Loading…
名称 ID 标签 描述 类型 访问 分类
burst_mode_select 0FFF 广播模式 广播模式选择——选择广播模式功能的模式。如果已使能广播,现场设备将在没有主机的个别请求的链接上生成HART消息。 枚举 128
pressure_units 138D 压力单位 Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure. 读/写 枚举 8
pressure_value 138E 压力 Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. 浮点 10
pressure_percent_range 138F 压力% 范围 Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. Pressure- Pressure of the process measured with respect to a reference pressure. 浮点 34
pressure_upper_range_limit 1393 压力 USL Upper Sensor Limit Value- Defines the maximum useable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. 浮点 8
pressure_lower_range_limit 1394 压力 LSL Lower Sensor Limit Value- Defines the minimum useable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. 浮点 8
pressure_minimum_span 1390 压力最小范围 Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. 浮点 8
pressure_output_transfer_function 1391 Pres xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. Pressure- Pressure of the process measured with respect to a reference pressure. 读/写 枚举 32
pressure_upper_range_value 1396 压力 URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. 读/写 浮点 32
pressure_lower_range_value 1397 压力 LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. 读/写 浮点 32
名称 ID 标签 描述 类型 访问 分类