0 |
Upload Variables |
1 |
Primo Advanced |
2 |
Operation Unit |
3 |
Device |
4 |
Meas.Functions |
5 |
Direction |
6 |
Empty Pipe Detect. |
7 |
Measuring Limits |
8 |
Process Val. Scale |
9 |
Output |
10 |
Frequency Output |
11 |
ImpPulse Output |
12 |
Pulse width |
13 |
Flow Limits |
14 |
Preset |
15 |
Factors |
16 |
Giver Ampl. Const. |
17 |
Diameter |
18 |
Password |
19 |
Error Message |
20 |
Filter(Damping) |
21 |
Reset changed flag |
22 |
Flow Simulation |
23 |
Analog Calibration |
24 |
Empty Pipe Calibr. |
25 |
Preset Restart |
26 |
Reset Totalizer |
27 |
Delete Error list |
28 |
Set Pulse width |
29 |
Set Frequency |
30 |
Update configuration |
31 |
Update config. |
32 |
Add. Trans.Status |
33 |
Parameter OK |
34 |
Analog Out Saturated |
35 |
PV Out of Limits |
36 |
ERROR 1 and 2 |
37 |
Parameter to large |
38 |
Parameter to small |
39 |
Set to nearest |
40 |
invalid selection |
41 |
LRV too High |
42 |
LRV too Low |
43 |
URV too High |
44 |
URV too Low |
45 |
URV and LRV range out |
46 |
Span to small |
47 |
In Write Protected Mode |
48 |
Badger Meter |
49 |
Device Status |
50 |
abs. Flowrate |
51 |
5.0f |
52 |
4.1f |
53 |
2.3f |
54 |
Flow unit |
55 |
Current output |
56 |
rel. Flowrate |
57 |
Square |
58 |
|
59 |
max. Flowrate |
60 |
min. Flowrate |
61 |
7d |
62 |
Low Flow Cutoff |
63 |
The low flow is suppressing the indication resp. totalisation of 'wrong' liquid movements. The setting is posssible in the range of 0 - 10% referring to the full scale. |
64 |
Device is Busy |
65 |
Flow Direction |
66 |
At measurement in uni-directional direction flows will be indicated and added only in main flow direction. In bi-directional direction flow in both directions will be indicated and added. |
67 |
unidirectional |
68 |
bidirectional |
69 |
Detector Factor |
70 |
Calibration constant detected and adjusted at the factory. Changing this value influences the measuring accuracy of the meter! This value should correspond to the transmitter constant on the sensor nameplate. |
71 |
Pulse output |
72 |
The pulse value defines how many pulses per volume unit will be given. Max. output frequency 10 kHz. |
73 |
.3f |
74 |
Imp/Volume Unit |
75 |
Pulse width Unit |
76 |
The time unit of the pulse length is ms (1/1000 second) |
77 |
The pulse width defines the temporal length of a pulse. Max. 500 ms. |
78 |
Invalid units code |
79 |
Frequency Unit |
80 |
The unit of the frequency is in Hz. (Pulse/1 second) |
81 |
Frequency |
82 |
The frequency for the scaled terminal value can be adjusted from 500 to 5000 Hz. |
83 |
Flow Signal Low |
84 |
The set point is for monitoring the momentary flow and is adjusted in percent (0-100%) of the full scale. The underflowing of this set point is signalled via relay 2. |
85 |
Flow Signal High |
86 |
The set point is for monitoring the momentary flow and is adjusted in percent (0-100%) of the full scale. The exceeding of this set point is signalled via relay 2. |
87 |
Preset |
88 |
Realisation of simple batches. The value for the preset quantity can be adjusted from 0,01 to 999,99 volume units. The preset quantity is counted down from this value to 0 and the reaching of the preset quantity is signalled via relay 2. The preset meter can be resetted via an external probe or in the program menu. |
89 |
Restart Preset |
90 |
Resetting of the preset meter |
91 |
Pipediameter Unit |
92 |
Size in mm |
93 |
Pipediameter Value |
94 |
Size of the detector |
95 |
6 |
96 |
8 |
97 |
10 |
98 |
15 |
99 |
20 |
100 |
25 |
101 |
32 |
102 |
40 |
103 |
50 |
104 |
65 |
105 |
80 |
106 |
100 |
107 |
125 |
108 |
150 |
109 |
200 |
110 |
250 |
111 |
300 |
112 |
350 |
113 |
400 |
114 |
450 |
115 |
500 |
116 |
550 |
117 |
600 |
118 |
650 |
119 |
700 |
120 |
750 |
121 |
800 |
122 |
850 |
123 |
900 |
124 |
950 |
125 |
1000 |
126 |
1200 |
127 |
1350 |
128 |
1400 |
129 |
Tot+ reset |
130 |
Resetting the totaliser in main flow direction |
131 |
Tot- reset |
132 |
Resetting the totaliser reverse the main flow direction |
133 |
Tot Day reset |
134 |
Resetting the totaliser in main flow direction (daily counter) |
135 |
Tot All reset |
136 |
Resetting the totaliser in main flow direction (total counter) |
137 |
Tot+ |
138 |
Totaliser in main flow direction (total counter) |
139 |
Tot- |
140 |
Totaliser reverse the main flow direction |
141 |
Tot Day |
142 |
Totaliser in main flow direction (daily counter) |
143 |
Analog Out. Offset |
144 |
Calibration of the analog output (already done at the factory). Adjusting the offset at 4 mA. |
145 |
Analog Out. Gain |
146 |
Calibration of the analog output (already done at the factory). Adjusting the range at 20 mA. |
147 |
Empty-Pipe-Value |
148 |
Measuring signal at fulfilled pipe. |
149 |
Empty-Pipe-H. Unit |
150 |
Measuring signal unit in mV |
151 |
Empty-Pipe-Hyst. |
152 |
Adjusting the hysteresis value (recommended appr. 1000 mV) |
153 |
Volume Unit |
154 |
Adjusting the volume unit for totalisation and preset |
155 |
delete |
156 |
Resetting of error list |
157 |
Power on counter |
158 |
This value indicates the total switching ons of the meter |
159 |
Pulse Type |
160 |
Adjusting the pulse type. Closed (no pulse = low / pulse = high) as well as open (no pulse = high / pulse = low) |
161 |
closed |
162 |
open |
163 |
End Flow Simulation |
164 |
Flow simulation of all outputs with the adjusted parameters |
165 |
Start Flow Simulation |
166 |
Start flow simulation |
167 |
Simulate Flow +100% |
168 |
100% of the full scale in main flow direction as well as relay 1 (forward) |
169 |
Simulate Flow +50% |
170 |
50% of full scale in main flow direction as well as relay 1 (forward) + relay 2 |
171 |
Simulate Flow 0% |
172 |
0% of full scale in main flow direction as well as relay 1 (forward) + relay 3 |
173 |
Simulate Flow -50% |
174 |
50% of the full scale reverse the main flow direction as well as relay 1 (backward) + relay 2 |
175 |
Simulate Flow -100% |
176 |
100% of the full scale reverse the main flow direction as well as relay 1 (backward) |
177 |
Password is only valid in connection with the keypad at the meter. Value between 0 and 999. |
178 |
Empty Pipe Detect. |
179 |
off |
180 |
on |
181 |
Error Code Index 1 |
182 |
Error index 1 |
183 |
Error detector |
184 |
Error Slave Ack |
185 |
Error wrong int |
186 |
Error wrong ver |
187 |
Error empty |
188 |
Error overflow |
189 |
Error gain |
190 |
Error slave msg |
191 |
Last error code |
192 |
Num. of Err In 1 |
193 |
Number of error index 1 |
194 |
Error Code Index 2 |
195 |
Error index 2 |
196 |
Num. of Err In 2 |
197 |
Number of error index 2 |
198 |
Error Code Index 3 |
199 |
Error index 3 |
200 |
Num. of Err In 3 |
201 |
Number of error index 3 |
202 |
Error Code Index 4 |
203 |
Error index 4 |
204 |
Num. of Err In 4 |
205 |
Number of error index 4 |
206 |
Error Code Index 5 |
207 |
Error index 5 |
208 |
Num. of Err In 5 |
209 |
Number of error index 5 |
210 |
Error Code Index 6 |
211 |
Error index 6 |
212 |
Num. of Err In 6 |
213 |
Number of error index 6 |
214 |
Error Code Index 7 |
215 |
Error index 7 |
216 |
Num. of Err In 7 |
217 |
Number of error index 7 |
218 |
Error Code Index 0 |
219 |
Error index 0 |
220 |
Num. of Err In 0 |
221 |
Number of error index 0 |
222 |
Index of Errorcodes |
223 |
error code information |
224 |
number of errors |
225 |
FMU860 |
226 |
DT |
227 |
DVC |
228 |
FCX |
229 |
AS800 |
230 |
340T |
231 |
340C |
232 |
344 |
233 |
Siemens Micro K |
234 |
SITRANS L |
235 |
SIPAN PH |
236 |
SITRANS P |
237 |
75SMT |
238 |
UNIDELTA |
239 |
8320 |
240 |
SX5100 |
241 |
TSV175 |
242 |
DMU |
243 |
3780 |
244 |
BM70 |
245 |
8u |
246 |
Reset changed flag ? |
247 |
Reset changed flag successfully performed! |
248 |
Selection for Flow Simulation |
249 |
100%;50%;0%;-50%;-100%;End |
250 |
Simulation Start? |
251 |
yes;no |
252 |
Flow Simulation is set to 100% |
253 |
Flow Simulation is set to 50% |
254 |
Flow Simulation is set to 0% |
255 |
Flow Simulation is set to -50% |
256 |
Flow Simulation is set to -100% |
257 |
Flow Simulation is finished |
258 |
Offset-value is %{offset}. |
259 |
Increment Offset;Decrement Offset;Set gain-value |
260 |
Gain-value is %{gain} |
261 |
Increment Offset;Decrement Offset;End |
262 |
Analog Calibration is finished |
263 |
Pipe filled? |
264 |
Empty-Pipe-Value: %0 |
265 |
Set Hysteres Value: %{pipehyst} |
266 |
Hysteres Value %{empty_pipe_calibration_hysteresis} is higher than 5000 - Empty Pipe Value: %{pipe_difference} |
267 |
Empty Pipe Calibration successfully performed! |
268 |
Preset Restart successfully performed! |
269 |
Selection for Reset |
270 |
Reset Tot+;Reset Tot-;Reset Tot Day;Reset Tot All;End |
271 |
Reset Tot+ successfully performed! |
272 |
Reset Tot- successfully performed! |
273 |
Reset Tot Day successfully performed! |
274 |
Reset Tot All successfully performed! |
275 |
Error list is deleted. |
276 |
Set Pulse width: %0 |
277 |
Set Frequency: %0 |