0 |
X3302 |
1 |
DET-TRONICS |
2 |
Operating Mode |
3 |
Maintenance Required |
4 |
Device Variable Alert |
5 |
Operating Mode 2 |
6 |
Apply clean air |
7 |
Stabilizing zero |
8 |
Apply cal gas |
9 |
Stabilizing span |
10 |
Remove cal gas |
11 |
Xmtr Addstatus 0 |
12 |
Field Device Specific Status Byte 1- Data that has Field Device status information relating to: failures / warnings / status of processes. |
13 |
Fire Alarm |
14 |
Indicates (Y) if the device is in a fire alarm status. - analog output is at 20mA, fire alarm relay is actuated and LED is red. |
15 |
Oi Cal Active |
16 |
Optical Integrity (Oi) Calibration is in progress. During caibration the detector should be cleaned and covered. Flame detection is disabled until calibration is complete. |
17 |
Manual Oi Active |
18 |
A manual Optical Integrity (Oi) test is in progress. During caibration the detector should be cleaned and covered. Flame detection is disabled until calibration is complete. |
19 |
Warm-Up |
20 |
Device is in the power-up time delay (warm-up) mode. Normal duration 30 seconds. |
21 |
Not Used |
22 |
Not Used, bit 4 |
23 |
Not Used, bit 5 |
24 |
Not Used, bit 6 |
25 |
Not Used, bit 7 |
26 |
Xmtr Addstatus 1 |
27 |
Field Device Specific Status Byte 2- Data that has Field Device status information relating to: failures / warnings / status of processes. |
28 |
Not Used, bit 0 |
29 |
Not Used, bit 1 |
30 |
Not Used, bit 2 |
31 |
Not Used, bit 3 |
32 |
Xmtr Addstatus 2 |
33 |
Field Device Specific Status Byte 3- Data that has Field Device status information relating to: failures / warnings / status of processes. |
34 |
Fault |
35 |
Indicates (Y) if a fault condition exists.Go to (Device Info) and select (Status Info) to determine the nature of the fault. |
36 |
Automatic Oi Fault |
37 |
Automatic Oi Fault. Check viewing windows and Oi reflector plate for cleanliness. |
38 |
Manual Oi Fault |
39 |
The detector has failed the last manual Oi test. |
40 |
Oi Cal Fault |
41 |
An Oi calibration fault has occured. |
42 |
Diminished Detect Fault |
43 |
Diminished Detection Fault. Excessive background IR radiation.Eliminate IR interference and/or re-aim/orient detector. |
44 |
Detection Disable Fault |
45 |
Flame detector function has been disabled! Check viewing windows for cleanliness and/or presence of excessive background IR signal. If uncorrectable replace sensor. |
46 |
Temp Out of Range |
47 |
Detector integral temperature out of range-Operating range: -40F to +167F (-40C to +75C). |
48 |
Voltage Out of Range |
49 |
Supply voltage is out of range. Specified operating voltage is 18 to 30 Vdc. |
50 |
Xmtr Addstatus 3 |
51 |
Field Device Specific Status Byte 4- Data that has Field Device status information relating to: failures / warnings / status of processes. |
52 |
Sensor Hdwr. Flt |
53 |
Sensor hardware fault.
-If fault clears 3 minutes after powerup check man oi test line not connected to DC- -Verify supply volt is within Operating range (18 to 30 Vdc) If fault does not clear, replace sensor module. |
54 |
HIB Hardware Fault |
55 |
HART interface board (HIB) hardware fault. If fault persists replace HIB. |
56 |
Internal Com. Flt |
57 |
Internal communication fault. If fault persists replace HART interface board and/or sensor module. |
58 |
Incompatible Firmware Fault |
59 |
Sensor module firmware version is not compatible with HART interface board. Replace the sensor module. |
60 |
.5f |
61 |
None |
62 |
No units defined. |
63 |
.3f |
64 |
.2f |
65 |
8.2f |
66 |
The user is encouraged to keep track of the last calibration date here. This date is for information only and is not used in any internal calculations. |
67 |
CalDate |
68 |
7d |
69 |
Event log request |
70 |
new event |
71 |
previous event |
72 |
next event |
73 |
exit |
74 |
Set Password |
75 |
The password is used to validate the command to enable or disable writes in the device. |
76 |
Set Write Protect |
77 |
Used to set the write protect mode. With Write Protect (On), variables cannot be written to the device and commands that cause actions to be performed in the device cannot occur. |
78 |
Change Password |
79 |
Sensor Unit |
80 |
Minimum Span |
81 |
AO Alarm type |
82 |
% Range |
83 |
Xfer Function |
84 |
Range Unit |
85 |
PV Snsr S/N |
86 |
Conc |
87 |
Self Test |
88 |
Self test will perform all internal checks immediately and return results in variables xmtr flt 1 & xmtr flt 2. |
89 |
Condensed Status |
90 |
Write Protect |
91 |
Abort response test |
92 |
return to normal |
93 |
Fire |
94 |
No |
95 |
Yes |
96 |
Oi Calibrate Active |
97 |
Oi Calibration is active. |
98 |
Manual Oi is active. |
99 |
Warm Up |
100 |
Fault |
101 |
Automatic Oi Fault |
102 |
Oi Calibrate Fault |
103 |
Diminish. Detect. Flt |
104 |
Detect. Disable Flt |
105 |
Temp Range Fault |
106 |
Voltage Fault |
107 |
Sensor Hdwr. Fault |
108 |
HIB Hardware Fault |
109 |
HART Interface Board hardware fault. If fault persists replace HIB. DEC PN 007308-005 |
110 |
Internal communication fault. If fault persists replace HART interface board and/or sensor module. |
111 |
Incompatible Fault |
112 |
RTC Seconds |
113 |
RTC seconds values 0-59. |
114 |
.2d |
115 |
RTC Minutes |
116 |
RTC minutes values 0-59. |
117 |
RTC Hours |
118 |
RTC hours values 0-23. |
119 |
RTC Date |
120 |
RTC date values 1-31. |
121 |
RTC Month |
122 |
RTC month values 1-12. |
123 |
RTC Year |
124 |
RTC year values 0-99. |
125 |
Log Temperature |
126 |
Log Code |
127 |
- |
128 |
Normal |
129 |
Warmup |
130 |
Soft Reset |
131 |
Hardware Reset |
132 |
Fire Alrm |
133 |
Man Oi Pass |
134 |
Man Oi Fault |
135 |
Auto Oi Fault |
136 |
Oi Cal Pass |
137 |
Oi Cal Fault |
138 |
Loop Test |
139 |
4-20 Cal |
140 |
Clk Reset |
141 |
Password Rst |
142 |
Hardware Fault |
143 |
Det Dsabl Fault |
144 |
Dimimished Detect |
145 |
Volt Fault |
146 |
Temp Fault |
147 |
Clr Evnt Log |
148 |
HART Hardware Fault |
149 |
MB Comm Fault |
150 |
Incompat Fault |
151 |
Fire Relay L/NL |
152 |
Fire relay, latching(L) or non-latching(NL). |
153 |
L |
154 |
NL |
155 |
Fire Relay NE/NDE |
156 |
Fire relay, normally energized(NE) or normally de-energized(NDE). |
157 |
NDE |
158 |
NE |
159 |
Fault Relay L/NL |
160 |
Fault relay, latching(L) or non-latching(NL). |
161 |
Fault Relay NE/NDE |
162 |
Fault relay, normally energized(NE) or normally de-energized(NDE). |
163 |
Aux Relay L/NL |
164 |
AUX relay, latching(L) or non-latching(NL). |
165 |
Aux Relay NE/NDE |
166 |
AUX relay, normally energized(NE) or normally de-energized(NDE). |
167 |
Sensitivity |
168 |
Detector sensitivity setting: Very high, High, Medium, or Low. |
169 |
Very High |
170 |
High |
171 |
Medium |
172 |
Low |
173 |
Consecutive Oi Fails |
174 |
Allowable number of consecutive Oi failures to produce a fault. Factory set to 3 (minutes). This is the time between fault occurrence and annunciation. |
175 |
Temp Setpoint |
176 |
Temperature at which heater begins operating. (-55C to+75C) |
177 |
Heater Power |
178 |
Actual heater power (0-100%). Heater prevents condensation and icing on the detector optics. |
179 |
Heater Setpoint |
180 |
Maximum amount of heater power allowed (in percent of full power, 0-100). |
181 |
Response Time |
182 |
Fire alarm processing time in seconds. |
183 |
Error |
184 |
3 Sec |
185 |
Oi Fail Count |
186 |
Number of consecutive Oi failures counted (one passed Oi test resets the counter). |
187 |
Left Oi |
188 |
Percent of calibrated Oi test signal returned by the left sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. |
189 |
Middle Oi |
190 |
Percent of calibrated Oi test signal returned by the middle sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. |
191 |
Right Oi |
192 |
Percent of calibrated Oi test signal returned by the right sensor. Reading should be 90 to 110 percent. If reading is below 90 percent, first try clean the window if the reading is still below 90 go to (Device Setup), select (Calibration) and perform Oi Calibration. If over 110% recalibrate. |
193 |
Voltage |
194 |
Actual detector supply voltage. Specified operating voltage is 18 to 30 Vdc. |
195 |
Temperature |
196 |
Actual integral temperature of detector. |
197 |
Part Number |
198 |
Manufacturer's part number for this device. |
199 |
.6d |
200 |
Dash Number |
201 |
Manufacturer's secondary part number for this device. |
202 |
.3d |
203 |
Manufacture Date |
204 |
Date of manufacture. Shown as month/day/year |
205 |
Sensor Firmware |
206 |
Firmware revision level of sensor module. |
207 |
HART Firmware |
208 |
Firmware revision level of HART interface board (HIB). |
209 |
Junk |
210 |
X3302 Root Menu |
211 |
Device Info Menu |
212 |
Command Menu |
213 |
Device Setup Menu |
214 |
Calibration Menu |
215 |
HART Command Menu |
216 |
General Info Menu |
217 |
Status Info Menu |
218 |
Oi Menu |
219 |
Hardware Menu |
220 |
Detector Settings |
221 |
Real Time Clock |
222 |
Configuration Menu |
223 |
HART PV Menu |
224 |
HART Info Menu |
225 |
HART Setup |
226 |
History Menu |
227 |
Write variables |
228 |
Calibrate Oi |
229 |
This procedure calibrates the Oi test signal for all three IR sensors. |
230 |
Start Passive Oi |
231 |
Test to check the cleanliness of the detector's optical surfaces and the ability to respond to an IR signal. Relays unaffected. |
232 |
Start Active Oi |
233 |
Test to check the cleanliness of the detector's optical surfaces and the ability to respond to an IR signal. Relays are affected. |
234 |
Clear Oi Fault |
235 |
Clear prior Oi faults. If the cause of the fault has not been corrected, subsequent Oi faults will occur. |
236 |
Reset Latches |
237 |
Latched relays are reset. LED turns green. |
238 |
Master Reset |
239 |
Initiates a hardware reset for both the sensor and the HART interface. Latched relays are reset. |
240 |
Clear Data Log |
241 |
Clears data log entries contained on the HART interface board. |
242 |
Alarm Log |
243 |
Scroll through 32 Alarm Logs with date, time, and temperature stamp. |
244 |
Fault Log |
245 |
Scroll through 32 Fault Logs with date, time, and temperature stamp. |
246 |
General Log |
247 |
Scroll through 32 General Logs with date, time, and temperature stamp. |
248 |
X3302 Abort Method. |
249 |
Part Number |
250 |
Current time and date setting of real time clock. Factory set to GMT minus 6 hours.
Date: month/day/year
Time: Hour:minute:second |
251 |
Serial Number |
252 |
Serial number of device. |
253 |
FMU860 |
254 |
DT |
255 |
DVC |
256 |
FCX |
257 |
AS800 |
258 |
340T |
259 |
340C |
260 |
344 |
261 |
Siemens Micro K |
262 |
SITRANS L |
263 |
SIPAN PH |
264 |
SITRANS P |
265 |
75SMT |
266 |
UNIDELTA |
267 |
8320 |
268 |
SX5100 |
269 |
TSV175 |
270 |
DMU |
271 |
3780 |
272 |
BM70 |
273 |
8u |
274 |
Oi calibration - Important! Clean and cover the detector before proceeding. |
275 |
Oi calibration. |
276 |
Cmd 130, Status Response Fault. |
277 |
Cmd 48, Status Response Fault. |
278 |
Checking status. |
279 |
Checking status... |
280 |
Uncover Detector Window. |
281 |
Success |
282 |
Passive Oi. |
283 |
Active Oi - Warning: This will cause an alarm indication. |
284 |
Clear Oi fault. |
285 |
Relay Latch reset. |
286 |
Hardware reset - Remove from loop. |
287 |
Clearing data logs... Are you sure? |
288 |
To Few Bytes Received. |
289 |
%{1}-%{2}-%{0} %{3}:%{4} %{6}C
%{7} |
290 |
Current;Previous;Next;Exit |
291 |
Warning: Current method abort. |
292 |
Part Number %{0}-%{1} |
293 |
Real Time Clock
Date: %{0}/%{1}/%{2}
Time: %{3}:%{4}:%{5} |
294 |
Device Serial Number: 000%{0} |