Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sensor_type | 4016 | センサー タイプ | Sensor type - Indicates the type of the sensor element: millivolt, thermocouple type, resistance thermometer type, ohms. | R/W | Enum | 2048 |
measurement_type | 4010 | 測定対象 | Measurement type - Indicates the type of measurement: single/differential or average, internal/external or const CJC, external CJC sensor Pt100 or Ni100, 2/3 or 4 wire. | R/W | Enum | 2048 |
meter_option | 4017 | メーター タイプ | Meter option - Defines whether there is a meter installed or not and possibly what information the meter will display. | R/W | Enum | 256 |
system_config | 4018 | system configuration | For future use | R | Enum | 2048 |
const_cjc_value | 4019 | Const. CJC value | Constant CJ temperature value, the actual temperature at the junction of the thermocouple wires and the terminals. Units of PV | R/W | Float | 2048 |
rtd_factor | 401A | RTD factor | Multiplication factor for 100 Ohm RTD, reciprocal value, e.g. X=2 for Pt50, X=0.1 for Pt1000 | R/W | Float | 2048 |
abs_max_value | 401B | Abs. max. value | Absolute maximum value on individual sensors for differential measurements in units of PV | R/W | Float | 2048 |
cable_resistance_config | 401C | Cable resistance config | Cable resistance configuration - Configures the cable resistance value | R/W | Enum | 4096 |
cable_resistance_value | 401D | Cable resistance value | Cable resistance value in Ohms. If RTD/Ohm 3 or 4 wire is selected, sensor 1 is the expected max value for the total cable resistance in 2 wires, otherwise it is the actual total cable resistance. | R/W | Float | 4096 |
current_output_100 | 401E | AO 100% | Output current value at PV = 100%, units of mA | R/W | Float | 2048 |