. To correct the condition, adjust the positioner mounting, linkage or feedback potentiometer to move the position sensor back into range then restart the calibration. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration. |
878 |
Indicates that during calibration, there was no motion of the actuator based on the current stroke time configuration. Check linkages and air supply to make sure the system is properly connected. If the time out occurred because the actuator is very large then simply retry the Quick cal and the positioner will automatically adjust for a larger actuator by doubling the time allowed for movement. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration. |
879 |
Indicates that during calibration, the position feedback sensor did not settle. Check for loose linkages or a loose positioner sensor. This error may be cleared by briefly pushing the quick-cal button, which will force the positioner to use the parameters from the last good calibration. This error may appear on some very small actuators during the initial calibration. Recalibrating may clear the problem. |
880 |
During calibration, the Inner Loop Offset value did not settle. This could result in less accurate positioning. Repeat the stroke calibration to get a more accurate ILO value. To proceed using the less accurate ILO value, this error may be cleared by briefly pushing the quick-cal button. Lowering the gain setting may help if the actuator is unstable during the calibration. Gain settings can be physically adjusted on the device. A lower letter represents lower gain. |
881 |
Jog Cal-Set 100% Posn. |
882 |
Indicates that during a jog calibration, the unit is waiting for the user to manually adjust the valve position to the desired 100% open position. Use the buttons on the positioner to adjust the valve to the desired fully open position. See the explanation of Jog Calibrate in the Quick-Cal section of main document for operation. |
883 |
Command Loop Status |
884 |
Command Loop status |
885 |
Indicates that during a Command Loop Calibration, the difference between the signal at 0% and the signal at 100% was too small. The system is designed to accept a difference greater than 2 mA. Recalibrate making sure to use a larger difference between command signal limits. The difference must exceed 2 mA. |
886 |
Indicates that during Command Loop Calibration, the 100% signal was out of range. The system is designed to accept a signal that is between approximately 3.5 mA and 22 mA. Recalibrate making sure to set the limits inside that range. |
887 |
Indicates that during Command Loop Calibration, the 0% signal was out of range. The system is designed to accept a signal that is between approximately 3.5 mA and 22 mA. Recalibrate making sure to set the limits inside that range. |
888 |
Indicates during an Analog Output Calibration the difference between the milliamp signal at 0% and the milliamp signal at 100% was too small. Recalibrate making sure to use a larger difference between signal limits. |
889 |
Configuration Indicators |
890 |
Configuration indicators |
891 |
When LOCKED, this indicates that the positioner feedback sensor is rotating clockwise to close. This affects the fail safe position of the valve in the event of linkage failure. In normal configurations, a spring will turn the sensor counter-clockwise upon release of the feedback linkage. Use the Valve Stability DIP switch to toggle this mode on or off. If high friction is set and this indicator never comes on, the error band limits may need to be adjusted. |
892 |
When REVERSED, this indicates that the positioner feedback sensor is rotating clockwise to close. In normally configured positioners, a spring will turn the sensor counter-clockwise upon release of the feedback linkage. This affects the fail safe position of the valve in the event of linkage failure. Ensure the feedback sensor spring will lead to a proper fail safe position. If needed, an optional internal biasing spring is available that can change the direction of failure position if the feedback linkage should break. |
893 |
Valve Travel |
894 |
Value of the Travel Accumulator. The Travel Accumulator measures the distance the valve stem has traveled since the last reset. Travel Deadband defines how large a stem movement is allowed before travel accumulator increases. The Travel Accumulator can be reset to zero using Reset Travel Count method. |
895 |
10.2f |
896 |
Valve Travel High Start |
897 |
Valve Travel High End |
898 |
Valve Travel % Yellow |
899 |
Valve Travel Length |
900 |
Valve Cycle High Start |
901 |
Valve Cycle High End |
902 |
Valve Cycle % Yellow |
903 |
Valve Cycle Deadband |
904 |
Pst Time Breakaway |
905 |
Measured when the valve has moved ½ % from the starting position |
906 |
Pst Pressure Difference |
907 |
The differential pressure in the actuator for double acting or the actuator pressure for single acting measured at the breakaway point. |
908 |
Pst Time To Target |
909 |
Actual time it took for the valve to arrive within 2% of the final value. |
910 |
6.3f |
911 |
Pst Time Limit |
912 |
Time used for pass/fail criteria for the partial stroke test. (0 to 60 sec.) |
913 |
3.2f |
914 |
Pst Result |
915 |
Gives a pass/fail indication of the test based on the reference time to target and the actual time to target. |
916 |
Fail |
917 |
The positioner has failed the partial stroke tes. |
918 |
Pass |
919 |
The positioner has passed the partial stroke test. |
920 |
Actuation Ratio High Start Limit |
921 |
Actuation Ratio Low Start Limit |
922 |
Actuation Ratio Percent |
923 |
Pilot Relay Cycle Count |
924 |
Pilot Relay Cycle High Start Limit |
925 |
Pilot Relay Cycle High End Limit |
926 |
Pilot Relay Cycle Percent Yellow |
927 |
Pilot Relay Travel Count |
928 |
Pilot Relay Travel High Start Limit |
929 |
Pilot Relay Travel High End Limit |
930 |
Pilot Relay Travel Percent Yellow |
931 |
Pilot Relay Cycle and Travel Reset |
932 |
Reset Pilot Relay Cycles |
933 |
help |
934 |
Reset Pilot Relay Travel |
935 |
Trend Index |
936 |
Trend Year |
937 |
Trend Month |
938 |
Trend Day |
939 |
Trend Hour |
940 |
Trend Minute |
941 |
Trend Second |
942 |
Trend Command |
943 |
Trend Position |
944 |
Trend Friction |
945 |
Trend Supply |
946 |
Trend Temp |
947 |
Trend State |
948 |
Return LLT Status |
949 |
Release LLT |
950 |
Freeze LLT |
951 |
Clear Trend and Friction Tables |
952 |
Clear Trend Table |
953 |
Clear Friction Table |
954 |
Stick Deviation |
955 |
Stick Start |
956 |
Stick End |
957 |
Stick Percent |
958 |
Pneumatic Leak Count |
959 |
Pneumatic Leak Start |
960 |
Pneumatic Leak End |
961 |
Pneumatic Leak Percent |
962 |
Place Holder Variable - Data Unreliable |
963 |
Force on the Piston |
964 |
Force on the Spring |
965 |
Force Rate |
966 |
Force Actuator |
967 |
Deviation Times Gain |
968 |
Piston Rate |
969 |
Friction Stability |
970 |
Friction Count |
971 |
Friction Rate Depend Up |
972 |
Friction Rate Depend Down |
973 |
Friction Starting |
974 |
Spring Forces 15 |
975 |
Spring Forces 85 |
976 |
Spring Rate |
977 |
Spring Preload |
978 |
Worst Valve |
979 |
Worst Actuator |
980 |
Worst Positioner |
981 |
Worst Control |
982 |
Supply Pressure Calibrated |
983 |
Supply pressure in user units used as basis for pressure sensor calibrations. Displayed value does not change until DD restart. |
984 |
Supply Pressure High Start |
985 |
Supply Pressure Low Start |
986 |
Supply Pressure Low End |
987 |
Supply Pressure High Percent |
988 |
Supply Pressure Low Percent |
989 |
Friction Status |
990 |
Friction High Start |
991 |
Friction High End |
992 |
Friction Low Start |
993 |
Friction High Percent Yellow |
994 |
Friction Low Percent Yellow |
995 |
Command not impleented |
996 |
Actuator |
997 |
Allows access to Actuator Manufacturer, Actuator Size, and selection, etc. |
998 |
Alarm Masks |
999 |
Allows access to available alarm and alert masks. Masks let you "turn off" unwanted alarms and alerts. |
1000 |
Alerts & Alarms |
1001 |
Allows access to Current Alarms, Alarm Masks, Error History, Temperature History, and the Hour Meters. |
1002 |
Burst Mode Settings |
1003 |
Allows access to view and change burst mode settings. |
1004 |
Allows access to Actuator/Stroke/Friction Calibration, Stroke Calibration, Analog Output Calibration, and Analog Input Calibration functions. |
1005 |
Partial Stroke Test |
1006 |
Parameters needed to run a partial Stroke Test. |
1007 |
Allows access to Partial Stroke Test. |
1008 |
Advanced Diagnostics |
1009 |
Custom Characterization Settings |
1010 |
Change individual characterization "y" values. |
1011 |
Configuration |
1012 |
Allows access to Device Configuration, Positioner Tuning, Pressure Control, Soft Limits & Cut-off, User Preferences, Device Information, Read Register, and Write Register. |
1013 |
Current Alarms |
1014 |
View all current alarms, alerts, modes, and states. |
1015 |
Change Travel Limit |
1016 |
Changing the Travel Limit allows you to control the Travel Limit warning level. |
1017 |
Valve Cycle / Travel Info |
1018 |
Allows access to the valve cycle and travel information and settings. |
1019 |
Change Air Action |
1020 |
Use to change air action from/to Air-to-Open/Air-to-Close. |
1021 |
Change Characterization |
1022 |
Select characterization for stem movement. Choices are linear, equal %, and custom. |
1023 |
Device Config |
1024 |
Allows access to Local Interface, Air Action, 4-20 mA signal configuration, Characterization, Auto Tuning, Valve Stability, Stroke Calibration type, Reset to Factory Default, and whether the positioner has been calibrated since last reset. |
1025 |
Device Info |
1026 |
Allows access to HART Information, Positioner version information, Actuator information, Valve Trim information, and Valve Body information. |
1027 |
Dynamic Vars |
1028 |
Event History |
1029 |
Allows access to last eight errors that occurred, the event count, and the ability to reset the Error History. |
1030 |
Hot Key Menu |
1031 |
Hour Meters |
1032 |
Displays hours of operation. |
1033 |
Position Alerts |
1034 |
Allows you to change position alert settings. Controls the Position Upper and Lower Limit Alert. |
1035 |
Positioner Revisions |
1036 |
View the positioner internal version and revision information. |
1037 |
Tuning values |
1038 |
Allows editing of positioner response tuning values. |
1039 |
Positioner Tuning |
1040 |
Allows access to the Positioner Tuning edit display. |
1041 |
Pressures |
1042 |
Displays pressure values. |
1043 |
Main Menu |
1044 |
Access to all available positioner functionality and data. |
1045 |
Limits |
1046 |
Edit Soft Limits and Position Cut-off limits. |
1047 |
Soft Limits & Cutoff |
1048 |
Allows access to Soft Limits and Position Cut-off limits edit display. |
1049 |
Enable/Disable pressure control |
1050 |
Allows user to Enable/Disable pressure control. |
1051 |
Pressure Control |
1052 |
Allows access to Pressure Control status and settings. |
1053 |
Change Command Source |
1054 |
Use to toggle command source Analog/Digital - Digital/Analog. |
1055 |
Status |
1056 |
Allows access to realtime command, position, and temperature data. Allows access to change the command source. If equipped, pressure data is also available. |
1057 |
Positioner |
1058 |
View HART information, change HART tag name, message, descriptor, and date. |
1059 |
Temperature History |
1060 |
Displays the temperatures attained during operation. |
1061 |
Upload Variables |
1062 |
Units |
1063 |
Allows you to view and change the pressure, if equipped, and temperature units of measure. |
1064 |
User Preferences |
1065 |
Allows access to Cycle and Travel Limits, Position Travel Alerts Configuration, Units of Measure, and Burst Mode Control. |
1066 |
Valve Body |
1067 |
Allows access to valve body information. |
1068 |
Valve Trim |
1069 |
Allows access to valve trim information and settings. |
1070 |
Positioning Information |
1071 |
Positioner Settings |
1072 |
View current positioner settings: diagnostics capabilities, positioner model, and characterization. |
1073 |
Process Variables |
1074 |
Repeatability, (%) |
1075 |
Electronics Temperature |
1076 |
Rueger |
1077 |
Mettler Toledo |
1078 |
Det-Tronics |
1079 |
TN Technologies |
1080 |
DeZURIK |
1081 |
Phase Dynamics |
1082 |
WELLTECH SHANGHAI |
1083 |
ENRAF |
1084 |
4tech ASA |
1085 |
Brandt Instrument |
1086 |
Nivelco |
1087 |
Camille Bauer |
1088 |
Metran |
1089 |
Milton Roy Co. |
1090 |
PMV |
1091 |
Turck |
1092 |
Panametrics |
1093 |
Stahl |
1094 |
Fieldbus International |
1095 |
BERTHOLD |
1096 |
InterCorr |
1097 |
China BRICONTE Co Ltd |
1098 |
Electron Machine |
1099 |
Sierra Instruments |
1100 |
Fluid Componenets |
1101 |
HART Communication Foundation |
1102 |
PSK Capable Device |
1103 |
PSK With Loop Current Signaling Disabled |
1104 |
Maintenance Required |
1105 |
Device Variable Alert |
1106 |
Lock Device Codes |
1107 |
Unlock |
1108 |
Temporary Lock |
1109 |
Permanent Lock |
1110 |
Write Device Variable Codes |
1111 |
Normal |
1112 |
Fix Value |
1113 |
Device Variable Family Codes |
1114 |
Simple PID |
1115 |
pH |
1116 |
Conductivity |
1117 |
Totalizer |
1118 |
Device Variable not Classified |
1119 |
Volumetric Flow |
1120 |
Volume |
1121 |
Length |
1122 |
Time |
1123 |
Mass |
1124 |
Mass Flow |
1125 |
Mass per Volume |
1126 |
Viscosity |
1127 |
Angular Velocity |
1128 |
Area |
1129 |
Energy (Work) |
1130 |
Force |
1131 |
Power |
1132 |
Frequency |
1133 |
Analytical |
1134 |
Current |
1135 |
Resistance |
1136 |
Angle |
1137 |
Conductance |
1138 |
Volume per Volume |
1139 |
Volume per Mass |
1140 |
Concentration |
1141 |
Valve Actuator |
1142 |
Trim Point Codes |
1143 |
Lower Trim Point Supported |
1144 |
Upper Trim Point Supported |
1145 |
Lower and Upper Trim Point Supported |
1146 |
Capture Mode Codes |
1147 |
Enabled - Capture From Specified Field Device |
1148 |
Enabled - Capture from BACK messages |
1149 |
Physical Layer Type Codes |
1150 |
Asynchronous (FSK) |
1151 |
Synchronous (PSK) |
1152 |
Lock Device Status Codes |
1153 |
Device is Locked |
1154 |
Lock is Permanent |
1155 |
Locked by Primary Master |
1156 |
Channel Flags |
1157 |
Input Channel |
1158 |
Process Data Status |
1159 |
Bad |
1160 |
Manual / Fixed |
1161 |
Poor Accuracy |
1162 |
Good |
1163 |
Limit Status |
1164 |
Not Limited |
1165 |
Low Limited |
1166 |
High Limited |
1167 |
Constant |
1168 |
Device Family Status |
1169 |
More Device Family Status Available |
1170 |
FMU860 |
1171 |
DT |
1172 |
DVC |
1173 |
FCX |
1174 |
AS800 |
1175 |
340T |
1176 |
340C |
1177 |
344 |
1178 |
Siemens Micro K |
1179 |
SITRANS L |
1180 |
SIPAN PH |
1181 |
SITRANS P |
1182 |
75SMT |
1183 |
UNIDELTA |
1184 |
8320 |
1185 |
SX5100 |
1186 |
TSV175 |
1187 |
DMU |
1188 |
3780 |
1189 |
BM70 |
1190 |
Extended Device Status |
1191 |
Provides additional Device Status information |
1192 |
Loop Current Mode |
1193 |
Indicates whether the loop current is active or fixed (i.e., the device is in multi-drop) |
1194 |
8u |
1195 |
8.3f |
1196 |
.3f |
1197 |
Analog output card not detected. |
1198 |
Analog output card detected. Continue with Analog Output calibration? |
1199 |
Attach a combination current source/current measurement device to the analog output pins. |
1200 |
Adjust minimum output until current reaches desired output level. Select 'Finish' when done. |
1201 |
Finish;+ .1%;+ 1%;+ 10%;- .1%;- 1%;- 10% |
1202 |
Adjust maximum output until current reaches desired output level. Select 'Finish' when done. |
1203 |
Analog Output Range too Small. Recalibrate... |
1204 |
Analog output calibration complete. |
1205 |
Current burst command = %{0}. Select new command? |
1206 |
1;2;3;33 |
1207 |
Burst mode is disabled. Enable? |
1208 |
Burst mode is enabled. Disable? |
1209 |
Change Cycle Limit from %[d]{oldLimit} to -> |
1210 |
newlimit |
1211 |
Value out of range. Enter new value -> |
1212 |
Select new pressure units: |
1213 |
psi;bar;kg/cm²;kPa |
1214 |
This will take the valve offline i.e.the analog 4-20mA signal will not control the valve. Do you want to continue? |
1215 |
After this value is changed control will be given back to the analog 4-20mA loop. |
1216 |
Code was built on %{codemonth}/%{codeday}/%{codeyear} at
%{codehour}:%{codemin}:%{codesec} |
1217 |
Warning! You must complete every step beyond this point. Otherwise, the positioner will not control the process. Continue? |
1218 |
Please enter the date and your initials in the format MM/DD/YYYY AAA. |
1219 |
Set the loop current to 4mA, then press OK. |
1220 |
Set the loop current to the desired 0% level, usually 4mA, then press OK. |
1221 |
Set the loop current to the desired 100% level, usually 20mA, then press OK. |
1222 |
Set the loop current back to the starting level |
1223 |
4-20mA Loop Calibration Error: Range Too Small.
Press Abort to exit. Press OK to continue. |
1224 |
4-20mA Loop Calibration Error: 100% Signal out of range.
.Press Abort to exit. Press OK to continue. |
1225 |
4-20mA Loop Calibration Error: 0% Signal out of range.
Press Abort to exit. Press OK to continue. |
1226 |
4-20mA Loop Calibration Complete. |
1227 |
4-20mA Loop Calibration Error. |
1228 |
Advanced model calibration. Continue? |
1229 |
Supply pressure must be 0 to %[6.3f]{NewRange}. |
1230 |
Enter supply pressure in selected units. |
1231 |
SupplyRef |
1232 |
Supply pressure out of range. Reenter. |
1233 |
Please Wait,
Calibration Complete. |
1234 |
Please Wait,
Calibrating Pressure... |
1235 |
Please Wait,
Waiting for valve to start closing... |
1236 |
Please Wait,
Valve is closing now... |
1237 |
Please Wait,
Setting feedback offset... |
1238 |
Please Wait,
Waiting for valve to begin opening... |
1239 |
Please Wait,
Calibrating Pressure...... |
1240 |
Please Wait,
Waiting for valve to stop opening... |
1241 |
Detecting FB direction... |
1242 |
Waiting for Upper JOG setpoint... |
1243 |
Waiting to release JOG buttons... |
1244 |
Please wait,
Pressure calibration in progress... |
1245 |
Please Wait,
Valve beginning to close... |
1246 |
Please Wait,
Wait for valve to stop closing... |
1247 |
Please Wait,
Pressure calibration in progress... |
1248 |
Waiting for upper JOG setpoint... |
1249 |
Please Wait,
Detecting IL Offset... |
1250 |
Please Wait,
Performing friction calibration... |
1251 |
Pressure calibration timed out... |
1252 |
Pressure calibration zero/span error... |
1253 |
Please Wait,
Calibration In Progress... |
1254 |
Calibration complete. |
1255 |
Pressure problem during calibration. |
1256 |
Timeout error during pressure calibration. |
1257 |
Feedback out of range during pressure calibration. |
1258 |
Feedback Range < Min. Recalibrate... |
1259 |
0% Position OORange. Recalibrate... |
1260 |
100% Position OORange. Recalibrate... |
1261 |
No Motion Time Out. Recalibrate... |
1262 |
Non-Settle Time Out. Recalibrate... |
1263 |
ILO Time Out. Recalibrate... |
1264 |
Pressure calibration zero/span error... |
1265 |
Loss of Supply Pressure |
1266 |
The variables you are about to change affect the process control of the valve. |
1267 |
You must have a register map to properly use this feature. |
1268 |
What Register Type? |
1269 |
char register; int register; long register |
1270 |
Please enter the register number |
1271 |
That register contains the value
%0 unformatted |
1272 |
That register does not contain a single byte value. |
1273 |
That register does not contain an integer value. |
1274 |
That register does not contain a long value. |
1275 |
This procedure will reset the cycle counter to zero. Do you want to continue? |
1276 |
This procedure will erase the stored Event History. Do you want to continue? |
1277 |
This procedure will reset the travel count to zero. Do you want to continue? |
1278 |
This procedure will set all values for the positioner to the factory defaults. Do you want to continue? |
1279 |
The variables you are about to change affect the process control of the valve. Are you sure you want to continue? |
1280 |
You must now perform Stroke Calibration for the positioner to operate properly. Perform stroke calibration now? |
1281 |
Actuator manufacturer - |
1282 |
Valtek (Piston);Kämmer;Valtek (Diaphragm Rotary);Automax;NAF;Valtek (Diaphragm Linear);Fisher;Other |
1283 |
Actuator model - |
1284 |
25;50;100;100C;150C;200;200C;300;400;500;600;Other |
1285 |
37;38;39;3D;47;48;49;4D;P0;P1;P2;P3;P4;P5;P6;P7;Other |
1286 |
NR1;NR2;NR3;Other |
1287 |
B050D;B063D;B085D;B100D;B115D;B125D;B150D;B175D;B200D;SNA250;SNA300;R205;R206;R207;R208;R310;R312;R314;R316;R414;R416;R418;R420;R422;R514;R516;R518;R520;R522;R524;Other |
1288 |
-02;-11;-12;-21;-22;-31;-32;-41;-42;-51;-52;Other |
1289 |
Actuator size - |
1290 |
127;252;502;700;1502;3002;Other |
1291 |
657-30;657-34;657-40;657-45;657-46;657-50;657-60;657-70;657-80;657-87;657-100;667-30;667-34;667-40;667-45;667-46;667-50;667-60;667-70;667-80;667-87;667-100;Other |
1292 |
Enter the four variables to burst? |
1293 |
Please enter Burst Variable #1. |
1294 |
Please enter Burst Variable #2. |
1295 |
Please enter Burst Variable #3. |
1296 |
Please enter Burst Variable #4. |
1297 |
This procedure will cause closure member movement.
Please, follow all safety procedures.
Continue? |
1298 |
Enter the Partial Stroke Test starting position. (110% to -10%) |
1299 |
Enter the Partial Stroke stopping position. (110% to -10%) |
1300 |
Enter time limit to reach stopping. (0 to 60 sec.) |
1301 |
Partial Stroke Test initiated. Please wait... |
1302 |
Partial Stroke Test completed on positioner. |
1303 |
The valve cannot control the process flow while calibrating. Do you want to continue? |
1304 |
Please enter the date and your initials in the format
MM/DD/YYYY AAA |
1305 |
Please Wait,
Calibrating Stroke... |
1306 |
Please wait,
Stroke calibration in progress... |
1307 |
Please Wait,
Stroke calibration in progress... |
1308 |
Stroke calibration timed out... |
1309 |
Stroke calibration zero/span error... |
1310 |
Calculating friction... |
1311 |
This procedure takes approximately 5 minutes to complete. Continue? |
1312 |
Taking control of positioner. Continue? |
1313 |
Enter settling time in seconds -> |
1314 |
liWaitTime |
1315 |
%[1.2f]{lfPercDone}% complete. |
1316 |
This is a dangerous feature. Writing directly to registers can make the valve unusable until a factory reset. |
1317 |
char register;int register;long register |
1318 |
Please enter the register value |
1319 |
Register value changed to
%{0} unformatted |
1320 |
That register does not contain a single byte value or is read only. |
1321 |
Registers value changed to
%{0} unformatted |
1322 |
That register does not contain an integer value or is read only. |
1323 |
That register does not contain a long value or is read only. |
1324 |
Change Travel Limit from %[d]{oldLimit} to -> |
1325 |
Changing air-action may cause closure member movement.
Please, follow all safety procedures.
Continue? |
1326 |
Current air-action setting = %{setting}. (0=ATC; 1=ATO) |
1327 |
ATC;ATO |
1328 |
Changing characterization type may cause closure member movement.
Please, follow all safety procedures.
Continue? |
1329 |
Current characterization type = %{setting}.
0=Custom
4 or 12=Linear
8=Equal percent
|
1330 |
Custom;Linear;Equal percent |
1331 |
Enabling/Disabling Pressure Control will affect positioning control.
Follow all safety procedures.
Continue? |
1332 |
Current Pressure Control setting = %{setting}. (0=Disabled; 8=Enabled) |
1333 |
Disable;Enable |
1334 |
Changing Command Source may cause closure member movement.
Please, follow all safety procedures.
Continue? |
1335 |
Desired Command Source setting = %{setting}. (0=Analog; 64=Digital).
Change to -> |
1336 |
Analog;Digital |