Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pv_digital_units | 4001 | PV unit | Field Device Variable Unit - Engineering unit that the Digital Value, Upper Range Value and Lower Range value will be displayed with. Any unit defined in Table 2. Unit Codes of the Common Tables document will be accepted, but calculation of values between units by the device, are only done when units are degC, degF ,degR or Kelvin | R/W | Enum | 0 |
atransfer_function | 4002 | Xfer fnctn | R/W | Enum | 0 | |
pv_digital_value | 4003 | PV | Field Device Variable Value - Digital value that dynamicly represents the actual measured primary value of the device, in engineering units. | R | Float | 2 |
analog_value | 4004 | PV AO | Analog Output value - Indicates the current output of the field instrument. | R/W | Float | 2 |
percent_range | 4005 | PV % rnge | Percent of Range - Digital value that is proportional to the Digital Value with respect to the range defined by the Lower Range Value and the Upper Range Value. The Units of this variable is always in percent. | R | Float | 34 |
alarm_select | 4006 | AO Alrm typ | R/W | Enum | 2 | |
upper_range_value | 4007 | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 0 |
lower_range_value | 4008 | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 0 |
damping_value | 4009 | PV Damp | Damping Value - Damping time constant applied to both the Digital Value and Analog Value of the respective output. The Unit of this variable is always in seconds. | R/W | Float | 0 |
atemperature_upper_sensor_limit | 400A | USL | Upper Sensor Limit - Value that defines the absolute upper endpoint (largest magnitude) for the digital value. Temperature - Temperature of the process measured with respect to some reference pressure. | R | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |