Name ID Label Description Type Access Class
sensor_value 4000 PV Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention R Float 10
sensor_units 4001 PV Snsr unit Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit R Enum 8
sensor_upper_limit 4002 PV USL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
sensor_lower_limit 4003 PV LSL Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. R Float 8
sensor_minimum_span 4004 PV Min span Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. R Float 8
sensor_damping_value 4005 PV Damp Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. R Float 8
analog_value 4006 AO1 Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes R/W Float 66
analog_alarm_code 4007 AO Alrm typ Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. R Enum 64
input_percent_range 4008 PV % rnge Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
input_transfer_function 4009 Xfer fnctn Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. R Enum 32
input_units 400A PV rnge unit Range Unit- Engineering unit to be displayed with the Upper Range Value and Lower Range Value R Enum 32
input_upper_value 400B PV URV Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
input_lower_value 400C PV LRV Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. R Float 32
sensor_serial_number 400D PV Snsr s/n Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. R Unsigned 2048
wsc_st_rev 400E st_rev R Unsigned 34
wsc_mode_blk_target 400F Target Mode Set mode to OOS to be able to read & write parameters. If mode is set to AUTO parameters can be read only R/W Enum 32
wsc_mode_blk_actual 4010 Actual Mode R Enum 34
primary_value_type 4011 Meas The type of measurement represented by primary value. R Enum 32
primary_value_status 4012 PV.status The status of the primary value. R Unsigned 34
primary_value_value 4013 PV Primary value. R Float 34
primary_value_range_eu_100 4015 PV.range_eu_100 R Float 32
primary_value_range_eu_0 4016 PV.range_eu_0 R Float 32
primary_value_range_units 4014 PV.range_units R Enum 32
primary_value_range_dec_pnt 4017 PV.range_dec_pnt R Integer 32
sensor_const 4018 Adj CC The calibrated cell constant. R/W Float 32
cal_point_hi 401A Cal point hi The highest calibrated value. R Float 32
cal_point_lo 401B Cal point lo The lowest calibrated value. R Float 32
cal_min_span 401C Cal min span The minimum calibration span value allowed. R Float 32
sensor_cal_method 401D Sensor cal method The method of the last sensor calibration. R Enum 32
secondary_value_status 401E SV.status The status of the secondary value. R Unsigned 34
secondary_value_value 401F SV Secondary value (temperature). R Float 34
secondary_value_unit 4020 Temp unit The engineering unit of secondary value. R/W Enum 32
sensor_temp_comp 4021 Temp comp Temperature measurement mode. R/W Enum 32
sensor_temp_man_value 4022 Man value The temperature value used in manual mode. R/W Float 32
sensor_type_temp 4023 Temp sensor The type of the connected temperature sensor. R/W Enum 32
sensor_type_cond 4024 Sensor type The type of the connected conductivity sensor. R/W Enum 32
sensor_ohms 4025 Ohms The raw ohms value of the sensor. R Float 34
temperature_coeff 4026 TC SC1 The temperature coefficient of the primary value. R/W Float 32
concentration_status 4028 PV conc.status The status the primary value concentration. R Unsigned 34
concentration_value 4029 PV conc Primary value concentration. R Float 34
sensor_serial_nr 402B Sensor serial nr R ASCII 32
sensor_const_unit 4019 Meas unit The cell constant unit. R/W Enum 32
measurement_type 402C Measure Select process parameter. R/W Enum 32
comp_method 4027 Method SC1 Temperature compensation method. R/W Enum 32
concentration_unit 402A Conc unit Concentration unit. R/W Enum 32
comp_matrix_sel 402D Matrix SC1 Selected compensation matrix for primary value. R/W Enum 32
matrix_temp_range_1 402E Matrix temp rg 1 Matrix temperature range 1. R/W Float 32
matrix_temp_range_2 4031 Matrix temp rg 2 Matrix temperature range 2. R/W Float 32
matrix_temp_range_3 4032 Matrix temp rg 3 Matrix temperature range 3. R/W Float 32
matrix_temp_range_4 4033 Matrix temp rg 4 Matrix temperature range 4. R/W Float 32
Name ID Label Description Type Access Class