0 |
FLOWSERVE |
1 |
Logix420 |
2 |
Mode Status 0 |
3 |
Factory Reset State |
4 |
Indicates the unit has had a factory reset and has not yet been calibrated. The unit will not respond to commands and will remain in the failsafe position until a calibration is successfully completed. Proper operation will require stroke, actuator, and friction calibration to be completed. This indicator can be disabled. |
5 |
Calibration in Progress |
6 |
Indicates the device is being calibrated. |
7 |
Signature in Progress |
8 |
Indicates a signature or PST is in progress. |
9 |
Jog Command Mode |
10 |
Indicates the unit has been placed in a local override mode where the valve can only be stroked using the two local jog buttons. Control the valve using the jog buttons. This mode may be canceled by briefly pushing the quick-cal button. |
11 |
Reserved |
12 |
TBD |
13 |
Feedback Loop Status 1 |
14 |
Psn Deviation ALM |
15 |
The device is not controlling at the set point. |
16 |
Psn Sensor Fail ALM |
17 |
The feedback arm may be disconnected from the valve assembly. |
18 |
Opened Too Far WRN |
19 |
The valve has opened farther than it did at the last calibration. |
20 |
Closed Too Far WRN |
21 |
The valve has closed farther than it did at the last calibration. |
22 |
PST Failed WRN |
23 |
The last partial stroke test failed. |
24 |
Position Status 2 |
25 |
Psn High Limit Alert |
26 |
The Position High Limit has been reached. The command and valve position are above the limit. |
27 |
Psn Low Limit Alert |
28 |
The Position Low Limit has been reached. The command and valve position are below the limit. |
29 |
Feedback Linkage Alarm |
30 |
The feedback linkage is broken or the position feedback POT is out of range. |
31 |
Cycles_Travel Status 3 |
32 |
Valve Cycles WRN |
33 |
The number of valve cycles is above the warning limit set by the user. |
34 |
Valve Travel WRN |
35 |
The amount of valve travel is above the warning limit set by the user. |
36 |
Pilot Cycles WRN |
37 |
The number of pilot relay cycles is above the warning limit. |
38 |
Pilot Travel WRN |
39 |
The amount of pilot relay travel is above the warning limit. |
40 |
Aux Mode Bits 4 |
41 |
Actuation Status 5 |
42 |
Supply Press Low ALM |
43 |
The supply pressure is below the low alarm limit. |
44 |
Friction 14 |
45 |
Control 15 |
46 |
Inner Loop 16 |
47 |
Pilot Response WRN |
48 |
The pilot relay response time is above the warning limit. |
49 |
Pilot Response ALM |
50 |
The pilot relay response time is above the alarm limit or the pilot relay is stuck open. |
51 |
Piezo Volts High WRN |
52 |
The voltage driving the piezo is above the warning limit. |
53 |
Piezo Volts High ALM |
54 |
The voltage driving the piezo is above the alarm limit. |
55 |
Piezo Volts Low WRN |
56 |
The voltage driving the piezo is below the warning limit. The valve may not fail safe on loss of power. |
57 |
Piezo Volts Low ALM |
58 |
The voltage driving the piezo is below the alarm limit. The valve may not fail safe on loss of power. |
59 |
Driver Module ALM |
60 |
The pilot relay can't open, the pilot relay can't shut, or the Hall sensor circuit has failed. |
61 |
Main Board 17 |
62 |
Main Board Fail WRN |
63 |
There has been an oscillator fault, position sensor ADC failure, supply voltage error, reference voltage error, shunt voltage error, or piezo voltage error. |
64 |
Software Error WRN |
65 |
There has been a watch dog time out, stack overflow warning, or CPU usage warning. |
66 |
Memory Error WRN |
67 |
CPU/FRAM has a memory problem. |
68 |
Not Applicable |
69 |
Temp High WRN |
70 |
The temperature in the positioner is above the high limit. |
71 |
Temp Low WRN |
72 |
The temperature in the positioner is below the low limit. |
73 |
Aux Boards 18 |
74 |
spare 1 19 |
75 |
spare 2 20 |
76 |
spare 3 21 |
77 |
CMD 48: Read additional device status |
78 |
cmd LS |
79 |
cmd PDQ |
80 |
Command Perc |
81 |
|
82 |
% |
83 |
cmd Fmly stat |
84 |
Command Units |
85 |
FB Class |
86 |
FB LS |
87 |
FB PDQ |
88 |
FB Fmly stat |
89 |
Position damping value |
90 |
5.2f |
91 |
Lower position limit |
92 |
5.1f |
93 |
Position minimum span |
94 |
.1f |
95 |
Position upper limit |
96 |
Position |
97 |
SP Class |
98 |
Final command |
99 |
Tertiary units |
100 |
Temperature |
101 |
UD1 Class |
102 |
UD1 LS |
103 |
UD1 PDQ |
104 |
UD1 Fmly stat |
105 |
UD2 Class |
106 |
UD2 LS |
107 |
UD2 PDQ |
108 |
UD2 Fmly stat |
109 |
Analog Command Units |
110 |
FeedBack USL |
111 |
FeedBack LSL |
112 |
FeedBack min span |
113 |
FeedBack damping value |
114 |
FeedBack snr |
115 |
Digital Command |
116 |
Digital Command Value |
117 |
Digital Command Units |
118 |
Digital Command PDQ |
119 |
Digital Command LS |
120 |
Digital Command Fmly stat |
121 |
Digital Command Classification |
122 |
CmdPctDigital USL |
123 |
CmdPctDigital LSL |
124 |
CmdPctDigital min span |
125 |
CmdPctDigital damping value |
126 |
CmdPctDigital snr |
127 |
Control Signal |
128 |
Control Signal Value |
129 |
Control Signal Units |
130 |
Control Signal PDQ |
131 |
Control Signal LS |
132 |
Control Signal Fmly stat |
133 |
Control Signal Classification |
134 |
CmdPct USL |
135 |
CmdPct LSL |
136 |
CmdPct min span |
137 |
CmdPct damping value |
138 |
CmdPct snr |
139 |
Command Input Target |
140 |
Command Input Target Value |
141 |
Command Input Target Units |
142 |
Command Input Target PDQ |
143 |
Command Input Target LS |
144 |
Command Input Target Fmly stat |
145 |
Command Input Target Classification |
146 |
CmdPctTarget USL |
147 |
CmdPctTarget LSL |
148 |
CmdPctTarget min span |
149 |
CmdPctTarget damping value |
150 |
CmdPctTarget snr |
151 |
Valve Stem Position |
152 |
Position Units |
153 |
Position PDQ |
154 |
Position LS |
155 |
Position Fmly stat |
156 |
Position Classification |
157 |
PsnPct USL |
158 |
PsnPct LSL |
159 |
PsnPct min span |
160 |
PsnPct damping value |
161 |
PsnPct snr |
162 |
Deviation |
163 |
Deviation Value |
164 |
Deviation Units |
165 |
Deviation PDQ |
166 |
Deviation LS |
167 |
Deviation Fmly stat |
168 |
Deviation Classification |
169 |
DevPct USL |
170 |
DevPct LSL |
171 |
DevPct min span |
172 |
DevPct damping value |
173 |
DevPct snr |
174 |
Pilot Relay Command |
175 |
Pilot Relay Command Value |
176 |
Pilot Relay Command Units |
177 |
Pilot Relay Command PDQ |
178 |
Pilot Relay Command LS |
179 |
Pilot Relay Command Fmly stat |
180 |
Pilot Relay Command Classification |
181 |
PilotCmdPct USL |
182 |
PilotCmdPct LSL |
183 |
PilotCmdPct min span |
184 |
PilotCmdPct damping value |
185 |
PilotCmdPct snr |
186 |
Pilot Relay Position |
187 |
Pilot Relay Position Value |
188 |
Pilot Relay Position Units |
189 |
Pilot Relay Position PDQ |
190 |
Pilot Relay Position LS |
191 |
Pilot Relay Position Fmly stat |
192 |
Pilot Relay Position Classification |
193 |
PilotPsnPct USL |
194 |
PilotPsnPct LSL |
195 |
PilotPsnPct min span |
196 |
PilotPsnPct damping value |
197 |
PilotPsnPct snr |
198 |
Temperature Value |
199 |
Temperature Units |
200 |
Temperature PDQ |
201 |
Temperature LS |
202 |
Temperature Fmly stat |
203 |
Temperature Classification |
204 |
Temperature USL |
205 |
Temperature LSL |
206 |
Temperature min span |
207 |
Temperature damping value |
208 |
Temperature snr |
209 |
Pilot Response Time |
210 |
Pilot Response Time Value |
211 |
Pilot Response Time Units |
212 |
Pilot Response Time PDQ |
213 |
Pilot Response Time LS |
214 |
Pilot Response Time Fmly stat |
215 |
Pilot Response Time Classification |
216 |
PilotResponseTime USL |
217 |
PilotResponseTime LSL |
218 |
PilotResponseTime min span |
219 |
PilotResponseTime damping value |
220 |
PilotResponseTime snr |
221 |
4-20 Command (mA) |
222 |
4-20 Command (%) |
223 |
Digital Command (%) |
224 |
Control Signal (%) |
225 |
Command Input, Actual Target, % |
226 |
Position (%) |
227 |
Deviation (%) |
228 |
Pilot Relay Command (%) |
229 |
Pilot Relay Position (%) |
230 |
Ambient Temperature |
231 |
Pilot Relay Response Time |
232 |
Actuation Status Mask |
233 |
Bit3=Supply Press Lo ALM |
234 |
Supply Press Lo ALM |
235 |
Mask or disable this alarm or warning |
236 |
Actuation Status |
237 |
Actuator Size |
238 |
Actuator Size / area |
239 |
Displays and allows selection of actuator manufacturer. |
240 |
Manufacturer |
241 |
Valtek (Piston) |
242 |
Kammer |
243 |
Valtek (Diaphragm Rotary) |
244 |
Automax |
245 |
NAF |
246 |
Valtek (Diaphragm Linear) |
247 |
Fisher |
248 |
Worcester/Norbro |
249 |
Other |
250 |
Not Configured |
251 |
Displays Actuator Model |
252 |
Actuator Model |
253 |
25 |
254 |
50 |
255 |
100 |
256 |
100C |
257 |
150C |
258 |
200 |
259 |
200C |
260 |
300 |
261 |
400 |
262 |
500 |
263 |
600 |
264 |
37 |
265 |
38 |
266 |
39 |
267 |
3D |
268 |
47 |
269 |
48 |
270 |
49 |
271 |
4D |
272 |
P0 |
273 |
P1 |
274 |
P2 |
275 |
P3 |
276 |
P4 |
277 |
P5 |
278 |
P6 |
279 |
P7 |
280 |
NR1 |
281 |
NR2 |
282 |
NR3 |
283 |
B050D |
284 |
B063D |
285 |
B085D |
286 |
B100D |
287 |
B115D |
288 |
B125D |
289 |
B150D |
290 |
B175D |
291 |
B200D |
292 |
SNA250 |
293 |
SNA300 |
294 |
R205 |
295 |
R206 |
296 |
R207 |
297 |
R208 |
298 |
R310 |
299 |
R312 |
300 |
R314 |
301 |
R316 |
302 |
R414 |
303 |
R416 |
304 |
R418 |
305 |
R420 |
306 |
R422 |
307 |
R514 |
308 |
R516 |
309 |
R518 |
310 |
R520 |
311 |
R522 |
312 |
R524 |
313 |
02 |
314 |
11 |
315 |
12 |
316 |
21 |
317 |
22 |
318 |
31 |
319 |
32 |
320 |
41 |
321 |
42 |
322 |
51 |
323 |
52 |
324 |
127 |
325 |
252 |
326 |
502 |
327 |
700 |
328 |
1502 |
329 |
3002 |
330 |
657-30 |
331 |
657-34 |
332 |
657-40 |
333 |
657-45 |
334 |
657-46 |
335 |
657-50 |
336 |
657-60 |
337 |
657-70 |
338 |
657-80 |
339 |
657-87 |
340 |
657-100 |
341 |
667-30 |
342 |
667-34 |
343 |
667-40 |
344 |
667-45 |
345 |
667-46 |
346 |
667-50 |
347 |
667-60 |
348 |
667-70 |
349 |
667-80 |
350 |
667-87 |
351 |
667-100 |
352 |
RG106 |
353 |
RG107 |
354 |
RG108 |
355 |
RG109 |
356 |
RG110 |
357 |
RG112 |
358 |
RG208 |
359 |
RG209 |
360 |
RG210 |
361 |
RG212 |
362 |
RG214 |
363 |
RG216 |
364 |
RG310 |
365 |
RG312 |
366 |
RG314 |
367 |
RG316 |
368 |
RG318 |
369 |
RG320 |
370 |
RG414 |
371 |
RG416 |
372 |
RG418 |
373 |
RG420 |
374 |
RG422 |
375 |
RG424 |
376 |
RG516 |
377 |
RG518 |
378 |
RG520 |
379 |
RG522 |
380 |
RG524 |
381 |
RG528 |
382 |
RG618 |
383 |
RG620 |
384 |
RG622 |
385 |
RG624 |
386 |
RG628 |
387 |
RG632 |
388 |
RG636 |
389 |
RG724 |
390 |
RG728 |
391 |
RG732 |
392 |
RG736 |
393 |
RG740 |
394 |
RG828 |
395 |
RG832 |
396 |
RG832T |
397 |
RG836 |
398 |
RG836T |
399 |
RG840 |
400 |
05 |
401 |
10 |
402 |
15 |
403 |
20 |
404 |
30 |
405 |
33 |
406 |
35 |
407 |
40 |
408 |
45 |
409 |
Spring type i.e. single or heavy duty etc. |
410 |
Actuator Spring |
411 |
Single |
412 |
Heavy duty |
413 |
Dual |
414 |
Multi |
415 |
None |
416 |
Standard |
417 |
1 |
418 |
2 |
419 |
3 |
420 |
4 |
421 |
5 |
422 |
6 |
423 |
7 |
424 |
8 |
425 |
9 |
426 |
Actuator type i.e. linear or rotary; piston or diaphragm etc. |
427 |
Actuator Style |
428 |
Linear (piston) |
429 |
Linear (diaphragm) |
430 |
Rotary (piston) |
431 |
Rotary (diaphragm) |
432 |
Rotary (rach & pinion) |
433 |
Displays the ID of Aux card 1 |
434 |
Aux Card 1 ID |
435 |
No Card |
436 |
MFC |
437 |
Safety DO |
438 |
Displays the ID of Aux card 2 |
439 |
Aux Card 2 ID |
440 |
Displays the Type of aux Card 1 |
441 |
Aux Card 1 Type |
442 |
Analog Output |
443 |
Discrete Output |
444 |
Discrete Input |
445 |
Displays the Type of aux Card 2 |
446 |
Aux Card 2 Type |
447 |
Command calibration bits |
448 |
Cal Cmd Config |
449 |
Set Command to OOS |
450 |
Set 4mA Position |
451 |
Set 0% Position |
452 |
Set 100% Position |
453 |
Cal Get Date Pntr |
454 |
Used in command 185 and 186 as a pointer to which cal date to read. |
455 |
Stroke Calibration |
456 |
Pressure Calibration |
457 |
Friction Calibration |
458 |
Triple Calibration |
459 |
Command Input Calibration |
460 |
Analog Output Calibration |
461 |
Cal Put Date Pntr |
462 |
Used in command 185 and 186 as a pointer to which cal date to write. |
463 |
Cal Date/Time |
464 |
The that the last calibration took place. |
465 |
Who Ran Calibration |
466 |
Initials of who ran the last calibration. |
467 |
Displays and sets the calibration state. |
468 |
Calibration State |
469 |
None / Abort |
470 |
Displays the position Characterization options (linear, equal %, custom, etc....) |
471 |
Other Characterization |
472 |
MaxFlo Linear |
473 |
MaxFlo Percent |
474 |
Valdisk Linear |
475 |
Valdisk Percent |
476 |
ShearStream Linear |
477 |
ShearStream Percent |
478 |
Custom |
479 |
Input 4-20mA command expressed in percent of full scale input. |
480 |
4-20 Cmd |
481 |
Enter the digital command value, in percent of full stroke. This variable is available only when the valve is being positioned by a digital command (digital source) rather than the 4-20mA analog signal (analog source). |
482 |
Digital Cmd |
483 |
The modified command signal, in percent of full stroke, which actually sets the controlled position of the valve. Cntrl Cmd is generated after custom characterization, soft limits, and minimum position cutoff parameters are evaluated. 4-20 mA command and Cntrl Cmd can differ if custom characterization, soft limits, or minimum position cutoff are active. |
484 |
Cntrl Cmd |
485 |
Control Input Source |
486 |
Contains the source of the control parameters of the input controlling signal or data. |
487 |
Digital Command Source |
488 |
Out Of Service |
489 |
Inner Loop Command Mode |
490 |
Valve Stability Enabled |
491 |
P-GAIN Enabled |
492 |
I-GAIN Enabled |
493 |
D-GAIN Enabled |
494 |
Date Day |
495 |
Current Day |
496 |
Time_Hourss |
497 |
Current time, hour parameter. |
498 |
Time_Minutes |
499 |
Current time, minutes parameter. |
500 |
Date Month |
501 |
Current Month |
502 |
January |
503 |
February |
504 |
March |
505 |
April |
506 |
May |
507 |
June |
508 |
July |
509 |
August |
510 |
September |
511 |
October |
512 |
November |
513 |
December |
514 |
Time_Seconds |
515 |
Current time, seconds parameter. |
516 |
Date Year |
517 |
Current Year. |
518 |
Cycles/Travel Mask |
519 |
Bit1=Valve Cycles WRN, Bit2=Valve Travel WRN, Bit7=Pilot Cycles WRN, Bit8=Pilot Travel WRN |
520 |
Cycles/Travel Status |
521 |
Displays the orientation of the positioner and LCD |
522 |
LCD Orientation |
523 |
Reversed |
524 |
Normal |
525 |
Displays the type of pilot relay positioner has |
526 |
Pilot Relay Type |
527 |
Spool |
528 |
Poppet |
529 |
DGain Basic Close |
530 |
D Gain Basic Close. |
531 |
DGain Basic Open |
532 |
D Gain Basic Open. |
533 |
Displays the position of the air action dip switch |
534 |
Dip Sw Air Action |
535 |
ATC |
536 |
ATO |
537 |
Displays the position of the auto tune dip switch |
538 |
Dip Sw AutoTune |
539 |
Off |
540 |
On |
541 |
Displays the position of the characterization dip switch |
542 |
Dip Sw Characterization |
543 |
Linear |
544 |
Displays the position of the pilot action dip switch |
545 |
Dip Sw Actuator |
546 |
Single Acting |
547 |
Double Acting |
548 |
Displays the position of the quick cal dip switch |
549 |
Dip Sw QuickCal |
550 |
Jog |
551 |
Auto |
552 |
Displays the position of the Signal to close dip switch |
553 |
Dip Sw Sig Closed |
554 |
20 mA |
555 |
4 mA |
556 |
Displays the position of the spare dip switch |
557 |
Dip Sw Spare |
558 |
B |
559 |
A |
560 |
Displays the position of the valve stability dip switch |
561 |
Dip Sw Stability |
562 |
High Friction |
563 |
Low Friction |
564 |
DTerm Depth Close |
565 |
D Term Depth Close. |
566 |
DTerm Depth Open |
567 |
D Term Depth Open. |
568 |
Elec Comp Status Mask |
569 |
Bit1=Pilot Can not Open, Bit2=Pilot Can not Shut, Bit3=Hall Sensor Fail, Bit4=ILO Out of Range |
570 |
Pilot Can not Open |
571 |
Pilot Can not Shut |
572 |
Hall Sensor Fail |
573 |
ILO Out of Range |
574 |
Elec Comp Status |
575 |
The pilot relay is stuck and will not move into the open position. |
576 |
The pilot relay is stuck and will not move into the closed position. |
577 |
The hall sensor has failed or is disconnected. |
578 |
ILO is not close to expected value. |
579 |
Elec Config Status Mask |
580 |
Bit4=LCD Present |
581 |
LCD Present |
582 |
Elec Config Status |
583 |
An LCD display is present. |
584 |
Serial Number of the electronics control board. |
585 |
Electronic S/N |
586 |
Embedded software release. |
587 |
Software Release |
588 |
ESR Major |
589 |
Embedded code major version number. |
590 |
ESR Minor |
591 |
Embedded code minor version number. |
592 |
Day/Year |
593 |
EventHistoryReadIndex |
594 |
EventHistoryReadIndex. |
595 |
Event State |
596 |
Event ON or OFF. |
597 |
False |
598 |
True |
599 |
Event Status |
600 |
Event indicator parameter. |
601 |
Power ON |
602 |
Initializing |
603 |
Stroke Calibration Required |
604 |
Pressure Calibration Required |
605 |
Friction Calibration Required |
606 |
Digital Command Mode |
607 |
Tight Shutoff Mode |
608 |
Valve Stability Locked |
609 |
Soft Stop High Limit Alert |
610 |
Soft Stop Low Limit Alert |
611 |
Continuous Stroke Test Mode |
612 |
Training Mode in Progress |
613 |
Training Mode Completed |
614 |
Event Captured |
615 |
Local Interface Off |
616 |
Squawk Mode |
617 |
Stroke Calibration in Progress |
618 |
Setting Inner Loop Offset |
619 |
Pressure Calibration in Progress |
620 |
Friction Calibration in Progress |
621 |
Command Input Calibration in Progress |
622 |
Analog Output Calibration in Progress |
623 |
Jog Calibration Set 100% Position |
624 |
Position Range Too Small |
625 |
Position Sensor Below ADC Range |
626 |
Position Sensor Above ADC Range |
627 |
No Motion Time Out |
628 |
Settle Time Out |
629 |
Inner Loop Offset Time Out |
630 |
Analog Output Range Too Small |
631 |
Command Input Range Too Small |
632 |
Command Input Below ADC Range |
633 |
Command Input Above ADC Range |
634 |
Stroke Shift |
635 |
Stroke Span Increase |
636 |
Stroke Span Decrease |
637 |
Aux Card 1 Present |
638 |
Aux Card 2 Present |
639 |
Pressure Sensor Board Present |
640 |
Signature or Partial Stroke Test in Progress |
641 |
Partial Stroke Test Scheduled |
642 |
DI Command Override |
643 |
Position Deviation Alarm |
644 |
Position sensor Failure Alarm |
645 |
Valve Opened Too Far Warning |
646 |
Valve Closed Too Far Warning |
647 |
Backlash Warning |
648 |
Backlach Alarm |
649 |
Partial Stroke Test Failed Warning |
650 |
Continuous Stroke Test Failed Warning |
651 |
Position High Limit Alert |
652 |
Position Low Limit Alert |
653 |
Valve Cycles Warning |
654 |
Valve Travel Warning |
655 |
Actuator Cycles Warning |
656 |
Actuator Travel Warning |
657 |
Bellows Cycles Warning |
658 |
Bellows Travel Warning |
659 |
Pilot Relay Cycles Warning |
660 |
Pilot Relay Travel Warning |
661 |
Fail Safe Mode |
662 |
Pressure Correction Mode |
663 |
Pressure Feedback Mode |
664 |
Open Feedback Loop Mode |
665 |
Open Inner Loop Mode |
666 |
Supply Pressure High Warning |
667 |
Supply Pressure Low Warning |
668 |
Supply Pressure Low Alarm |
669 |
Actuation Ratio Warning |
670 |
Spring Unable to Fail Safe Warning |
671 |
Pneumatic Leak Warning |
672 |
Air Supply Humid Warning |
673 |
Air Supply Icing Warning |
674 |
Friction High Warning |
675 |
Friction High Alarm |
676 |
Friction Low Warning |
677 |
Friction Low Alarm |
678 |
Stiction Warning |
679 |
Stiction Alarm |
680 |
Valve Can Not Open Alarm |
681 |
Valve Can Not Close Alarm |
682 |
Command Frequency Warning |
683 |
Commnad Frequency Alarm |
684 |
Command Amplitude Warning |
685 |
Command Amplitude Alarm |
686 |
Position Frequency Warning |
687 |
Position Frequency Alarm |
688 |
Position Amplitude Warning |
689 |
Position Amplitude Alarm |
690 |
Pilot Relay Response Warning |
691 |
Pilot Relay Response Alarm |
692 |
Piezo Voltage High Warning |
693 |
Piezo Voltage High Alarm |
694 |
Piezo Voltage Low Warning |
695 |
Piezo Voltage Low Alarm |
696 |
Driver Module Alarm |
697 |
Main Board Electronic Failure Warning |
698 |
Software Error Warning |
699 |
Memory Error Warning |
700 |
Loss of Inter-PCB comm Alarm |
701 |
Temp High Warning |
702 |
Temp Low Warning |
703 |
Aux Card 1 Failure Warning |
704 |
Aux Card 2 Failure Warning |
705 |
Aux Card 1 No Loop Power |
706 |
Aux Card 2 No Loop Power |
707 |
Aux Card 1 Error |
708 |
Aux Card 2 Error |
709 |
Pressure sensor Board Failure Warning |
710 |
Low Battery Warning |
711 |
Reversed Spring |
712 |
Insufficient Spring |
713 |
No Spring |
714 |
Oscillator Fault |
715 |
Position Sensor ADC Failure |
716 |
Supply Voltage Error |
717 |
Reference Voltage Error |
718 |
Shunt Voltage Error |
719 |
Piezo Voltage Error |
720 |
Pilot Can Not Open |
721 |
Pilot Can Not Shut |
722 |
Hall Sensor Failure |
723 |
NVMEM CRC Error |
724 |
RAM Error |
725 |
RAM CRC Error |
726 |
FLASH CRC Error |
727 |
Watch Dog Time Out |
728 |
Stack Overflow Warning |
729 |
CPU Usage Warning |
730 |
Firmware Update Applied |
731 |
Port S Out of Range |
732 |
Port A Out of Range |
733 |
Port B Out of Range |
734 |
Port S Range Too Small |
735 |
Port A Range Too Small |
736 |
Port B Range Too Small |
737 |
Pressure Sensor Failure |
738 |
Event 1. |
739 |
Event 2. |
740 |
Event 3. |
741 |
Event 4. |
742 |
Event 5. |
743 |
Event 6. |
744 |
Event 7. |
745 |
Event 8. |
746 |
Event 9. |
747 |
Event 10. |
748 |
Event 11. |
749 |
Event 12. |
750 |
Event 13. |
751 |
Event 14. |
752 |
Event 15. |
753 |
Event 16. |
754 |
Event 17. |
755 |
Event 18. |
756 |
Event 19. |
757 |
Event 20. |
758 |
Event 21. |
759 |
Event 22. |
760 |
Event 23. |
761 |
Event 24. |
762 |
Event 25. |
763 |
Event 26. |
764 |
Event 27. |
765 |
Event 28. |
766 |
Event 29. |
767 |
Event 30. |
768 |
Event 31. |
769 |
Event 32. |
770 |
Time |
771 |
EventTimelineConfig |
772 |
EventTimelineConfig. |
773 |
Event Day |
774 |
Event_Hours |
775 |
Event time, hour parameter. |
776 |
Event Minutes |
777 |
Event time, minutes parameter. |
778 |
Event Month |
779 |
Event Seconds |
780 |
Event time, seconds parameter. |
781 |
Event Year |
782 |
Event Year. |
783 |
FeedBack Loop Status Mask |
784 |
Bit1=Psn Deviation ALM, Bit2=Psn Sensor Fail ALM, Bit3=Opened Too Far WRN, Bit4=Closed Too Far WRN, Bit7=PST Failed WRN |
785 |
FeedBack Loop Status |
786 |
Friction in user units. |
787 |
Friction |
788 |
Valve Stability Mask |
789 |
Bit7=Valve Can Not Open ALM, Bit8=Valve Can Not Shut ALM |
790 |
Valve Can Not Open ALM |
791 |
Valve Can Not Shut ALM |
792 |
Valve Stability Status |
793 |
Pressure has been applied, but the valve is not opening. |
794 |
Pressure has been applied, but the valve is not closing. |
795 |
SAVED FOR FUTURE USE |
796 |
FUTURE USE |
797 |
Integer register Number. |
798 |
Register Number |
799 |
Integer Register Value |
800 |
Int Value |
801 |
HART Dev Type |
802 |
HART Device Type Number. |
803 |
HART Manufacturer ID |
804 |
Hart Manufactuer ID number. |
805 |
Lifetime Hours |
806 |
Number of hours positioner has run for its lifetime. |
807 |
Power Up Hours |
808 |
Number of hours positioner has since last power cycle. |
809 |
Reset Hours |
810 |
Number of hours positioner has run since last reset. |
811 |
IGain Close |
812 |
I Gain Close. |
813 |
IGain Open |
814 |
I Gain Open. |
815 |
Inner Loop Status Mask |
816 |
Bit1=Pilot Response WRN, Bit2=Pilot Response ALM, Bit3=Piezo Volts High WRN, Bit4=Piezo Volts High ALM, Bit5=Piezo Volts Low WRN, Bit6=Piezo Volts Low ALM, Bit7=Driver Module ALM |
817 |
Inner Loop Status |
818 |
Inner Loop Offset |
819 |
Diagnostics Level |
820 |
Indicates whether positioner is Standard, Advanced or Professional. |
821 |
Pressure sensors are used for control only. |
822 |
Advanced |
823 |
Pressure values and alarms are available. |
824 |
Pro |
825 |
Full diagostic features are available including friction and partial stroke testing. |
826 |
Tamper Lock |
827 |
Indicates whether the local pannel of the device has been enabled or disabled. |
828 |
Disabled |
829 |
Enabled |
830 |
Pin Code |
831 |
Pin code to disable local interface. |
832 |
Main Board Detail Status Mask |
833 |
Bit2=Oscillator Fault, Bit3=Psn Sensor ADC Fail, Bit4=Supply Voltage Error, Bit5=Ref Voltage Error, Bit6=Shunt Voltage Error, Bit7=Piezo Voltage Error |
834 |
Psn Sensor ADC Fail |
835 |
Ref Voltage Error |
836 |
Main Board Detail Status |
837 |
The CPU clock had an error. |
838 |
The feedback POT analog-to-digital converter failed. |
839 |
The supply voltage is out of range. |
840 |
The reference voltage is out of range. |
841 |
The terminal (compliance) voltage is out of range. |
842 |
The piezo driver voltage is incorrect. |
843 |
Main Board Status Mask |
844 |
Bit1=Main Board Fail WRN, Bit2=Software Error WRN, Bit3=Memory Error WRN, Bit4=Not Applicable, Bit5=Temperature High WRN, Bit6=BTemperature Low WRN |
845 |
Main Board Status |
846 |
Min Close Time |
847 |
Min Close Time. |
848 |
sec. |
849 |
Min Open Time |
850 |
Min Open Time. |
851 |
Mode Status Mask 1 |
852 |
Bit1=Dig Cmd Mode, Bit2=Tight Shut Off mode, Bit3=Valve Stability Lock, Bit4=Soft Stop High Alert, Bit5=Soft Stop Low Alert |
853 |
Digital Cmd Mode |
854 |
Tight Shut Off Mode |
855 |
Valve Stability Lock |
856 |
Soft Stop High Alert |
857 |
Soft Stop Low Alert |
858 |
Mode States Status Mask |
859 |
Bit1=Factory Reset State, Bit2=Calibration in Prog, Bit3=Signature or PST, Bit4=Jog Cmd Mode |
860 |
Calibration in Prog |
861 |
Signature or PST |
862 |
Jog Cmd Mode |
863 |
Mode Status 1 |
864 |
The device is in digital command mode. |
865 |
One side of the actuator has full supply pressure while the other is fully vented to ensure a tight shut-off. |
866 |
The positioner is actively using pressure readings to keep the valve steady. |
867 |
The Soft Stop High Limit has been reached. The command is above the limit. The positioner is holding the valve position at the limit. |
868 |
The Soft Stop Low Limit has been reached. The command is below the limit. The positioner is holding the valve position at the limit. |
869 |
Mode States Status |
870 |
The positioner is in factory reset state. Calibration is required to enable control. |
871 |
A calibration is in progress. |
872 |
A partial stroke test, ramp test, step test, or inner loop signature is in progress. |
873 |
The device is responding to manual input using the jog buttons. |
874 |
Pilot Cyc Full Warning |
875 |
Pilot valve Cycles high end limit. |
876 |
Cycles |
877 |
Pilot Cyc Hi % Warning |
878 |
Pilot valve Cycles high percent Warning. |
879 |
Pilot Cyc Initial Warning |
880 |
Pilot valve Cycles high start limit. |
881 |
PGain Max Close |
882 |
P Gain at Max Close. |
883 |
PGain Max Open |
884 |
P Gain at Max Open. |
885 |
PGain Mult Close |
886 |
P Gain Multiplier Close. |
887 |
PGain Mult Open |
888 |
P Gain Multiplier Open. |
889 |
Pilot Cycles |
890 |
Pilot valve Cycles. |
891 |
Pilot Cycle Rate |
892 |
Pilot valve Cycles center rate monitor. |
893 |
Pilot Resp Time |
894 |
Pilot Travel |
895 |
Pilot valve travel. |
896 |
x100% |
897 |
Pilot Trav Cntr Rate Mon |
898 |
Pilot valve travel center rate monitor. |
899 |
cycles/day |
900 |
The difference between the modified position command (Cntrl Cmd) signal and the stem position signal expressed in percent of full stroke. Deviation = Position - Cntrl Cmd. |
901 |
Pos Deviation |
902 |
Displays positioner model number |
903 |
Model Number |
904 |
Logix 505MD+ |
905 |
Logix 510MD+ |
906 |
Logix 520MD+ |
907 |
Logix 3100MD+ |
908 |
Logix 3200MD+ |
909 |
Logix 420 |
910 |
Actual stem position in percent of full stroke, as measured by the position stem position transducer. |
911 |
Tight Shutoff Active |
912 |
Is position Tight Shutoff Mode active. |
913 |
Position Status Mask |
914 |
Bit1=Psn High Limit Alert, Bit2=Psn Low Limit Alert, Bit3=Feedback Linkage Alarm |
915 |
Position Status |
916 |
Window Gain |
917 |
Gain of the Valve Stability window. |
918 |
Pressure Lock |
919 |
Indicates that the current position is within the Valve Stability Window. |
920 |
No |
921 |
Yes |
922 |
Window Mult |
923 |
Multiplier of the Valve Stability window. |
924 |
Window |
925 |
Size of the Valve Stability window. |
926 |
Pilot Resp Alarm |
927 |
Pilot Response high end limit |
928 |
Pilot Resp % Warning |
929 |
Pilot Response High Percent Warning |
930 |
Pilot Resp Warning |
931 |
Pilot Response high start limit |
932 |
Priority Alarm |
933 |
The position deviation deadband. |
934 |
Posn Dev Deadband |
935 |
The position deviation time. |
936 |
Posn Dev Time |
937 |
The high position that the alert is turned on. |
938 |
Position High Setpoint |
939 |
The low position that the alert is turned on. |
940 |
Position Low Setpoint |
941 |
Force at Breakaway |
942 |
Pressure measured at movement. |
943 |
6.2f |
944 |
PST Result |
945 |
Gives a pass/fail indication of the test based on the reference time to target and the actual time to target. |
946 |
Fail |
947 |
Pass |
948 |
Not Run |
949 |
In Progress |
950 |
Aborted by User |
951 |
Aborted On Cmd |
952 |
PST Time Limit |
953 |
Actual time it took for the valve to arrive within 2% of the final value. |
954 |
PST Net Breakaway Time |
955 |
Measured when the valve has moved ½ % from the starting position |
956 |
PST Time To Target |
957 |
Set bit on to reset the pilot travel and pilot cycle counters |
958 |
Pilot Trav/Cyc Reset |
959 |
Reset Pilot Travel |
960 |
Reset Pilot Cycles |
961 |
Pilot Trav Full Warning |
962 |
Pilot valve travel high end limit. |
963 |
Pilot Trav Hi % Warning |
964 |
Pilot valve travel high percent Warning. |
965 |
Pilot Trav Initial Warning |
966 |
Pilot valve travel high start limit. |
967 |
The Piezo command 1 average. |
968 |
Piezo Cmd1 Avg |
969 |
Volts |
970 |
The Piezo command 2 average. |
971 |
Piezo Cmd2 Avg |
972 |
Piezo High Alarm |
973 |
Piezo High Warning |
974 |
Piezo Low Alarm |
975 |
Piezo Low Warning |
976 |
The Piezo voltage. |
977 |
Piezo volts |
978 |
The Piezo voltage 1 average. |
979 |
Piezo volt1 Avg |
980 |
The Piezo voltage 2 average. |
981 |
Piezo volt2 Avg |
982 |
The Piezo voltage high percent yellow. |
983 |
Pz High Pct Warning |
984 |
The Piezo voltage low percent Warning. |
985 |
Pz Low % Warning |
986 |
The gain position of the rotary switch user interface. |
987 |
Rotary Sw |
988 |
C |
989 |
D |
990 |
E |
991 |
F |
992 |
G |
993 |
H |
994 |
I |
995 |
J |
996 |
Sig Config |
997 |
Signature configuration |
998 |
Start Signature |
999 |
End Signature |
1000 |
Init Bi-directional Signature |
1001 |
Init Ramp Signature |
1002 |
Signature Started |
1003 |
Signals Last Data Frame |
1004 |
Init Pilot Relay Signature |
1005 |
Init PST |
1006 |
Signature Day |
1007 |
Pst Force at Breakaway |
1008 |
The Signature hold time. |
1009 |
Sig Hold Time |
1010 |
Signature time, hour parameter. |
1011 |
Signature time, minutes parameter. |
1012 |
Signature Month |
1013 |
Sig Num |
1014 |
Signature Number type |
1015 |
Step Baseline |
1016 |
Ramp Baseline 1 |
1017 |
Ramp Baseline 2 |
1018 |
PST Baseline |
1019 |
PST Current |
1020 |
Current 1 |
1021 |
Current 2 |
1022 |
The time it takes the signature to run the ramp. |
1023 |
Sig Ramp Time |
1024 |
Sig Result |
1025 |
Signature time, seconds parameter. |
1026 |
The Signature starting position. |
1027 |
Sig Start Pos |
1028 |
The Signature stopping position. |
1029 |
Sig StOP Pos |
1030 |
Sig Time Limit |
1031 |
Sig Time To Breakaway |
1032 |
Sig Time To Target |
1033 |
Signature Year. |
1034 |
Software Status Mask |
1035 |
Bit1=NVMEM CRC Error, Bit2=RAM Error, Bit3=RAM CRC Error, Bit4=Flash CRC Error, Bit5=Watch Dog Time Out, Bit6=Stack Overflow WRN, Bit7=CPU Usage WRN, Bit8=Firmware Update |
1036 |
Flash CRC Error |
1037 |
Stack Overflow WRN |
1038 |
CPU Usage WRN |
1039 |
Firmware Update |
1040 |
Software Status |
1041 |
The NVMEM CRC is incorrect. |
1042 |
The RAM location is bad. |
1043 |
The RAM data memory is corrupt. |
1044 |
The FLASH program memory is corrupt. |
1045 |
The flow monitor detected a problem. |
1046 |
The stack is about to overflow. |
1047 |
The CPU usage is too high. |
1048 |
The embedded code on the controller board has been upgraded. |
1049 |
The position high end softstop. |
1050 |
Soft Stop High |
1051 |
The position low end softstop. |
1052 |
Soft Stop Low |
1053 |
Displays if a pressure board is present or not |
1054 |
Press Board Status |
1055 |
Absent |
1056 |
Present |
1057 |
Displays if an LCD is present or not |
1058 |
LCD Avail Status |
1059 |
StartUp Status Mask |
1060 |
Bit1=Power On, Bit2=Initializing, Bit3=Stroke cal Req |
1061 |
Power On |
1062 |
Stroke Cal Req |
1063 |
StartUp Status |
1064 |
Main board has been powered on. |
1065 |
Main board is initializing. |
1066 |
A stroke calibration is required for proper positioning. |
1067 |
Mode Status 2 |
1068 |
Bit enumerated Bit1=CST Mode, Bit2=Training in Progress, Bit3=Training Complete, Bit4=Event Captured, Bit5=Local Interface Off, Bit6=Squawk Mode |
1069 |
Cal Status |
1070 |
Bit1=Stroke Cal In Prog, Bit2=Setting ILO, Bit5=Cmd In Cal In Prog, Bit7=Jog Cal set 100% |
1071 |
Stroke Cal In Prog |
1072 |
The positioner is currently performing a stroke calibration. |
1073 |
Setting ILO |
1074 |
The positioner is currently finding the inner control loop offset. |
1075 |
Cmd In Cal In Prog |
1076 |
A calibration of the command signal (analog input) is in progress. |
1077 |
Jog Cal Set 100% Pos |
1078 |
Waiting for the user to move the valve to the 100% position using the jog buttons. |
1079 |
Cal Error Status 1 |
1080 |
Bit1=Position Range Small, Bit2=Position < ADC Range, Bit3=Position > ADC RAnge, Bit4=No Motion Time Out, Bit5=Settle Time Out, Bit6=ILO Time Out |
1081 |
Position Range Small |
1082 |
Position < ADC Range |
1083 |
Position > ADC RAnge |
1084 |
ILO Time Out |
1085 |
Cal Error Status 2 |
1086 |
Bit1=AO Range Small, Bit2=Cmd In Range Small, Bit3=Cmd In < ADC Range, Bit4=Cmd In > ADC Range, Bit5=Stroke Shift, Bit6=Stroke Span Increase, Bit7=Stroke Span Decrease |
1087 |
Cmd In Range Small |
1088 |
Cmd In < ADC Range |
1089 |
Cmd In > ADC Range |
1090 |
spare |
1091 |
Control Status |
1092 |
Bit1=Cmd Frequency WRN, Bit2=Cmd Frequency ALM, Bit3=Cmd Amplitude WRN, Bit4=Cmd Amplitude ALM, Bit5=Psn Frequency WRN, Bit6=Psn Frequency ALM, Bit7=Psn Amplitude WRN, Bit8=Psn Amplitude ALM |
1093 |
Elec Board Status |
1094 |
Bit1=Card 1 Fail WRN, Bit2=Card 2 Fail WRN, Bit3=Card 1 No Loop Pwr, Bit4=Card 2 No Loop Pwr, Bit5=Card 1 Error, Bit6=Card 2 Error, Bit7=Press Board Fail WRN, Bit8=Low Battery WRN |
1095 |
Stroke/Fric Status |
1096 |
Bit1=Reversed Spring, Bit2=Insufficient Spring, Bit3=No Spring |
1097 |
Press Cal Status |
1098 |
Bit1=Port S Out of Range, Bit2=Port A Out of Range, Bit3=Port B Out of Range, Bit4=Port S Range Small, Bit5=Port A Range Small, Bit6=Port B Range Small, Bit7=Pressure Sensor Fail |
1099 |
Bit1=Stroke Cal In Prog, Bit2=Setting ILO, Bit3=Pressure Cal In Prog, Bit4=Friction Cal In Prog, Bit5=Cmd In Cal In Prog, Bit6=AO Cal In Prog, Bit7=Jog Cal set 100% |
1100 |
Initial Duration: |
1101 |
Strip chart initial duration. |
1102 |
60 sec. |
1103 |
Interval |
1104 |
Strip chart interval. |
1105 |
~ 2 sec. |
1106 |
Stroke Time Close |
1107 |
The time it takes to stroke the valve closed |
1108 |
Stroke Time Open |
1109 |
The time it takes to stroke the valve open |
1110 |
Current Temp |
1111 |
Current Temperature |
1112 |
Max Lifetime Temp |
1113 |
Maximum temperature reached for the life of the unit |
1114 |
Min Lifetime Temp |
1115 |
Minimum temperature reached for the life of the unit |
1116 |
Max PowerUp Temp |
1117 |
Maximum temperature reached since last power up |
1118 |
Min PowerUp Temp |
1119 |
Minimum temperature reached since last power up |
1120 |
Max Reset Temp |
1121 |
Maximum temperature reached since last reset of the unit |
1122 |
Min Reset Temp |
1123 |
Minimum temperature reached since last reset of the unit |
1124 |
Tight Shutoff Hyst |
1125 |
Position Tight Shutoff Hysteresis. |
1126 |
Tight Shutoff Lower |
1127 |
Position Tight Shut Off Lower Limit |
1128 |
Tight Shutoff Upper |
1129 |
Position Tight Shut off Upper Limit |
1130 |
Area Units |
1131 |
Units for area measurements. |
1132 |
in² |
1133 |
cm² |
1134 |
Flow Units |
1135 |
Units for flow measurements. |
1136 |
Force Units |
1137 |
Units for force measurements. |
1138 |
Display the engineering units for pressure. |
1139 |
Press Units |
1140 |
Engineering units being used for ambient main board temperature measurement. |
1141 |
Temp Units |
1142 |
Travel Units |
1143 |
Units for travel measurements. |
1144 |
Select valve body material. |
1145 |
Valve Body Mat |
1146 |
Alloy 20 |
1147 |
Aluminum |
1148 |
Bronze |
1149 |
Carbon steel |
1150 |
Special Alloy |
1151 |
Hastelloy |
1152 |
Inconel |
1153 |
Monel 400 |
1154 |
Nickel |
1155 |
Titanium |
1156 |
Type 304 |
1157 |
Type 316 |
1158 |
Select valve body size in inches. |
1159 |
Valve Body Size |
1160 |
.25 INCH |
1161 |
.5 INCH |
1162 |
.75 INCH |
1163 |
1.0 INCH |
1164 |
1.25 INCH |
1165 |
1.5 INCH |
1166 |
2.0 INCH |
1167 |
2.5 INCH |
1168 |
3.0 INCH |
1169 |
4.0 INCH |
1170 |
5.0 INCH |
1171 |
6.0 INCH |
1172 |
8.0 INCH |
1173 |
10.0 INCH |
1174 |
12.0 INCH |
1175 |
14.0 INCH |
1176 |
16.0 INCH |
1177 |
18.0 INCH |
1178 |
20.0 INCH |
1179 |
24.0 INCH |
1180 |
28.0 INCH |
1181 |
32.0 INCH |
1182 |
36.0 INCH |
1183 |
40.0 INCH |
1184 |
Select valve bonnet type. |
1185 |
Valve Bonnet Type |
1186 |
Extended |
1187 |
Bellows Seal |
1188 |
Low Temperature |
1189 |
Valve Cycles |
1190 |
Valve Cycles. |
1191 |
Valve Cycle Rate |
1192 |
Valve Cycles center rate monitor. |
1193 |
Pressure rating for the outlet of the valve. |
1194 |
Outlet Press |
1195 |
Select valve end connections. |
1196 |
Valve End Conn |
1197 |
Sep. Flange |
1198 |
Integral Flange |
1199 |
Weld end |
1200 |
flangeless / Water |
1201 |
Clamped |
1202 |
Screwed |
1203 |
FailDirection |
1204 |
Direction valve will go in a failed state |
1205 |
Fail Closed |
1206 |
Fail Open |
1207 |
Fail In Place |
1208 |
OTHER |
1209 |
FlowDirection |
1210 |
Direction of the flow |
1211 |
Flow Over |
1212 |
Flow Under |
1213 |
Select valve manufacturer. |
1214 |
Valve Manuf. |
1215 |
Valtek |
1216 |
Select valve model type. |
1217 |
Valve Model |
1218 |
Mark One |
1219 |
Mark One-X |
1220 |
Mark 100 |
1221 |
Mark Two |
1222 |
Mark Six |
1223 |
Mark Eight |
1224 |
Mark Ten (survivor) |
1225 |
ShearStream SB |
1226 |
ShearStream HP |
1227 |
MaxFlo 3 |
1228 |
Valdisk BX |
1229 |
FlowTop |
1230 |
FlowPak |
1231 |
FlowPro |
1232 |
VariCool |
1233 |
HpFlow |
1234 |
LinedFlow |
1235 |
TotalFlow |
1236 |
ColdFlow |
1237 |
DrainFlow |
1238 |
SmallFlow |
1239 |
CleanFlow |
1240 |
Multi-Z |
1241 |
020000 |
1242 |
025000 |
1243 |
030000 |
1244 |
185000 |
1245 |
Setball |
1246 |
Duball |
1247 |
Trunnball |
1248 |
torex |
1249 |
Unex |
1250 |
GSV |
1251 |
MaxFlo 4 |
1252 |
Durco |
1253 |
Worcester |
1254 |
Atomac |
1255 |
McCANNA |
1256 |
Nobel Alloy |
1257 |
Valbart |
1258 |
Argus |
1259 |
Mark 200 |
1260 |
Select valve packing type. |
1261 |
Valve Pack Type |
1262 |
Single Packing PTFE |
1263 |
Single Packing Graphite |
1264 |
Double Packing PTFE |
1265 |
Double Packing Graphite |
1266 |
Spring Loaded |
1267 |
valve pressure balance. |
1268 |
Valve Press Bal |
1269 |
Unbalanced |
1270 |
Balanced |
1271 |
Select valve body ANSI Pressure Rating (class). |
1272 |
Press Class |
1273 |
CL 150 |
1274 |
CL 300 |
1275 |
CL 600 |
1276 |
CL 900 |
1277 |
CL 1500 |
1278 |
CL 2500 |
1279 |
CL 4500 |
1280 |
PN 10 |
1281 |
PN 16 |
1282 |
PN 25 |
1283 |
PN 40 |
1284 |
PN 63 |
1285 |
PN 100 |
1286 |
PN 160 |
1287 |
PN 250 |
1288 |
PN 400 |
1289 |
PN 4000 |
1290 |
Travel for which this unit is rated. |
1291 |
Rated Travel |
1292 |
Select ANSI shutoff leakage class. |
1293 |
Leak Class |
1294 |
Class I |
1295 |
Class II |
1296 |
Class III |
1297 |
Class IV |
1298 |
Class V |
1299 |
Class VI |
1300 |
~2% Rate |
1301 |
Valve serial number in the format, xxxxxx.xxx. Contains sales order number plus the page. |
1302 |
Valve Ser.# |
1303 |
Stem/shaft diameter in inches. |
1304 |
Stem Dia. |
1305 |
Stroke Length |
1306 |
Stroke length in percent. |
1307 |
Valve Travel |
1308 |
Valve travel. |
1309 |
Valve Travel Rate |
1310 |
Valve travel center rate monitor. |
1311 |
Select valve trim characteristics. (Informational use only) |
1312 |
Valve Character. |
1313 |
Equal % |
1314 |
Quick Open |
1315 |
bi-linear |
1316 |
Select Valve Trim Diameter. |
1317 |
Valve Trim Size |
1318 |
0.10 - 0.12 in (2.5 - 3.0 mm) |
1319 |
0.13 - 0.15 in (3.1 - 3.8 mm) |
1320 |
0.16 - 0.19 in (3.9 - 4.8 mm) |
1321 |
0.20 - 0.24 in (4.9 - 6.1 mm) |
1322 |
0.25 - 0.30 in (6.2 - 7.6 mm) |
1323 |
0.31 - 0.37 in (7.7 - 9.4 mm) |
1324 |
0.38 - 0.45 in (9.5 - 11.4 mm) |
1325 |
0.46 - 0.55 in (11.5 - 14.0 mm) |
1326 |
0.56 - 0.67 in (14.1 - 17.0 mm) |
1327 |
0.68 - 0.81 in (17.1 - 20.6 mm) |
1328 |
0.82 - 0.98 in (20.7 - 24.9 mm) |
1329 |
0.99 - 1.18 in (25.0 - 30.0 mm) |
1330 |
1.19 - 1.42 in (30.1 - 36.1 mm) |
1331 |
1.43 - 1.7 in (36.2 - 43 mm) |
1332 |
1.8 - 2.1 in (44 - 54 mm) |
1333 |
2.2 - 2.7 in (55 - 68 mm) |
1334 |
2.8 - 3.3 in (69 - 84 mm) |
1335 |
3.4 - 4.1 in (85 - 103 mm) |
1336 |
4.2 - 4.9 in (104 - 125 mm) |
1337 |
5.0 - 6.0 in (126 - 152 mm) |
1338 |
6.1 - 7.3 in (153 - 184 mm) |
1339 |
7.4 - 8.8 in (185 - 223 mm) |
1340 |
8.9 - 10.5 in (224 - 268 mm) |
1341 |
10.6 - 12.7 in (269 - 322 mm) |
1342 |
12.8 - 15.2 in (323 - 386 mm) |
1343 |
15.3 - 18.2 in (387 - 462 mm) |
1344 |
18.3 - 21.8 in (463 - 552 mm) |
1345 |
Select valve trim material. |
1346 |
Valve Trim Mat |
1347 |
Stainless Steel |
1348 |
Stainless Steel (hardened) |
1349 |
Alloy 6 |
1350 |
Soft Seated |
1351 |
Special Alloys |
1352 |
Select valve trim (standard, CavControl, MegaStream, etc.) |
1353 |
Trim Type |
1354 |
CavControl |
1355 |
ChannelStream |
1356 |
MegaStream |
1357 |
Tiger-Tooth |
1358 |
Stealth |
1359 |
MicroCav |
1360 |
CavStream |
1361 |
MultiStream |
1362 |
SilentPack |
1363 |
Kammer Type I-III |
1364 |
Z-Trim |
1365 |
Multi-Stage |
1366 |
V-Port |
1367 |
CPT |
1368 |
Ultra Low Flow |
1369 |
Reduced Port |
1370 |
Full Port |
1371 |
Valve Type |
1372 |
Select the type of valve |
1373 |
Rotary |
1374 |
Pressure rating for the inlet of the valve. |
1375 |
Valve Inlet Press |
1376 |
Vlv Cyc Dead Band |
1377 |
Valve Cycle dead band. |
1378 |
Vlv Cyc Full Warning |
1379 |
Valve Cycles high end limit. |
1380 |
Vlv Cyc Hi % Warning |
1381 |
Valve Cycles high percent Warning. |
1382 |
Vlv Cyc Initial Warning |
1383 |
Valve Cycles high start limit. |
1384 |
StrokeLength |
1385 |
Valve stroke Length. |
1386 |
Status bits |
1387 |
Valve Trav/Cyc Reset |
1388 |
Reset Valve Travel |
1389 |
Reset Valve Cycles |
1390 |
Vlv Trav Full Warning |
1391 |
Valve travel high end limit. |
1392 |
Vlv Trav Hi % Warning |
1393 |
Vlv Trav Initial Warning |
1394 |
Valve travel high start limit. |
1395 |
Vlv Trav Dead Band |
1396 |
Valve travel dead band. |
1397 |
Too Few Data Bytes |
1398 |
Device is Busy |
1399 |
Command not implemented |
1400 |
Events |
1401 |
Last 32 events |
1402 |
State |
1403 |
Indication |
1404 |
Cal Cmd In |
1405 |
This method allows the user to Calibrate the command input A/D. |
1406 |
Calibrate |
1407 |
Calibrates the travel of the valve position (zero and span), and if auto tuning is enabled the gain values for the positioner are also calculated. |
1408 |
View/Set Date/Time |
1409 |
View and set the positioner date and time. |
1410 |
Acquire Event History |
1411 |
Execute this method to acquire the events. View the complete list of events (alarms, calibrations etc.). The latest event is shown first. |
1412 |
Reset Factory Defaults |
1413 |
This method allows the user to initiate a factory reset. This will reset all of the devices parameters back to factory defaults. |
1414 |
method4 |
1415 |
method6 |
1416 |
Full Initial Setup |
1417 |
This method directs the user through the initial steps to setup the positioner when it is fresh from the factory or has has a factory reset performed. |
1418 |
Run PST |
1419 |
This method allows the user to initiate a partial stroke test. |
1420 |
Select Actuator Info |
1421 |
Allows you to select your actuator manufacturer, model/size. |
1422 |
Flowserve Logo |
1423 |
Picture Lgx 420 |
1424 |
TEMP |
1425 |
High Alarm |
1426 |
High Warning |
1427 |
Current Value |
1428 |
Low Alarm |
1429 |
Low Warning |
1430 |
Warning |
1431 |
Alarm |
1432 |
Maximum |
1433 |
Current |
1434 |
Minimum |
1435 |
Low |
1436 |
High |
1437 |
Cmd Pos Dev |
1438 |
CMD |
1439 |
POS |
1440 |
DEV |
1441 |
Travel |
1442 |
Data Chart |
1443 |
Real time data logger. |
1444 |
Piezo Volts Chart |
1445 |
View piezo volts and settings graphically. |
1446 |
Pilot Response Chart |
1447 |
View pilot relay response and settings graphically. |
1448 |
Pilot Cycles Chart |
1449 |
View pilot cycles and settings graphically. |
1450 |
Pilot Travel Chart |
1451 |
View pilot travel and settings graphically. |
1452 |
Position Alert Chart |
1453 |
View position and alert settings graphically. |
1454 |
Position Deviation Chart |
1455 |
View position deviation and settings graphically. |
1456 |
Cmd. Pos. Dev. |
1457 |
View command, position, deviation, and temperature graphically. |
1458 |
Valve Tracking |
1459 |
Valve Cycle Chart |
1460 |
View current cycle count and settings graphically. |
1461 |
Valve Travel Chart |
1462 |
View current travel and settings graphically. |
1463 |
Actuation error status indicators and mask settings. |
1464 |
Actuator Health |
1465 |
View health indicator of the actuator. |
1466 |
Actuator Information |
1467 |
Allows view and edit access to the actuator information parameters. |
1468 |
Alarm Annunciators |
1469 |
View and manage alerts and alarms. |
1470 |
Annunciators |
1471 |
View current warnings, alarms, and events. |
1472 |
Burst Configuration |
1473 |
Activate burst mode and change settings. |
1474 |
Calibration |
1475 |
Allows access to the calibration functions and variables of the device. |
1476 |
View the status of indicators related to calibrations. |
1477 |
Command Info |
1478 |
Command, feedback, and temperature data. |
1479 |
Command Data |
1480 |
Allows user to view the health data of the device. |
1481 |
Configuration |
1482 |
Allows access to the configuration of the device for both viewing and editing. |
1483 |
Control Config |
1484 |
Allows access to the control configuration variables of the device for both viewing and editing. |
1485 |
Control Health |
1486 |
View and set health settings for the positioner control. |
1487 |
View the modes or behavior configurations of the positioner. |
1488 |
Cycle/Travel Status |
1489 |
Cycle and travel status indicators and mask settings. |
1490 |
Dashboard |
1491 |
Display positioner status |
1492 |
Data Monitor (GUI only) |
1493 |
View a data strip chart. |
1494 |
Device Config |
1495 |
Allows use to view and set up the dip switches and aux cards of the device. |
1496 |
Device Information |
1497 |
Allows view and edit access to the device information parameters. |
1498 |
Device Menu |
1499 |
Device menu. |
1500 |
Diagnostic Menu |
1501 |
Top level menu. |
1502 |
Dip Switch |
1503 |
Dip switch settings. |
1504 |
Electronic Detail Status |
1505 |
Electronic detail error status indicators and mask settings. |
1506 |
Electronic Config Status |
1507 |
Presence of LCD board indicator. |
1508 |
View Event Grid (GUI only) |
1509 |
Acquire and view last 32 events. |
1510 |
Feedback Status |
1511 |
Position feedback status indicators and mask settings. |
1512 |
Valve Stability |
1513 |
Valve stability indicators and mask settings. |
1514 |
Health |
1515 |
View the overall health status. |
1516 |
Hot Key Menu |
1517 |
Hour Meters |
1518 |
View the hour meters. |
1519 |
Inner loop status indicators and mask settings. |
1520 |
Local Interface |
1521 |
Lock the local interface of the positioner and set a pin code. Locking the local interface prevents unauthorized changes from taking place at the positioner's button panel that affect the control or configuration of the positioner. |
1522 |
Maintenance Menu |
1523 |
Maintenance options |
1524 |
Main Board Detail |
1525 |
Main board detail status and mask settings. |
1526 |
Main board status indicators and mask settings. |
1527 |
Management Annunciators |
1528 |
Management Annunciators contain settings with ranges. |
1529 |
Mode Status |
1530 |
Operational mode indicators and mask settings. |
1531 |
Offline Diagnostics |
1532 |
Configure and perform the partial stroke test and view the results. |
1533 |
Offline Menu |
1534 |
Offline menu. |
1535 |
Online Diagnostics |
1536 |
View data logger. |
1537 |
Partial Stroke Test |
1538 |
Run a partial stroke tests and view results. |
1539 |
Piezo Voltage |
1540 |
Displays the Piezo voltages. |
1541 |
Pilot Relay |
1542 |
View and set the Pilot Relay Response warning limits. The pilot relay response is a measure of how rapidly the pilot relay is following the pilot relay command. Longer times indicate slower response. |
1543 |
Pilot Travel/Cycles |
1544 |
Allows use to view travel and cycles of the pilot valve and edit the alarm end points of the device. |
1545 |
Position Alert Settings |
1546 |
View and configure position alert settings. |
1547 |
Allows view and edit of the position alert parameters. |
1548 |
Positioner Health |
1549 |
View and set health settings for the positioner. |
1550 |
Positioner Information |
1551 |
Allows view and edit access to the tuning parameters. |
1552 |
Positioner Tuning |
1553 |
Position alert indicators and mask settings. |
1554 |
PV Menu |
1555 |
PV menu. |
1556 |
Revs and SNs |
1557 |
View inforamtion about the system revisions and serial numbers. |
1558 |
LOGIX 420 Main menu selection |
1559 |
Main Menu |
1560 |
Software Detail Status |
1561 |
Software detail error status and mask settings. |
1562 |
Soft Limits and Shutoff |
1563 |
Allows view and edit of the soft limits and tight shutoff parameters. |
1564 |
Startup |
1565 |
Initialization status indicators and mask settings. |
1566 |
Diagnostic Values |
1567 |
Allows user to view the diagnostic parameters of the device. |
1568 |
Tech Annunciators |
1569 |
View the status of low-level indicators. |
1570 |
Temperature History |
1571 |
View the temperature history. |
1572 |
Command 3 |
1573 |
Select primary, secondary, tertiary, and fourth variables. |
1574 |
Select Units |
1575 |
Allows view and edit access to the unit parameters. |
1576 |
User Preferences |
1577 |
Allows view and edit access to user definable parameters. |
1578 |
Valve Body Info |
1579 |
Allows view and edit access to the valve trim and body parameters. |
1580 |
Valve Health |
1581 |
View the health of valve cycles and travel. |
1582 |
Valve Trim Info |
1583 |
Secondary Analog Channel Saturated |
1584 |
Tertiary Analog Channel Saturated |
1585 |
Quaternary Analog Channel Saturated |
1586 |
Quinary Analog Channel Saturated |
1587 |
Secondary Analog Channel Fixed |
1588 |
Tertiary Analog Channel Fixed |
1589 |
Quaternary Analog Channel Fixed |
1590 |
Quinary Analog Channel Fixed |
1591 |
PV Analog Channel Saturated |
1592 |
PV Analog Channel Fixed |
1593 |
Enable on token-passing data link layer only |
1594 |
Enable on TDMA data link layer only |
1595 |
Enable on both TDMA and token-passing data link layer |
1596 |
Wireless |
1597 |
WirelessHART Device |
1598 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
1599 |
Primary |
1600 |
Primary Analog Channel |
1601 |
Secondary |
1602 |
Secondary Analog Channel |
1603 |
Tertiary |
1604 |
Tertiary Analog Channel |
1605 |
Quaternary |
1606 |
Quaternary Analog Channel |
1607 |
Quinary |
1608 |
Quinary Analog Channel |
1609 |
Critical Power Failure |
1610 |
Lock all |
1611 |
Trim not supported |
1612 |
Configuration cannot be changed |
1613 |
Locked by gateway |
1614 |
Analog Input Channel |
1615 |
Analog Output Channel |
1616 |
Wired HART Enabled |
1617 |
Enabled on Wired HART device connection only |
1618 |
Wireless HART Enabled |
1619 |
Enabled on WirelessHART device connection only |
1620 |
Both Wired and WirelessHart Enabled |
1621 |
Enabled on both Wired and WirelessHART connections |
1622 |
8u |
1623 |
8.3f |
1624 |
.3f |
1625 |
Burst Command |
1626 |
** WARNING ** This may affect the accuracy of the positioner. Continue? |
1627 |
Yes;No |
1628 |
Enter your initials. (up to 3 letters) |
1629 |
Set the Command Input to 0% position then select Enter.. |
1630 |
Set the Command Input to 100% position then select Enter.. |
1631 |
Calibration complete |
1632 |
Calibration not performed |
1633 |
Do you wish to run Calibration? ** WARNING ** This proceedure will cause the valve to move. |
1634 |
Please Wait,
Stroke Cal in Progress... |
1635 |
Please Wait,
Setting ILO in Progress... |
1636 |
Please Wait,
Pressure Cal in Progress... |
1637 |
Please Wait,
Stroke/Pressure Cal in Progress... |
1638 |
Please Wait,
Friction Cal in Progress... |
1639 |
Calibration Complete |
1640 |
Do you wish to change the date/time?
The current date and time is:
%{CurrentDay} %{CurrentMonth} 20%{CurrentYear} %{CurrentHour}:%{CurrentMinutes}:%{CurrentSeconds}
|
1641 |
Select the Day |
1642 |
1;2;3;4;5;6;7;8;9;10;11;12;13;14;15;16;17;18;19;20;21;22;23;24;25;26;27;28;29;30;31 |
1643 |
Select the Month |
1644 |
January;February;March;April;May;June;July;August;September;October;November;December |
1645 |
Select the Year |
1646 |
2011;2012;2013;2014;2015;2016;2017;2018;2019;2020;2021;2022;2023;2024;2025;2026;2027;2028;2029;2030;Other |
1647 |
Enter value for Year |
1648 |
NewYear |
1649 |
Value entered is out of range, must be between 2000 and 2099. Reenter |
1650 |
Enter the Hour (24 Hour Clock) |
1651 |
NewHour |
1652 |
Value entered is out of range, must be between 0 and 23. Reenter |
1653 |
Enter the Minutes (0 - 59) |
1654 |
NewMin |
1655 |
Value entered is out of range, must be between 0 and 59. Reenter |
1656 |
The current date and time is:
%{CurrentDay} %{CurrentMonth} 20%{CurrentYear} %{CurrentHour}:%{CurrentMinutes}:%{CurrentSeconds} |
1657 |
Acquiring Events... |
1658 |
Temp2 |
1659 |
, |
1660 |
|
1661 |
: |
1662 |
at |
1663 |
** WARNING ** Do you wish to continue? This proceedure will cause a loss of all user control and calibration parameters. The user will have to reconfigure the device. |
1664 |
No;Yes |
1665 |
Device has been reset. Device must now be reconfigured. |
1666 |
Reset was not performed. |
1667 |
** WARNING ** This proceedure will cause the valve to move. Do you wish to continue? |
1668 |
Select PST Type |
1669 |
Baseline;Non Baseline |
1670 |
Enter PST Start Position. |
1671 |
LocStartPos |
1672 |
Start Position out of range (0-100). Reenter |
1673 |
Enter PST End Position. |
1674 |
LocEndPos |
1675 |
End Position out of range (0-100). Reenter |
1676 |
Enter the Hold Time in seconds. |
1677 |
LocHoldTime |
1678 |
Enter the Ramp Time in seconds. |
1679 |
LocRampTime |
1680 |
Enter the PST Time Limit in seconds. |
1681 |
LocTimeLimit |
1682 |
PST in progress. Please Wait |
1683 |
PST not performed |
1684 |
Actuator manufacturer - |
1685 |
Valtek (Piston);Kammer;Valtek (Diaphragm Rotary);Automax;NAF;Valtek (Diaphragm Linear);Fisher;Other |
1686 |
Actuator size - |
1687 |
25;50;100;100C;150C;200;200C;300;400;500;600;Other |
1688 |
37;38;39;3D;47;48;49;4D;P0;P1;P2;P3;P4;P5;P6;P7;Other |
1689 |
NR1;NR2;NR3;Other |
1690 |
B050D;B063D;B085D;B100D;B115D;B125D;B150D;B175D;B200D;SNA250;SNA300;R205;R206;R207;R208;R310;R312;R314;R316;R414;R416;R418;R420;R422;R514;R516;R518;R520;R522;R524;Other |
1691 |
-02;-11;-12;-21;-22;-31;-32;-41;-42;-51;-52;Other |
1692 |
127;252;502;700;1502;3002;Other |
1693 |
657-30;657-34;657-40;657-45;657-46;657-50;657-60;657-70;657-80;657-87;657-100;667-30;667-34;667-40;667-45;667-46;667-50;667-60;667-70;667-80;667-87;667-100;Other |
1694 |
Enter value for Actuator Area |
1695 |
ActArea |
1696 |
Value entered is not reasonable, must be between 0 and 1000. Reenter |