0 |
pdpCustomerMaxMinValues units |
1 |
inH2O (68°F) |
2 |
inHg (0°C) |
3 |
ftH2O (68°F) |
4 |
mmH2O (68°F) |
5 |
mmHg (0°C) |
6 |
psi |
7 |
bar |
8 |
mbar |
9 |
g/cm2 |
10 |
kg/cm2 |
11 |
Pa |
12 |
kPa |
13 |
torr (0°C) |
14 |
atm |
15 |
inH2O (60°F) |
16 |
MPa |
17 |
inH2O (4°C) |
18 |
mmH2O (4°C) |
19 |
staticPressureCustomerMaxMinValues units |
20 |
sensorTemperatureCustomerMaxMinValues units |
21 |
°C |
22 |
°F |
23 |
°R |
24 |
K |
25 |
Min value reached by the Pressure Sensor |
26 |
Min.Pressure Value |
27 |
.3f |
28 |
Max value reached by the Pressure Sensor |
29 |
Max.Pressure Value |
30 |
Min value reached by the Static Pressure Sensor |
31 |
Min.Static Pressure Value |
32 |
Max value reached by the Static Pressure Sensor |
33 |
Max.Static Pressure Value |
34 |
Min value reached by the Sensor Temperature |
35 |
Min.Temperature Value |
36 |
.2f |
37 |
Max value reached by the Sensor Temperature |
38 |
Max.Temperature Value |
39 |
array CustomerMaxMin |
40 |
index array CustomerMaxMin |
41 |
pdpServiceMaxMinValues units |
42 |
staticPressureServiceMaxMinValues units |
43 |
sensorTemperatureServiceMaxMinValues units |
44 |
array ServiceMaxMin |
45 |
index array ServiceMaxMin |
46 |
reset customerMaxMinValues |
47 |
reset serviceMaxMinValues |
48 |
Simulation Status |
49 |
Disabled |
50 |
Enabled |
51 |
pdpSimulation units |
52 |
Pressure Value |
53 |
staticPressureSimulation_units |
54 |
Static P.Value |
55 |
sensorTemperatureSimulation units |
56 |
Sens.Temp.Val |
57 |
array SimulationValues |
58 |
index array_SimulationValues |
59 |
Set PV to desired Value |
60 |
pdpBiasValue units |
61 |
Value used as Bias for the elevation or suppression of the measure in order to match the Output with what desired as New PV |
62 |
Bias Value |
63 |
Upper Range Value |
64 |
Upper Range Value |
65 |
Lower Range Value |
66 |
Lower Range Value |
67 |
Warning! Span too Small |
68 |
Curve for output signal |
69 |
Linearization Type |
70 |
Linear |
71 |
Linear Table 22pt |
72 |
Cylindrical tank- fixed table |
73 |
Spherical tank- fixed function |
74 |
Square Root |
75 |
Square Root Third Power |
76 |
Square Root Fifth Power |
77 |
Bi-Directional Square Root |
78 |
Unit |
79 |
Unit for digital output |
80 |
ft3/min |
81 |
gal/min |
82 |
L/min |
83 |
ImpGal/min |
84 |
m3/h |
85 |
ft/s |
86 |
m/s |
87 |
gal/s |
88 |
Million gal/d |
89 |
L/s |
90 |
MillionL/d |
91 |
ft3/s |
92 |
ft3/d |
93 |
m3/s |
94 |
m3/d |
95 |
ImpGal/h |
96 |
ImpGal/d |
97 |
mV |
98 |
Ohms |
99 |
Hz |
100 |
mA |
101 |
gal |
102 |
L |
103 |
ImpGal |
104 |
m3 |
105 |
ft |
106 |
m |
107 |
barrels |
108 |
in |
109 |
cm |
110 |
mm |
111 |
min |
112 |
s |
113 |
h |
114 |
d |
115 |
cST |
116 |
cP |
117 |
microS |
118 |
% |
119 |
V |
120 |
pH |
121 |
g |
122 |
kg |
123 |
t |
124 |
lb |
125 |
STon |
126 |
LTon |
127 |
mS/cm |
128 |
microS/cm |
129 |
N |
130 |
N.m |
131 |
g/s |
132 |
g/min |
133 |
g/h |
134 |
kg/s |
135 |
kg/min |
136 |
kg/h |
137 |
kg/d |
138 |
t/min |
139 |
t/h |
140 |
t/d |
141 |
lb/s |
142 |
lb/min |
143 |
lb/h |
144 |
lb/d |
145 |
STon/min |
146 |
STon/h |
147 |
STon/d |
148 |
LTon/h |
149 |
LTon/d |
150 |
decaTherm |
151 |
SGU |
152 |
g/cm3 |
153 |
kg/m3 |
154 |
lb/gal |
155 |
lb/ft3 |
156 |
g/ml |
157 |
kg/L |
158 |
g/L |
159 |
lb/in3 |
160 |
STon/yd3 |
161 |
°Twad |
162 |
°Baum (hv) |
163 |
°Baum (lt) |
164 |
°API |
165 |
% sol/wt |
166 |
% sol/vol |
167 |
°Ball |
168 |
proof/vol |
169 |
proof/mass |
170 |
Bushel |
171 |
yd3 |
172 |
ft3 |
173 |
in3 |
174 |
in/s |
175 |
in/min |
176 |
ft/min |
177 |
deg/sec |
178 |
rps |
179 |
rpm |
180 |
m/h |
181 |
m3/h normal |
182 |
L/h normal |
183 |
ft3/min std |
184 |
bbl (liq) |
185 |
oz |
186 |
ft·lbf |
187 |
kW |
188 |
kW·h |
189 |
hp |
190 |
ft3/h |
191 |
m3/min |
192 |
barrels/s |
193 |
barrels/min |
194 |
barrels/h |
195 |
barrels/d |
196 |
gal/h |
197 |
ImpGal/s |
198 |
L/h |
199 |
ppm |
200 |
Mcalth/h |
201 |
MJ/h |
202 |
Btuth/h |
203 |
deg |
204 |
rad |
205 |
micro g/L |
206 |
icro g/m3 |
207 |
%Consistency |
208 |
% vol |
209 |
% stm qual |
210 |
Ft in Sixteenths |
211 |
ft3/lb |
212 |
pF |
213 |
ml/L |
214 |
micro l/L |
215 |
%Plato |
216 |
% Lower Explosion Level |
217 |
Mcalth |
218 |
Kohms |
219 |
MJ |
220 |
Btuth |
221 |
m3 normal |
222 |
L normal |
223 |
ft3 std |
224 |
ppb |
225 |
gal/d |
226 |
hl |
227 |
None |
228 |
Custom Unit |
229 |
Upper limit for digital output |
230 |
Lower limit for digital output |
231 |
Special unit |
232 |
Custom Unit |
233 |
static Pressure New Value |
234 |
staticPressureBias units |
235 |
special unit |
236 |
Min Temperature Limit |
237 |
Minimum limit of temperature within the sensor is compensated as from data sheet |
238 |
Max Temperature Limit |
239 |
Maximum limit of temperature within the sensor is compensated as from data sheet |
240 |
Sensor Temperature Trim Value |
241 |
Enables local operation with push buttons |
242 |
Local Operations |
243 |
Curve only for the variable to be displayed |
244 |
Unit of the variable to be displayed |
245 |
Unit |
246 |
Upper Range of the variable to be displayed |
247 |
Lower Range of the variable to be displayed |
248 |
Display language |
249 |
Language |
250 |
English |
251 |
German |
252 |
French |
253 |
Spanish |
254 |
Italian |
255 |
Display luminosity |
256 |
Contrast |
257 |
Selection of the lines to be used for the display |
258 |
Display Mode |
259 |
One Line |
260 |
One Line + Bargraph |
261 |
Two Lines |
262 |
Two Lines + Bargraph |
263 |
Variable to be displayed on line 1 |
264 |
Line 1 View |
265 |
Pressure |
266 |
Scaled output |
267 |
Current Output |
268 |
Output Percent |
269 |
Totalizer 1 |
270 |
Totalizer 2 |
271 |
Batch Counter |
272 |
Sensor Temperature |
273 |
Static Pressure |
274 |
HMI Scaled Output |
275 |
Variable to be displayed on line 2 |
276 |
Line 2 View |
277 |
Variable to be represented on the bargraph |
278 |
Bargraph View |
279 |
Software revision of the display when it is installed |
280 |
Display Revision |
281 |
Not Installed |
282 |
1 |
283 |
2 |
284 |
3 |
285 |
4 |
286 |
5 |
287 |
6 |
288 |
7 |
289 |
8 |
290 |
9 |
291 |
10 |
292 |
11 |
293 |
12 |
294 |
13 |
295 |
14 |
296 |
15 |
297 |
16 |
298 |
17 |
299 |
18 |
300 |
19 |
301 |
20 |
302 |
21 |
303 |
22 |
304 |
23 |
305 |
24 |
306 |
25 |
307 |
26 |
308 |
27 |
309 |
28 |
310 |
29 |
311 |
30 |
312 |
31 |
313 |
32 |
314 |
33 |
315 |
34 |
316 |
35 |
317 |
36 |
318 |
37 |
319 |
38 |
320 |
39 |
321 |
40 |
322 |
41 |
323 |
42 |
324 |
43 |
325 |
44 |
326 |
45 |
327 |
46 |
328 |
47 |
329 |
48 |
330 |
49 |
331 |
50 |
332 |
51 |
333 |
52 |
334 |
53 |
335 |
54 |
336 |
55 |
337 |
56 |
338 |
57 |
339 |
58 |
340 |
59 |
341 |
60 |
342 |
61 |
343 |
62 |
344 |
63 |
345 |
64 |
346 |
65 |
347 |
66 |
348 |
67 |
349 |
68 |
350 |
69 |
351 |
70 |
352 |
71 |
353 |
72 |
354 |
73 |
355 |
74 |
356 |
75 |
357 |
resetPdpBias |
358 |
resetStaticPressureBias |
359 |
Long tag value |
360 |
Long Tag |
361 |
Limit gains near zero |
362 |
Lin.Square Root Point [%] |
363 |
Low flow cut off |
364 |
Cut Off |
365 |
Actual value of the reference |
366 |
Lower Balance Point |
367 |
|
368 |
Current table status |
369 |
Table status |
370 |
No Init |
371 |
Good |
372 |
Not Monoton Inc |
373 |
Not Enough Value |
374 |
Value Not Exp |
375 |
Currently Loading |
376 |
Not Init Offs |
377 |
New Operation |
378 |
Last Value |
379 |
Delete Point |
380 |
Insert Point |
381 |
Replace Point |
382 |
Sensor communication error |
383 |
Upper Balance Point |
384 |
Type of Sensor |
385 |
Sensor Type |
386 |
Differential Pressure |
387 |
Absolute Pressure |
388 |
Gauge Pressure |
389 |
Type of Sensor |
390 |
Differential Pressure |
391 |
Absolute Pressure |
392 |
Gauge Pressure |
393 |
pdpSensor_units |
394 |
Minimum value for range limits |
395 |
Lower Sensor Limit |
396 |
Maximum value for range limits |
397 |
Upper Sensor Limit |
398 |
Minimum difference between URV and LRV |
399 |
Minimum Span |
400 |
staticPressureTrim_units |
401 |
Minimum value for range limits |
402 |
Maximum value for range limits |
403 |
Minimum difference between URV and LRV |
404 |
array_PressureSensor_Limits_and_TrimValues |
405 |
index_array_PressureSensor_Limits_and_TrimValues |
406 |
HW version major |
407 |
SW version major |
408 |
dummy_revision_byte0 |
409 |
dummy_revision_byte1 |
410 |
dummy_revision_byte2 |
411 |
sensor revision byte 0 |
412 |
sensor revision byte 1 |
413 |
sensor revision byte 2 |
414 |
Material of process wetted diaphragm of the Sensor |
415 |
Diaphragm Material |
416 |
Monel |
417 |
Tantalum |
418 |
Ceramic |
419 |
AISI 316L Stainless Steel |
420 |
Hastelloy C276 |
421 |
Gold plated Hastelloy C276 |
422 |
Monel Gold Plated |
423 |
PTFE Hastelloy |
424 |
Monel 400 |
425 |
Not used |
426 |
Sensor filling liquid |
427 |
Filling Fluid |
428 |
Silicone Oil |
429 |
Fluorcarbon |
430 |
White oil (FDA) |
431 |
Inert Oil (Galden) |
432 |
Glycerin + H2O |
433 |
Santotherm |
434 |
Silicone oil food |
435 |
Vegetable oil Neobee |
436 |
Dowtherm |
437 |
Ethyl Benzene |
438 |
Ethyl Alcohol |
439 |
Prophylene glicol/water |
440 |
ABB Fill (dibutyl penthalate) |
441 |
Syltherm 800 |
442 |
Mercury |
443 |
DC97 9120 Pharma-B-Grade |
444 |
Mineral oil (Marcol 82) |
445 |
Silicon oil Hi Temp AN140 |
446 |
Silicon Oil Low Temp Syltherm XLT |
447 |
Inert Oil (Halocarbon 4.2) |
448 |
Not used |
449 |
Type of Process connction for Gauge pressure transmitters |
450 |
Process Connection Material |
451 |
Carbon Steel |
452 |
AISI 304SS |
453 |
AISI 316 Stainless Steel |
454 |
Hastelloy C |
455 |
Kynar |
456 |
17-PH-17 |
457 |
Type of Process connction on the side L of the Differential Transmitters |
458 |
Connection Type |
459 |
Conventional |
460 |
Remote Seal |
461 |
Level Flange Type Flush |
462 |
Level Flange Type Extended |
463 |
Welded Flange |
464 |
Level Sanitary |
465 |
Level Food |
466 |
No Flange, Direct Connection |
467 |
All Welded for Remote Seal |
468 |
Gasketed for Remote Seal |
469 |
Direct Mount Seal (level) |
470 |
Integral with seal |
471 |
Welding bushing |
472 |
Chemical tee |
473 |
Threaded |
474 |
364 Flange type |
475 |
Material of the process connection of the Differential Transmitters |
476 |
Flange Material |
477 |
AISI 304SS |
478 |
Material of process wetted sealing of the Differential Transmitters |
479 |
O-Ring Material |
480 |
AISI 316 SS |
481 |
PTFE |
482 |
Viton |
483 |
Buna-N |
484 |
Ethyl Prop. |
485 |
Nitrile Rubber (Perbunan NBR) |
486 |
Aluminium |
487 |
TFE Glass Filled |
488 |
Perfluoro elastomer |
489 |
EPDM |
490 |
Graphite |
491 |
Silicone Rubber |
492 |
Garlock |
493 |
Material of sealing plug of the Differential Transmitters |
494 |
Blanking Plug |
495 |
Number of remote seal(s) |
496 |
Number |
497 |
One |
498 |
Two |
499 |
One on low side |
500 |
One on high side |
501 |
Type of remote seal on the side H of the Sensor |
502 |
Type |
503 |
Wafer |
504 |
Off line threated |
505 |
Chemical Tee |
506 |
Button |
507 |
Triclamp & Cherry Burrell |
508 |
Alimentary (Union Nut) |
509 |
Union Connection |
510 |
Aseptic |
511 |
Off line flanged connection |
512 |
Sanitary Flush |
513 |
Sanitary Extended |
514 |
Flush Flanged |
515 |
Extended Flanged |
516 |
Urea Service |
517 |
Pulp & Paper |
518 |
Beverage |
519 |
Monel |
520 |
Tantalum |
521 |
AISI 316L Stainless Steel |
522 |
Inconel |
523 |
Hastelloy C276 |
524 |
AISI 316L TFE Coated |
525 |
Monel Gold Plated |
526 |
Hastelloy C276 TFE Coated |
527 |
Monel 400 |
528 |
Inert Oil (Galden) |
529 |
Glyceryn + H2O |
530 |
Silicon oil Hi Temp (AN140) |
531 |
Silicon oil Low Temp (Syltherm XLT) |
532 |
Silicon oil Hi Temp (DC740) |
533 |
Silicon oil (Baysilone M5 / 5 Cts) |
534 |
Silicon oil (DC200/ 10 Cts) |
535 |
Mineral oil (Marcol 122) |
536 |
Fail Safe Level |
537 |
Software Output fault direction between UP and DOWN |
538 |
High |
539 |
Low |
540 |
Saturation limit low of the analog output current |
541 |
Low Saturation |
542 |
Saturation limit High of the analog output current |
543 |
High Saturation |
544 |
< 4mA during a fault. |
545 |
Low Alarm Value |
546 |
> 20mA during a fault |
547 |
High Alarm Value |
548 |
Current Fail Safe |
549 |
Source of the Output fault between hardware and Software |
550 |
Hardware Fail Safe Type |
551 |
Software Fail Safe Type |
552 |
The current meas.value correspond to: |
553 |
pdpValue_units |
554 |
staticPressureValue_units |
555 |
sensorTemperatureValue_units |
556 |
communicationScaleOutValue_units |
557 |
Scaled Output |
558 |
totalizer1Value_units |
559 |
Custom unit |
560 |
Totalization 1 |
561 |
totalizer2Value units |
562 |
Totalization 2 |
563 |
totaliserBatchValue units |
564 |
Totalization Batch |
565 |
.0f |
566 |
pdpTrimValue units |
567 |
Cal Pressure |
568 |
staticPressureTrimValue units |
569 |
Cal Static Pres |
570 |
array_266deviceVariableValues |
571 |
index_array_266deviceVariableValues |
572 |
Maximum Working Pressure Units - The units of the Maximum working pressure. |
573 |
maxWorkingPressure units |
574 |
Maximum limit of pressure within the sensor is compensated. |
575 |
Max Working Pressure |
576 |
serialNo_Part0 |
577 |
serialNo_Part1 |
578 |
serialNo_Part2 |
579 |
serialNo_Part2a |
580 |
serialNo_Part3 |
581 |
serialNo_Part4 |
582 |
serialNo_Part5 |
583 |
opCode_saveActualTrimming |
584 |
Save Actual Trimming |
585 |
opCode_resetSensorTrimming |
586 |
Reset Sensor Trimming |
587 |
resetToDefault |
588 |
save to default |
589 |
En/Dis the effect of the PILD diagnosis result on the Process Variable output |
590 |
Affect PV |
591 |
Off |
592 |
On |
593 |
Lower bound of the frequency range over which the signal power is computed |
594 |
Band Low |
595 |
.5f |
596 |
Upper bound of the frequency range over which the signal power is computed |
597 |
Band High |
598 |
period of time the PILD decide for the plugging state |
599 |
Detection Time |
600 |
Max variation of the dP to maintain the last training still valid |
601 |
Max.Press.Deviation |
602 |
En/Dis. the automatic execution of the training |
603 |
Auto Retrain |
604 |
No |
605 |
Yes |
606 |
Duration of training period |
607 |
Training Time |
608 |
Num. of training attempts if the result is not valid |
609 |
Training Retries |
610 |
PILD algorithm sensitivity |
611 |
Sensitivity |
612 |
Lowest |
613 |
Very Low |
614 |
Medium |
615 |
Very High |
616 |
Highest |
617 |
En/Dis. the autotune of the signal frequency band |
618 |
Band Autotuning |
619 |
Start/Stop PILD execution |
620 |
PILD Command |
621 |
Idle |
622 |
Go-Off |
623 |
Training |
624 |
Stop Training |
625 |
diagnosisConditionNumber |
626 |
diagnosisConditionDetailsClass |
627 |
diagnosisConditionDetailsGroup |
628 |
diagnosisConditionDetailsPriority |
629 |
diagnosisConditionDetailsAlarmCounter |
630 |
diagnosisConditionDetailsAlarmTimeCounterDay |
631 |
diagnosisConditionDetailsAlarmTimeCounterMsec |
632 |
diagnosisConditionDetailsTimeStampLastAlarmDay |
633 |
diagnosisConditionDetailsTimeStampLastAlarmMsec |
634 |
diagnosisConditionDetailsCodes0 |
635 |
diagnosisConditionDetailsCodes1 |
636 |
diagnosisConditionDetailsCodes2 |
637 |
diagnosisConditionDetailsCodes3 |
638 |
diagnosisConditionDetailsCodes4 |
639 |
diagnosisConditionDetailsCodes5 |
640 |
diagnosisConditionDetailsCodes6 |
641 |
diagnosisConditionDetailsCodes7 |
642 |
diagnosisConditionDetailsCodes8 |
643 |
diagnosisConditionDetailsCodes9 |
644 |
diagnosisConditionDetailsCodes10 |
645 |
diagnosisConditionDetailsCodes11 |
646 |
diagnosisConditionDetailsCodes12 |
647 |
diagnosisConditionDetailsCodes13 |
648 |
Diagnosis Masking Byte 0 |
649 |
P-dP Out Of Limit |
650 |
Static Pressure Out Of Limit |
651 |
Sensor Temperature Out Of Limit |
652 |
Diagnosis Masking Byte 1 |
653 |
Primary Variable Out of Range |
654 |
Diagnosis Masking Byte 2 |
655 |
Non-Volatile memory burn error |
656 |
Electronic Interface error |
657 |
Memory Failure |
658 |
Diagnosis Masking Byte 3 |
659 |
Max.Working Pressure Exceeded |
660 |
Diagnosis Masking Byte 4 |
661 |
Pressure Overrange |
662 |
Impulse Line on Low Side Plugged |
663 |
Analog Output Saturated |
664 |
Unreliable Output Current |
665 |
Power Supply warning |
666 |
Configuration Error |
667 |
PILD Output |
668 |
Changed Operating Conditions |
669 |
Diagnosis Masking Byte 5 |
670 |
Output ReadBack Failure |
671 |
Electronic Temperature out of Limit |
672 |
Diag Simulation |
673 |
By enabling diagnosis simulation, any one diagnosis can be simulated at a time. Actual device diagnosis are not reported when diagnosis simulation is turned ON |
674 |
Diagnosis Simulation Group0 |
675 |
P-dP Sensor Fail |
676 |
Static Pressure Sensor Fail |
677 |
Sensor Temperature Fail |
678 |
Both Impulse Lines Plugged |
679 |
Diagnosis Simulation Group1 |
680 |
Impulse Line on High Side Plugged |
681 |
Impulse Line on Low Side Plugged |
682 |
One Undetected impulse line plugged |
683 |
Diagnosis Simulation Group2 |
684 |
Sensor Memory Fail |
685 |
Analog Output Low Saturated |
686 |
Analog Output High Saturated |
687 |
Digital to Analogue converter problem |
688 |
Diagnosis Simulation Group3 |
689 |
Wrong Device Configuration |
690 |
Electronic Temperature out of High Limit |
691 |
Electronic Temperature out of Low Limit |
692 |
Power Supply too Low |
693 |
Power Supply too High |
694 |
P-dP Simulation Active |
695 |
Diagnosis Simulation Group4 |
696 |
Static Pressure Simulation Active |
697 |
Sensor Temperature Simulation Active |
698 |
Primary variable Out of High Range |
699 |
Primary variable Out of Low Range |
700 |
Missing Primary Signal |
701 |
Invalid Sensor |
702 |
Trend Configuration Error |
703 |
Diagnosis Simulation Group5 |
704 |
Replace required-Both data direction valid |
705 |
Replace required - FE to CB not applicable |
706 |
Replace enabled -FE to CB not applicable |
707 |
Totaliser Configuration Error |
708 |
PILD algorithm status |
709 |
PILD Status |
710 |
Normal |
711 |
PILD Diagnosis conditions |
712 |
Not Valid |
713 |
Press Deviation too different |
714 |
One Undetected line Plugged |
715 |
Both Lines Plugged |
716 |
Line H Plugged |
717 |
Line L Plugged |
718 |
Training Output |
719 |
Result of the Training phase |
720 |
Training Not Done |
721 |
Training OK |
722 |
Training Frequency Tuning |
723 |
Training Power Instable |
724 |
Training Pressure Instable |
725 |
Training Process noises too low |
726 |
Process Condition (Min.Alfa) |
727 |
Number of Start up |
728 |
No. Power On |
729 |
Total Working time_day |
730 |
Total Working time_sec |
731 |
Partial Working time_0 |
732 |
Partial Working time_1 |
733 |
Engineering unit of the Totalizer |
734 |
Conversion factor to be applied to the selected Input variable for the Totalizer |
735 |
Conv.Factor |
736 |
.4f |
737 |
Input Selector |
738 |
MassFlow |
739 |
VolumetricFlow |
740 |
Direction of the totalization counting |
741 |
Count direction |
742 |
Up |
743 |
Down |
744 |
Value the batch totalization must reach for UP counting or to start from for DOWN counting |
745 |
Preset Value |
746 |
Reloading type of the Preset Value |
747 |
Reload |
748 |
Auto Reload |
749 |
One Shot |
750 |
Totalization Mode |
751 |
Totalizer Mode |
752 |
Batch |
753 |
Mode1 (Forward/Reverse) |
754 |
Mode2 (Forward-Reverse) |
755 |
Mode3 (Forward+Reverse) |
756 |
totalizer1_dummyvar |
757 |
input to be totalized |
758 |
totalizer2_dummyvar |
759 |
index_array_totalizerConfig |
760 |
array totalizerConfig |
761 |
totalizer Password Action |
762 |
Password for enabling the reset of the Totalizer |
763 |
Entry Password |
764 |
Totalizer Reset |
765 |
Totalizer Status |
766 |
Start/stop Totalization |
767 |
Stop |
768 |
Run |
769 |
Status of the totalizer protection |
770 |
Protected |
771 |
Unprotected |
772 |
Integration Time |
773 |
A/D converter integration time |
774 |
sec |
775 |
Identify |
776 |
Device |
777 |
Additional Device Revision |
778 |
Measurement Point |
779 |
Additional Information |
780 |
Parameterize |
781 |
General |
782 |
Sensor Set-up |
783 |
P-dP Sensor |
784 |
Static Press Sensor |
785 |
Operational Limits |
786 |
Sensor Materials |
787 |
Process Connection High Side |
788 |
Process Connection Low Side |
789 |
Basic Sensor Materials |
790 |
Gauge Sensor |
791 |
Remote Seals |
792 |
Quantity |
793 |
High Side |
794 |
Low Side |
795 |
P-dP |
796 |
Process Variable [P/dP] |
797 |
Measured Value |
798 |
Scaling |
799 |
Value Input |
800 |
Process Pressure Transfer |
801 |
PV Bias |
802 |
Parallel Shift |
803 |
Transfer Function |
804 |
Square Root Setting |
805 |
Output [P/dP] |
806 |
Filter |
807 |
Hart Mapping |
808 |
Fail Safe |
809 |
Current Saturation Limits |
810 |
Current Alarm Limits |
811 |
Totalizer |
812 |
Input Setting |
813 |
Batch Setting |
814 |
Display |
815 |
Display Setting |
816 |
Display Scaling |
817 |
Process Variable |
818 |
Output |
819 |
Operate |
820 |
Extras |
821 |
Resets |
822 |
Reset |
823 |
Savings |
824 |
Load factory settings |
825 |
Totalizer Protection |
826 |
Change Password |
827 |
Reset Totalizer |
828 |
Simulation |
829 |
Calibration |
830 |
Pressure Sensor |
831 |
Diagnosis |
832 |
Diagnosis Monitoring |
833 |
Device state is :Maintenance required |
834 |
Device state is :Function check |
835 |
Device state is :Out of specification |
836 |
Device state is :Failure |
837 |
Device state is OK |
838 |
Electronics |
839 |
Sensor/Actuators |
840 |
Installation/Start up |
841 |
Process |
842 |
Operating Conditions |
843 |
Configuration |
844 |
PILD |
845 |
PILD Monitoring |
846 |
PILD Training |
847 |
PILD Setting |
848 |
Historic Info |
849 |
Pressure Variable Logging |
850 |
Sensor Temperature Logging |
851 |
Static Pressure Logging |
852 |
Offline |
853 |
Output Simulation |
854 |
Physical device identification |
855 |
Observe |
856 |
Trend |
857 |
Analog Output |
858 |
Edit user curve |
859 |
User-Curve Value |
860 |
User-Curve |
861 |
User-Curve Graph |
862 |
Customer Specific Curve |
863 |
Displays the Customer specific Input points,Output points |
864 |
No. |
865 |
X-value in % |
866 |
Y-value in % |
867 |
X0 Val |
868 |
7.3f |
869 |
X1 Val |
870 |
X2 Val |
871 |
X3 Val |
872 |
X4 Val |
873 |
X5 Val |
874 |
X6 Val |
875 |
X7 Val |
876 |
X8 Val |
877 |
X9 Val |
878 |
X10 Val |
879 |
X11 Val |
880 |
X12 Val |
881 |
X13 Val |
882 |
X14 Val |
883 |
X15 Val |
884 |
X16 Val |
885 |
X17 Val |
886 |
X18 Val |
887 |
X19 Val |
888 |
X20 Val |
889 |
X21 Val |
890 |
Y0 Val |
891 |
Y1 Val |
892 |
Y2 Val |
893 |
Y3 Val |
894 |
Y4 Val |
895 |
Y5 Val |
896 |
Y6 Val |
897 |
Y7 Val |
898 |
Y8 Val |
899 |
Y9 Val |
900 |
Y10 Val |
901 |
Y11 Val |
902 |
Y12 Val |
903 |
Y13 Val |
904 |
Y14 Val |
905 |
Y15 Val |
906 |
Y16 Val |
907 |
Y17 Val |
908 |
Y18 Val |
909 |
Y19 Val |
910 |
Y20 Val |
911 |
Y21 Val |
912 |
Load curve from device |
913 |
Save curve to device |
914 |
Create a new curve and save it to device |
915 |
User Curve |
916 |
Input Pressure |
917 |
PdP |
918 |
Static Pressure |
919 |
Output |
920 |
Analog Output |
921 |
Analog |
922 |
Bargraph |
923 |
Rerange 4-20mA |
924 |
Set PV to Zero |
925 |
Enable the setting of the PV = 0.0 operation |
926 |
Set PV Val |
927 |
Enable the New PV operation |
928 |
PV Bias Reset |
929 |
PV Scaling Reset method - P-dP Bias will be Reset |
930 |
Enable Parallel Shift operation |
931 |
Rerange 4-20mA |
932 |
Perform a device rerange to 4 - 20ma by applying source pressure input. |
933 |
Set PV Zero |
934 |
PV Bias Reset - Static Pressure Bias will be Reset |
935 |
Parallel Shift |
936 |
Enable the Parallel Shift Operation |
937 |
Full trim method - The full trimming allows the performance of high or low trim. |
938 |
Full trim |
939 |
Sensor Temperature Trimming |
940 |
Sensor Temperature Trimming |
941 |
LO trim method - Allows the performance low trim. |
942 |
Lo Trim |
943 |
Reset Device |
944 |
Warm Start-up configuration is not changed the device is restarted |
945 |
Reset to User Sensor Trimming |
946 |
Reset Configuration To Default |
947 |
Reset device parameters to their default values (not the address) |
948 |
Reset Configuration Changed Flag |
949 |
Reset the device Configuration Changed flag |
950 |
Save as User Sensor Trimming |
951 |
Save the actual sensor trimming as User Trimming |
952 |
Save Configuration as Default |
953 |
The actual device configuration is saved as default configuration |
954 |
Reset Factory Sensor Trimming |
955 |
Reset to Factory Sensor Trimming |
956 |
Reset Factory Output Trimming |
957 |
Reset to Factory Output D/A converter Trimming |
958 |
Aborting Input Simulation |
959 |
Input Simulation |
960 |
Protect Totaliser |
961 |
Unprotect Totaliser |
962 |
Execute |
963 |
Reset Totalizer 1 |
964 |
Reset the Totalizer 1 value |
965 |
Reset Totalizer 2 |
966 |
Reset Totalizer Batch |
967 |
Reset the counter of Batch Number |
968 |
n |
969 |
Device Serial No |
970 |
Unique device serial No. |
971 |
Hardware Revision |
972 |
Hardware revision |
973 |
Software Revision |
974 |
Software Revision |
975 |
Sensor Revision |
976 |
cancel pild training |
977 |
PILD Execute |
978 |
PILD CommaNd Execute method |
979 |
More Info |
980 |
More Information Available:Electronic Temperature |
981 |
More Information Available:PILD Output |
982 |
More Information Available:Analog output |
983 |
More Information Available: Configuration Error |
984 |
More Information Available: input simulation |
985 |
More Information Available:unreliable Output Current |
986 |
More Information Available:invalid sensor |
987 |
More Info: |
988 |
More Information Available:primary value |
989 |
More Information Available:Replace Info |
990 |
Hours |
991 |
Total Working time |
992 |
Time the device is working |
993 |
Clear Other Diag Simulation |
994 |
Change PV Mapping |
995 |
Change SV Mapping |
996 |
Change TV Mapping |
997 |
Change QV Mapping |
998 |
P-dP |
999 |
Engineering Unit |
1000 |
Totalizer 2 |
1001 |
Batch Number |
1002 |
Set Lower Range Value |
1003 |
Perform a device rerange to 4 ma by applying source pressure input. |
1004 |
Set Upper Range Value |
1005 |
Perform a device rerange to 20 ma by applying source pressure input. |
1006 |
New PV |
1007 |
Desired Output Measure |
1008 |
Reset PV Bias |
1009 |
Enable the Reset of the Bias = 0.0 operation |
1010 |
Execution of the Parallel Shift operation |
1011 |
Pressure Simulation |
1012 |
Simulation Value |
1013 |
Static Pressure Simulation |
1014 |
Sensor Temp Simulation |
1015 |
Pressure Simulation |
1016 |
Static Pressure Simulation |
1017 |
Sensor Temperature Simulation |
1018 |
Pressure Input |
1019 |
Definition of High (+) and Low (-) sides of the Pressure Inputs |
1020 |
Direct |
1021 |
Reverse |
1022 |
Pressure Polarity |
1023 |
Local_DeviceSerialNumber |
1024 |
Device State |
1025 |
OK |
1026 |
Function Check |
1027 |
Out of Specification |
1028 |
Maintenance Required |
1029 |
Failure |
1030 |
2600T 266 Pressure |
1031 |
Possible Cause :Mechanical damage to the sensor. Loss of fill fluid from the cell; ruptured diaphragm..
Suggested Action :The sensor must be replaced. |
1032 |
Possible Cause :The circuitry for the sampling of the static pressure has failed.
Suggested Action : The sensor must be replaced. |
1033 |
Possible Cause :The circuitry for the sampling of the temperature has failed.
Suggested Action :The sensor must be replaced. |
1034 |
Reserved |
1035 |
Possible Cause :The measurement range has not been correctly calculated OR an incorrect transducer model has been selected.
Suggested Action :The compatibility of pressure transmitter model and process conditions has to be checked. Probably a different transmitter type is required. |
1036 |
Possible Cause :The static pressure of the process exceeds the limit of the sensor. Exceeding the Static Pressure can reduce accuracy, mechanically damage the diaphragm and may require calibration/replacement. An incorrect transducer model could have been selected.
Suggested Action :The compatibility of pressure transmitter model and process conditions has to be checked. Probably a different transmitter type is required. |
1037 |
Possible Cause :The temperature of the process environment affects the pressure transmitter; Excess temperature can reduce accuracy, degrade device components and may require calibration/replacement.
Suggested Action :The compatibility of pressure transmitter model and process conditions has to be checked. A different installation type could be required e.g. use of remote seals. |
1038 |
Sensor Invalid |
1039 |
Possible Cause :Sensor memory corrupted.
Suggested Action :The Sensor must be replaced. |
1040 |
Possible Cause :Writings to the Sensor non-Volatile Memory was not successful.
Suggested Action :The Sensor should be replaced as soon as possible. |
1041 |
Possible Cause :Exchange of data between Electronics and Sensor have problems.
Suggested Action :Power cycle the device and retry the operation, if the error persist the electronics should be replaced as soon as possible. |
1042 |
Memory Failure |
1043 |
Possible Cause :Electronic memory corrupted.
Suggested Action :The electronics must be replaced. |
1044 |
Possible Cause :Writings to the electronic non-Volatile Memory was not successful.
Suggested Action :The electronics should be replaced as soon as possible. |
1045 |
Input Simulation Active |
1046 |
Possible Cause :The static pressure of the process exceeds the limit of the max working Pressure supported by the transmitter. Exceeding the Max Working Pressure can mechanically damage the process connections (flanges, pipes....) and/or be dangerous .
Suggested Action :The compatibility of the process connection type and material with process conditions has to be checked. A different installation type could be required e.g. use of remote seals. |
1047 |
Possible Cause :This effect could be produced by other equipment on the process, (valves.....). Exceeding the pressure range can cause reduced accuracy or mechanical damage to the diaphragm material and may require calibration/replacement.
Suggested Action :The compatibility of pressure transmitter model and process conditions has to be checked. A different transmitter type could be required . |
1048 |
Loop Test |
1049 |
Possible Cause :The analog and digital analog outputs for the Primary Variable are held at the requested value. Device is in fixed current (Loop Test) mode.
Suggested Action :Use a HART configurator to place device back into normal operating mode (Remove from Loop Test - Fixed output mode). |
1050 |
Possible Cause :Process conditions have changed to an extent that new settings for the PILD algorithm are needed.
Suggested Action :A new Training is necessary for this new process condition. |
1051 |
PILD output |
1052 |
Possible Cause :The output circuit could be broken or not correctly calibrated.
Suggested Action :Perform an Output Trimming and if the error persist the electronics must be replaced. |
1053 |
Replace info |
1054 |
The Electronics or the Sensor have been changed,but the replacement operation has not been executed |
1055 |
Cmd 48 byte 14 |
1056 |
Device state |
1057 |
Function check |
1058 |
Out of specification |
1059 |
Failure |
1060 |
Maintenance required |
1061 |
Cmd 48 byte 16 |
1062 |
Cmd 48 byte 17 |
1063 |
Cmd 48 byte 18 |
1064 |
Cmd 48 byte 19 |
1065 |
Cmd 48 byte 20 |
1066 |
Cmd 48 byte 21 |
1067 |
Cmd 48 byte 22 |
1068 |
Cmd 48 byte 23 |
1069 |
QV is |
1070 |
New Lower range push upper range out of sensor limits |
1071 |
Pressure -Differential Pressure |
1072 |
Pdp USL |
1073 |
Pdp LSL |
1074 |
Pdp Minimum Span |
1075 |
7d |
1076 |
Physical unit for process pressure |
1077 |
Damp an irregular signal |
1078 |
Damping |
1079 |
.1f |
1080 |
Alarm with analog output |
1081 |
O/P during fault |
1082 |
Size |
1083 |
sensor1 trim low |
1084 |
sensor1 trim high |
1085 |
Sensor1 trim support |
1086 |
Pressure Status |
1087 |
Static Pressure Status |
1088 |
Sensor Temperature Status |
1089 |
Scaled Output Status |
1090 |
Totalization 1 Status |
1091 |
Totalization 2 Status |
1092 |
Pres LS |
1093 |
Pres Fmly stat |
1094 |
Acquisition Period |
1095 |
classification |
1096 |
device Family |
1097 |
StaticPr Value |
1098 |
Static Pressure will be shown in this unit |
1099 |
Static Pressure Unit |
1100 |
Static Pressure Collection |
1101 |
Linearity |
1102 |
sensor Temperature value |
1103 |
Sensor Temperature will be shown in this unit |
1104 |
Temperature Unit |
1105 |
Sensor Temperature Damping |
1106 |
SensorTemp Collection |
1107 |
devVar3 Value |
1108 |
devVar3 Damping |
1109 |
enggUnit collection |
1110 |
devVar4 value |
1111 |
devVar4 Units |
1112 |
Totaliser1 collection |
1113 |
devVar5 value |
1114 |
devVar5 Units |
1115 |
Totaliser2 collection |
1116 |
devVar6 value |
1117 |
devVar6 Units |
1118 |
Totaliser Batch Collection |
1119 |
P-dp |
1120 |
upload to device |
1121 |
upload from device |
1122 |
PV |
1123 |
SV |
1124 |
TV |
1125 |
QV |
1126 |
Squawk Control |
1127 |
Off |
1128 |
On |
1129 |
Squawk once |
1130 |
squawk_abort_label |
1131 |
Start Squawk |
1132 |
Common Tables |
1133 |
Interoperable * |
1134 |
Universal |
1135 |
Common Practice |
1136 |
Pressure Universal |
1137 |
Pressure Common |
1138 |
Menu |
1139 |
Rosemount Magflow |
1140 |
Rosemount Pressure |
1141 |
Moore Products |
1142 |
Siemens Pressure |
1143 |
P2 Common |
1144 |
Wireless |
1145 |
Munge |
1146 |
Analytical Oxygen/Combustion/Methane/CO |
1147 |
Flow Totalizer - Rate Indicator |
1148 |
Flow Variable Area |
1149 |
Flow Coriolis Mass |
1150 |
Flow Ultrasonic - Gas |
1151 |
Flow Ultrasonic - Liquid |
1152 |
Level Ultrasonic |
1153 |
Level Radar - Microwave |
1154 |
Pressure Absolute |
1155 |
Level Capacitance |
1156 |
Pressure Differential |
1157 |
Level Hydrostatic |
1158 |
Level |
1159 |
Pressure Absolute/Relative |
1160 |
Level Microwave |
1161 |
Level Radar |
1162 |
Level Density - Nuclear |
1163 |
Flow Electromagnetic |
1164 |
Flow Vortex |
1165 |
Flow Magmeter - Rack Version |
1166 |
Flow High Performance Magmeter |
1167 |
Flow Mass |
1168 |
Flow Ultrasonic |
1169 |
Flow Magnetic |
1170 |
Flow Magnetic - Custody Transfer |
1171 |
Flow 2-wire Magnetic |
1172 |
Flow Coriolis Mass - Custody Transfer |
1173 |
Flow 2-wire Vortex |
1174 |
Flow Thermal |
1175 |
Temperature Head Mounted |
1176 |
Temperature Compact |
1177 |
Temperature DIN Rail Mounted |
1178 |
Analytical pH |
1179 |
Analytical Conductivity - Conductive |
1180 |
Analytical Conductivity - Inductive |
1181 |
Temperature Sensor |
1182 |
Level Servo |
1183 |
Temperature DIN Rail |
1184 |
Temperature |
1185 |
Analytical ORP |
1186 |
Analytical pION |
1187 |
Analytical IConc |
1188 |
Analytical Electrode Conductivity |
1189 |
Analytical Toroidal Conductivity |
1190 |
Valve Positioner |
1191 |
Valve Controller |
1192 |
Pressure |
1193 |
Pressure Multivariable |
1194 |
Analytical pH/ORP |
1195 |
Flow Coriolis |
1196 |
Analytical Conductivity |
1197 |
Valve Positioner/Pneumatic |
1198 |
Valve Actuator - Electrical |
1199 |
Temperature Dual Input |
1200 |
Valve Actuator |
1201 |
Analytical Corrosion |
1202 |
Analytical Density - Nuclear |
1203 |
Level Continuous Gamma |
1204 |
Level Laser Ranging |
1205 |
Pressure Safety |
1206 |
Flow Vortex/Swirl |
1207 |
Flow |
1208 |
Analytical 4 Electrode Conductivity |
1209 |
Analytical 2 Electrode Conductivity |
1210 |
Analytical Troidal Conductivity |
1211 |
Analytical pH/ORP/pIon/Ion Conc |
1212 |
Analytical Oxygen |
1213 |
Pressure P, dP + Multivariable |
1214 |
Temperature 2-wire |
1215 |
Pressure w/ PID |
1216 |
Pressure Saturated Steam |
1217 |
Analytical Density - Gamma Ray |
1218 |
Level Gamma Ray |
1219 |
Analytical Weight - Gamma Ray |
1220 |
Level w/ Density - Gamma Ray |
1221 |
Analytical Motorized Density |
1222 |
Flow Multivariable Mass |
1223 |
Temperature Multivariable |
1224 |
Specialty HART-to-Analog Signal Conv |
1225 |
Flow dP |
1226 |
Pressure Low Power |
1227 |
Pressure Certified SIL2 |
1228 |
Interoperable |
1229 |
Analytical Density |
1230 |
Valve Positioner/Electropneumatic |
1231 |
Flow Magnetic Inductive |
1232 |
Analytical |
1233 |
Analytical Opacity Monitor |
1234 |
Analytical Oxygen/Combustion |
1235 |
Analytical 2-wire Conductivity |
1236 |
Analytical 2-wire Conductivity w/ pure H20 |
1237 |
Analytical 2-wire Conductivity w/ % conc |
1238 |
Analytical 2-wire Oxygen/Chlorine/Ozone |
1239 |
Analytical 2-wire pH/ORP |
1240 |
Analytical 2-wire Contacting/Toroidal |
1241 |
Analytical Oxygen - High Temperature |
1242 |
Analytical Conductivity w/ % conc |
1243 |
Analytical pH/ORP/ISE |
1244 |
Analytical Amperometric Analyzer |
1245 |
Analytical Dual Input Analyzer |
1246 |
Pressure Pressure/Level |
1247 |
Analytical Consistency |
1248 |
Analytical Microwave-Pulp Consistency |
1249 |
Analytical Microwave Consistency |
1250 |
Valve Digital Positioner |
1251 |
Valve Smart Valve Positioner |
1252 |
Temperature Differential |
1253 |
Analytical Dissolved Oxygen |
1254 |
Analytical pH Controller |
1255 |
Analytical Conductivity/Resistivity Controller |
1256 |
Analytical Conductivity/Resistivity |
1257 |
Level Displacement |
1258 |
Temperature w/ PID |
1259 |
Valve Universal Positioner |
1260 |
Level Radar - Reflex |
1261 |
Pressure Gauge |
1262 |
Pressure Sealed Gauge |
1263 |
Valve Digital Positioner w/ PID |
1264 |
Valve Intelligent Positioner |
1265 |
Analytical Gas Detector |
1266 |
Analytical Infrared Gas Detector |
1267 |
Analytical Electrochemical Gas Detector |
1268 |
Analytical Measuring Instruments |
1269 |
Level Magnostrictive |
1270 |
Valve On/Off Valve Controller |
1271 |
Level Radar - Pulse |
1272 |
Level Continuous Capactive |
1273 |
Valve Damper Actuator |
1274 |
Valve Electric Damper Actuator |
1275 |
Flow Electronic |
1276 |
Flow Vortex - Multiparameter Mass |
1277 |
Analytical UV Flame Detector |
1278 |
Analytical UVIR Flame Detector |
1279 |
Analytical IR Flame Detector |
1280 |
Analytical Fire Detector |
1281 |
Analytical Gas Detector Display Interface |
1282 |
Analytical Toxic Gas Detector |
1283 |
Analytical Flame Detector |
1284 |
Level Nuclear |
1285 |
Analytical Microwave |
1286 |
Analytical Density - Radiometric |
1287 |
Level Radiometric |
1288 |
Analytical Gas/Steam |
1289 |
Level Nucleonic |
1290 |
Analytical Blade Consistency |
1291 |
Analytical Rotary Consistency |
1292 |
Pressure Absolute/Differential |
1293 |
Positioner |
1294 |
Analytical Combustible Gas Detector |
1295 |
Analytical Point Infrared Gas Detector |
1296 |
Analytical Multi-Detector Monitor System |
1297 |
Valve Positioner/Electro-hydraulic |
1298 |
Valve Monitor |
1299 |
Enable on token-passing data link layer only |
1300 |
Enable on TDMA data link layer only |
1301 |
Enable on both TDMA and token-passing data link layer |
1302 |
WirelessHART Device |
1303 |
IEEE 802.15.4 2.4GHz DSSS with O-QPSK Modulation |
1304 |
Primary |
1305 |
Primary Analog Channel |
1306 |
Secondary |
1307 |
Secondary Analog Channel |
1308 |
Tertiary |
1309 |
Tertiary Analog Channel |
1310 |
Quaternary |
1311 |
Quaternary Analog Channel |
1312 |
Quinary |
1313 |
Quinary Analog Channel |
1314 |
Critical Power Failure |
1315 |
Lock all |
1316 |
Trim not supported |
1317 |
Configuration cannot be changed |
1318 |
Locked by gateway |
1319 |
Analog Input Channel |
1320 |
Analog Output Channel |
1321 |
Secondary Analog Channel Saturated |
1322 |
Tertiary Analog Channel Saturated |
1323 |
Quaternary Analog Channel Saturated |
1324 |
Quinary Analog Channel Saturated |
1325 |
Secondary Analog Channel Fixed |
1326 |
Tertiary Analog Channel Fixed |
1327 |
Quaternary Analog Channel Fixed |
1328 |
Quinary Analog Channel Fixed |
1329 |
Simulation active |
1330 |
The device is in simulation mode and the level output is not representative of the process. |
1331 |
Non-Volatile memory failure |
1332 |
The Non-Volatile memory check is invalid or maybe corrupt, or the battery of a battery-backed memory has failed. |
1333 |
Volatile memory error |
1334 |
The RAM memory check is invalid or maybe corrupt |
1335 |
Watchdog reset executed |
1336 |
A watchdog reset has been performed |
1337 |
Voltage conditions out of range |
1338 |
A voltage condition is outside its allowable range |
1339 |
Environmental conditions out of range |
1340 |
An internal or environmental condition is beyond acceptable limits. |
1341 |
Electronic failure |
1342 |
A hardware problem not related to the sensor has been detected. |
1343 |
Subdevice list changed |
1344 |
Duplicate master detected |
1345 |
Capacity Denied |
1346 |
The device was unable to acquire the communication bandwidth required to support the Burst Messaging specified |
1347 |
Bandwidth allocation pending |
1348 |
Block transfer pending |
1349 |
Continuous |
1350 |
The Burst Message is published continuously at (worst case) the Minimum Update Period. |
1351 |
Window |
1352 |
The Burst Message is triggered when the source value deviates more than the specified trigger value |
1353 |
Rising |
1354 |
The Burst Message is triggered when source value Rises Above the specified trigger value. |
1355 |
Falling |
1356 |
The Burst Message is triggered when the source value Falls Below the specified trigger value. |
1357 |
On-change |
1358 |
The Burst Message is triggered when any value in the message changes. |
1359 |
Battery life |
1360 |
Percent range |
1361 |
Loop current |
1362 |
Primary variable |
1363 |
Secondary variable |
1364 |
Tertiary variable |
1365 |
Quaternary variable |
1366 |
Enable event notification on token-passing data link layer |
1367 |
Enable event notification on TDMA data link layer |
1368 |
Enable event notification on TDMA and token-passing data link layer |
1369 |
Configuration changed event pending |
1370 |
Device status event pending |
1371 |
More status available event pending |
1372 |
Disable |
1373 |
Enable single data point trending |
1374 |
Enable filtered trending |
1375 |
The sample is filtered using a time constant equal to one-third the trend sample period |
1376 |
Enable average trending |
1377 |
The value obtained by dividing the sum of all samples in the period by the total number of samples |
1378 |
Read receive time |
1379 |
Write date and time |
1380 |
Non-Volatile Clock |
1381 |
When set the device contains a battery-backed clock. In this case, the clock does not need to be reset if there is a power failure. |
1382 |
Clock Uninitialized |
1383 |
The real-time clock has never been set with the date and time. For example, the clock is volatile and power was removed from and restored to the device. |
1384 |
Line Power |
1385 |
Device is powered via a hardwired connection to a plant power source. |
1386 |
Battery Power |
1387 |
Device operates solely of its (internal) battery. |
1388 |
Recharg.B./Power Sc. |
1389 |
Rechargeable battery power or power scavenging. The device has a short-term supply of energy (must be at least one hour) that is continuously being replenished. The device's power is being replenished by harvesting and converting energy from the environment surrounding the device (e.g. solar, vibration, heat). |
1390 |
Idle |
1391 |
Active search |
1392 |
Looking for neighbors. |
1393 |
Negotiating |
1394 |
Quarantined |
1395 |
Operational |
1396 |
Suspended |
1397 |
Deep sleep |
1398 |
Ultra-low power |
1399 |
Wireless Signal Found |
1400 |
Network packets have been recognized |
1401 |
Wireless Signal Identified |
1402 |
Wireless Time Synchronized |
1403 |
WirelessHart Signal Identified |
1404 |
Network Admission Requested |
1405 |
Set on transmission of first join request |
1406 |
Join Retrying |
1407 |
Set after the first join request retry (i.e. when number of join requests > 2). Cleared when device is authenticated or when Active Search started. |
1408 |
Join Failed |
1409 |
Set on transition from Active Search mode to Deep Sleep mode. Cleared on transition from Deep Sleep to Active Search. |
1410 |
Network Security Clearance Granted |
1411 |
Network Manager Session Established |
1412 |
Network Joined |
1413 |
Network Joined. Normal superframe and links obtained. |
1414 |
Network Bandwidth Requested |
1415 |
Negotiating Network Properties. Gateway session obtained. |
1416 |
Join Complete |
1417 |
Normal operating mode. |
1418 |
No restrictions |
1419 |
SI Only |
1420 |
Restricted to SI Unit codes only |
1421 |
Open - accept all devices |
1422 |
Use Whitelist for access |
1423 |
Use Blacklist |
1424 |
Use Whitelist and Blacklist |
1425 |
Lockdown - disable join links |
1426 |
Process automation device |
1427 |
Discrete device |
1428 |
Hybrid:Process automation+discrete |
1429 |
I/O System |
1430 |
WirelessHART Process automation device |
1431 |
WirelessHART Discrete device |
1432 |
WirelessHART Process automation+discrete |
1433 |
WirelessHART Gateway |
1434 |
WirelessHART Access point |
1435 |
WirelessHART Process adapter |
1436 |
WirelessHART Discrete adapter |
1437 |
WirelessHART enabled handheld/portable maintenance tool |
1438 |
Don't attempt to join |
1439 |
Join now |
1440 |
Attempt to join immediately on powerup or reset |
1441 |
US |
1442 |
United States of America |
1443 |
JP |
1444 |
Japan |
1445 |
DE |
1446 |
Germany |
1447 |
FR |
1448 |
France |
1449 |
ES |
1450 |
Spain |
1451 |
RU |
1452 |
Russian Federation |
1453 |
CN |
1454 |
People's Republic of China |
1455 |
Nominal |
1456 |
Device Power Status is nominal |
1457 |
Low |
1458 |
Device Power Status is low |
1459 |
Critically Low |
1460 |
Device Power Status is critically low |
1461 |
Recharging - Low |
1462 |
Recharging - High |
1463 |
Secondary Master |
1464 |
Primary Master |
1465 |
PV Analog Channel Saturated |
1466 |
PV Analog Channel Fixed |
1467 |
Device Profile |
1468 |
Device Diagnostic Status 0 |
1469 |
Device Diagnostic Status 1 |
1470 |
I/O and Subdevice Status |
1471 |
WirelessHART Status |
1472 |
Time Set Option |
1473 |
Real Time Clock Flags |
1474 |
Country |
1475 |
Country of intended device installation |
1476 |
SI Unit Control |
1477 |
Indicates if device should only display SI unit codes |
1478 |
Burst Trigger Units |
1479 |
Burst Trigger Class |
1480 |
Wired HART Enabled |
1481 |
Enabled on Wired HART device connection only |
1482 |
Wireless HART Enabled |
1483 |
Enabled on WirelessHART device connection only |
1484 |
Both Wired and WirelessHart Enabled |
1485 |
Enabled on both Wired and WirelessHART connections |
1486 |
Burst Msg Trigger Mode |
1487 |
Event Status |
1488 |
Event Notification Control |
1489 |
Operate mode Mask |
1490 |
Not Defined |
1491 |
Power Source |
1492 |
Power source of the device |
1493 |
Wireless Mode |
1494 |
Join Status |
1495 |
The current location in the joining sequence of operations. |
1496 |
Network Access Mode |
1497 |
Join Mode |
1498 |
Power Status |
1499 |
Power status of the device |
1500 |
Master Mode |
1501 |
This sets the I/O System's Data Link Layer operation on all channels as either primary or secondary master mode. |
1502 |
Trend Units |
1503 |
Trend Device Variable Unit Code |
1504 |
Trend Classification |
1505 |
Trend Device Variable Classification |
1506 |
Trend Control |
1507 |
Device Status Mask |
1508 |
Ext dev status Mask |
1509 |
Device Diagnostic Status 0 Mask |
1510 |
Device Diagnostic Status 1 Mask |
1511 |
Device Diagnostic Status 2 Mask |
1512 |
Device Diagnostic Status 3 Mask |
1513 |
AO saturated Mask |
1514 |
AO fixed Mask |
1515 |
Latched Device Status |
1516 |
Latched Ext dev status |
1517 |
Latched Operate Mode |
1518 |
Latched Device Diagnostic Status 0 |
1519 |
Latched Device Diagnostic Status 1 |
1520 |
Latched Device Diagnostic Status 2 |
1521 |
Latched Device Diagnostic Status 3 |
1522 |
Latched AO saturated |
1523 |
Latched AO fixed |
1524 |
Wireless Module Device Type |
1525 |
Device type of the Wireless Radio |
1526 |
Wireless Module Manufacturer ID |
1527 |
Manufacturer of the Wireless Radio contained in this device |
1528 |
Subdevice Device Type |
1529 |
Device type of the subdevice attached to this system. |
1530 |
Subdevice Manufacturer Id |
1531 |
Manufacturer of the subdevice attached to this system. |
1532 |
Time Stamp |
1533 |
Relative time value on network |
1534 |
8u |
1535 |
Dynamic Variables Returned for Device Variables |
1536 |
Command Response Truncated |
1537 |
Configuration Change Counter Mismatch |
1538 |
Status bytes mismatch |
1539 |
Device Variable |
1540 |
8.3f |
1541 |
Number of points in the Device is -> %{pdp_TAB_ACTUAL_NUMBER} |
1542 |
Upload in progress, please wait... |
1543 |
All X-Y values read from device !! |
1544 |
We are about to create a new linearisation curve. Please take care of following points to save a new curve successfully in the device
1) X/Y value pair must be monotonously incremented
2) First value of X/Y pair must be 0/0
3) Last value of X/Y pair must be 100/100
Continue ? |
1545 |
Yes;No |
1546 |
Select no of points (X/Y pairs) to be entered |
1547 |
2;3;4;5;6;7;8;9;10;11;12;13;14;15;16;17;18;19;20;21;22 |
1548 |
X0 Value |
1549 |
x0 |
1550 |
Y0 Value |
1551 |
y0 |
1552 |
X1 Value |
1553 |
x1 |
1554 |
Y1 Value |
1555 |
y1 |
1556 |
X2 Value |
1557 |
x2 |
1558 |
Y2 Value |
1559 |
y2 |
1560 |
X3 Value |
1561 |
x3 |
1562 |
Y3 Value |
1563 |
y3 |
1564 |
X4 Value |
1565 |
x4 |
1566 |
Y4 Value |
1567 |
y4 |
1568 |
X5 Value |
1569 |
x5 |
1570 |
Y5 Value |
1571 |
y5 |
1572 |
X6 Value |
1573 |
x6 |
1574 |
Y6 Value |
1575 |
y6 |
1576 |
X7 Value |
1577 |
x7 |
1578 |
Y7 Value |
1579 |
y7 |
1580 |
X8 Value |
1581 |
x8 |
1582 |
Y8 Value |
1583 |
y8 |
1584 |
X9 Value |
1585 |
x9 |
1586 |
Y9 Value |
1587 |
y9 |
1588 |
X10 Value |
1589 |
x10 |
1590 |
Y10 Value |
1591 |
y10 |
1592 |
X11 Value |
1593 |
x11 |
1594 |
Y11 Value |
1595 |
y11 |
1596 |
X12 Value |
1597 |
x12 |
1598 |
Y12 Value |
1599 |
y12 |
1600 |
X13 Value |
1601 |
x13 |
1602 |
Y13 Value |
1603 |
y13 |
1604 |
X14 Value |
1605 |
x14 |
1606 |
Y14 Value |
1607 |
y14 |
1608 |
X15 Value |
1609 |
x15 |
1610 |
Y15 Value |
1611 |
y15 |
1612 |
X16 Value |
1613 |
x16 |
1614 |
Y16 Value |
1615 |
y16 |
1616 |
X17 Value |
1617 |
x17 |
1618 |
Y17 Value |
1619 |
y17 |
1620 |
X18 Value |
1621 |
x18 |
1622 |
Y18 Value |
1623 |
y18 |
1624 |
X19 Value |
1625 |
x19 |
1626 |
Y19 Value |
1627 |
y19 |
1628 |
X20 Value |
1629 |
x20 |
1630 |
Y20 Value |
1631 |
y20 |
1632 |
X21 Value |
1633 |
x21 |
1634 |
Y21 Value |
1635 |
y21 |
1636 |
Select |
1637 |
Continue;Re-enter no of x/y pairs |
1638 |
Result :%[L]{pdp_TAB_STATUS} -> %{pdp_TAB_STATUS} |
1639 |
Click on 'Load curve from device' button to load the curve from device |
1640 |
Now Apply input pressure
URV:%{0} %{2} LRV:%{1} %{2} |
1641 |
Current process value: %{0} %{1} |
1642 |
Continue read value;Set as 4mA value;Set as 20mA value;Exit |
1643 |
Aborting procedure due to last error |
1644 |
PV value read
PV : %{0}%{1} |
1645 |
Set PV Zero;Ready |
1646 |
PV value read
PV: %{0}%{1} |
1647 |
Set PV Value;Ready |
1648 |
Enter new PV value: |
1649 |
P-dP Bias will be Reset |
1650 |
OP :%{2}% PV :%{0}%{1}
URV and LRV will be shifted. Continue? |
1651 |
Enter new OP percent val: |
1652 |
Now Apply input pressure
(URV is %{0}%{2})
(LRV is %{1}%{2}) |
1653 |
Read new value;Set as 4mA value;Set as 20mA value;Exit |
1654 |
Static Pressure Bias will be Reset |
1655 |
Last Input val used:
Hival: %{2}%{0}
Loval: %{1}%{0} |
1656 |
Select choice: |
1657 |
High Trim;Low Trim;Display limits;Exit |
1658 |
Apply a Hival Pres. Higher than Loval |
1659 |
Pressure stabilizing. PLEASE WAIT... |
1660 |
Pres. applied: %{1}%{0} |
1661 |
Enter applied Hival: |
1662 |
Apply a Loval Pres. Lower than Hival |
1663 |
Enter applied Loval: |
1664 |
SENSOR LIMITS:
USL: %{2}%{0}
LSL: %{1}%{0} |
1665 |
CALIBRATION:
URV: %{5}%{3}
LRV: %{4}%{3} |
1666 |
Applied values read:
PV: %{1}%{0} |
1667 |
Last Input val used:
Val: %{1}%{0} |
1668 |
Enter the reference Temperature: |
1669 |
Applied values read:
PV: %{1} %{0} |
1670 |
Applied zero reads:
PV: %{1}%{0} |
1671 |
Last Input val used:
Hival: %{2}%{0} Loval: %{1}%{0} |
1672 |
Last Input val used:
Loval: %{1}%{0} |
1673 |
Low Trim;Display limits;Exit |
1674 |
Apply Pres. |
1675 |
SENSOR LIMITS:
LSL: %{1}%{0} |
1676 |
CALIBRATION:
LRL: %{4}%{3} |
1677 |
Applied values read:
PV: %{1}
Units: %{0} |
1678 |
Applied zero reads:
PV: %{1}
Units: %{0} |
1679 |
Device will perform warm startup.After the end of this operation it may be necessary to reconnect the device. Continue? |
1680 |
The Sensor Trimming is set to the User trimming! Actual settings are lost. Continue? |
1681 |
The Device is set to default setting! Actual settings are lost.After the end of this operation it may be necessary to reconnect the device. Continue? |
1682 |
The Configuration Changed Flag is cleared! Continue? |
1683 |
The Actual Sensor Trimming is Saved as User Trimming! Continue? |
1684 |
The Actual device settings is Saved as Default setting! Continue? |
1685 |
The Sensor Trimming parameters are set to the factory settings! User specific settings are lost. Continue? |
1686 |
The Output Trimming parameters are set to the factory settings! User specific settings are lost. Continue? |
1687 |
Simulate Presure Value;Simulate Sensor Temperature Value;Exit |
1688 |
Enter the Pressure Simulation Value |
1689 |
Enter the Sensor Temperature Simulation Value |
1690 |
Simulate Presure Value;Simulate Static Presure Value;Simulate Sensor Temperature Value;Exit |
1691 |
Enter the Static Pressure Simulation Value |
1692 |
Enter the Password |
1693 |
Enter New Password |
1694 |
Warning! Totalizer 1 Value will be reset if you continue |
1695 |
Warning! Totalizer 2 Value will be reset if you continue |
1696 |
Warning! Totalizer Batch Value will be reset if you continue |
1697 |
Device Serial No:%{0}%{1}%{2}000000000%{4} |
1698 |
Device Serial No:%{0}%{1}%{2}00000000%{4} |
1699 |
Device Serial No:%{0}%{1}%{2}0000000%{4} |
1700 |
Device Serial No:%{0}%{1}%{2}000000%{4} |
1701 |
Device Serial No:%{0}%{1}%{2}00000%{4} |
1702 |
Device Serial No:%{0}%{1}%{2}0000%{4} |
1703 |
Device Serial No:%{0}%{1}%{2}000%{4} |
1704 |
Device Serial No:%{0}%{1}%{2}00%{4} |
1705 |
Device Serial No:%{0}%{1}%{2}0%{4} |
1706 |
Device Serial No:%{0}%{1}%{2}%{4} |
1707 |
Hardware Revision:0%{0}.0%{1}.0%{2} |
1708 |
Software Revision:0%{0}.0%{1}.0%{2} |
1709 |
Sensor Revision:0%{0}.0%{1}.0%{2} |
1710 |
The PILD is running.do you want to Stop it? |
1711 |
Please wait.... |
1712 |
PILD Status:%{0}
PILD Output: %{1}
PILD Training Output: %{2} |
1713 |
Do you want start now the new Training phase ? |
1714 |
This operation may take several minutes.. |
1715 |
PILD Training in progress.
Please wait.... |
1716 |
PILD Status: %{0}
PILD Output: %{1}
PILD Training Output: %{2} |
1717 |
Electronic Temperature out Of Low Limit |
1718 |
Electronic Temperature out Of High Limit |
1719 |
Electronic Temperature out Of Low Limit
Electronic Temperature out Of High Limit |
1720 |
Power Supply Too Low |
1721 |
Power Supply Too High |
1722 |
Power Supply Too Low
Power Supply Too High |
1723 |
Both Impulse Line plugged |
1724 |
Impulse Line On High Side Plugged |
1725 |
Impulse Line On Low Side Plugged |
1726 |
One Undetected Impulse Line Plugged |
1727 |
Both Impulse Line plugged
Impulse Line On High Side Plugged |
1728 |
Impulse Line On High Side Plugged
Impulse Line On Low Side Plugged |
1729 |
Impulse Line On High Side Plugged
One Undetected Impulse Line Plugged |
1730 |
Impulse Line On Low Side Plugged
One Undetected Impulse Line Plugged |
1731 |
Both Impulse Line plugged
One Undetected Impulse Line Plugged |
1732 |
Both Impulse Line plugged
Impulse Line On Low Side Plugged |
1733 |
Both Impulse Line plugged
Impulse Line On High Side Plugged
Impulse Line On Low Side Plugged |
1734 |
Impulse Line On High Side Plugged
Impulse Line On Low Side Plugged
One Undetected Impulse Line Plugged |
1735 |
Both Impulse Line plugged
Impulse Line On Low Side Plugged
One Undetected Impulse Line Plugged |
1736 |
Both Impulse Line plugged
Impulse Line On High Side Plugged
One Undetected Impulse Line Plugged |
1737 |
Both Impulse Line plugged
Impulse Line On High Side Plugged
Impulse Line On Low Side Plugged
One Undetected Impulse Line Plugged |
1738 |
Analog Output Low Saturated |
1739 |
Analog Output High Saturated |
1740 |
Analog Output Low Saturated
Analog Output High Saturated |
1741 |
Trend Configuration Error |
1742 |
Totaliser Configuration Error |
1743 |
Trend Configuration Error
Totaliser Configuration Error |
1744 |
P-dp Simulation Active |
1745 |
P-dp Simulation Active
Static Pressure Simulation Active |
1746 |
P-dp Simulation Active
Sensor Temperature Simulation Active |
1747 |
Static Pressure Simulation Active
Sensor Temperature Simulation Active |
1748 |
P-dp Simulation Active
Static Pressure Simulation Active
Sensor Temperature Simulation Active |
1749 |
Digital To Analog Convertor Problem |
1750 |
Wrong Device Configuration |
1751 |
Digital To Analog Convertor Problem
Wrong Device Configuration |
1752 |
Missing Primary Signal |
1753 |
Invalid Sensor |
1754 |
Missing Primary Signal
Invalid Sensor |
1755 |
Primary Value Out Of Low Range |
1756 |
Primary Value Out Of High Range |
1757 |
Primary Value Out Of Low Range
Primary Value Out Of High Range |
1758 |
Replace required - Both data direction valid |
1759 |
Replace required - FE to CB not applicable |
1760 |
Replace enabled - FE to CB not applicable |
1761 |
Replace required - Both data direction valid
Replace required - FE to CB not applicable |
1762 |
Replace required - Both data direction valid
Replace enabled - FE to CB not applicable |
1763 |
Replace required - FE to CB not applicable
Replace enabled - FE to CB not applicable |
1764 |
Replace required - Both data direction valid
Replace required - FE to CB not applicable
Replace enabled - FE to CB not applicable |
1765 |
Days :%{1}
Hours :%{2}
Minutes :%{3}
Seconds :%{4} |
1766 |
PV is: |
1767 |
SV is: |
1768 |
TV is: |
1769 |
QV is: |
1770 |
Select the Lock type: |
1771 |
Permanent lock;Temporary lock;Lock All |
1772 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}000000000%{Local_DeviceSerialNumber} |
1773 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}00000000%{Local_DeviceSerialNumber} |
1774 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}0000000%{Local_DeviceSerialNumber} |
1775 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}000000%{Local_DeviceSerialNumber} |
1776 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}00000%{Local_DeviceSerialNumber} |
1777 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}0000%{Local_DeviceSerialNumber} |
1778 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}000%{Local_DeviceSerialNumber} |
1779 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}00%{Local_DeviceSerialNumber} |
1780 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}0%{Local_DeviceSerialNumber} |
1781 |
Device Serial No:%{serialNo_Part0}%{serialNo_Part1}%{serialNo_Part2}%{Local_DeviceSerialNumber} |
1782 |
Squawk in progress.. |
1783 |
Do you want to end squawk? |