Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
squawk_control | 0988 | Squawk Control | W | Enum | 2048 | |
xmtr_chk_abort_flag | 415E | R/W | Unsigned | 4096 | ||
static_pressure_value | 4002 | SP | Static Pressure- Pressure of the process measured with respect to the reference pressure equal to 0. | R | Float | 10 |
static_pres_percent | 4003 | SP % | Static pressure percent of range- Static Pressure Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
snsr_temp_value | 4004 | センサー温度 | Sensor temperature- Temperature measured at sensor capsule. | R | Float | 10 |
easy_engr_unit | 40B4 | Engineer Unit Select Code for Easy Setting | R/W | Enum | 256 | |
engr_disp_value | 4005 | Engr Disp | Engineering display- Process variable displayed in user scale and unit. | R | Float | 258 |
engr_exp | 4006 | Engr exp | Engineering display exponents- Exponents for user scale display. | R/W | Enum | 256 |
engr_disp_unit | 4007 | Engr Unit | Engineering unit- Engineering unit for user scale display. | R/W | ASCII | 256 |
p_lower_trim_dev | 4039 | P LTD | Lower pressure trim deviation- Deviation from the original value. | R | Float | 8 |
p_upper_trim_dev | 403A | P UTD | Upper pressure trim deviation- Deviation from the original value. | R | Float | 8 |
sp_lower_trim_point | 403D | SP LTP | Lower static pressure trim point- Applied static pressure at which the last lower static pressure trim was performed. | R | Float | 8 |
sp_upper_trim_point | 403E | SP UTP | Upper static pressure trim point- Applied static pressure at which the last upper static pressure trim was performed. | R | Float | 8 |
sp_lower_trim_dev | 4040 | SP LTD | Lower static pressure trim deviation- Deviation from the original value. | R | Float | 8 |
sp_upper_trim_dev | 4041 | SP UTD | Upper static pressure trim deviation- Deviation from the original value. | R | Float | 8 |
trim_who | 4043 | Trim Who | Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record who to trim the device. | R/W | PackedAscii | 2048 |
trim_date | 4044 | Trim Date | Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record when the latest trim is done for the device. | R/W | HartDate | 2048 |
trim_loc | 4045 | Trim Loc | Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record where the latest trim is done for the device. | R/W | PackedAscii | 2048 |
trim_desc | 4046 | Trim Desc | Trim information- Text that is associated with the trim information. This text can be used by the user in any way, and there is no recommended use. | R/W | PackedAscii | 2048 |
low_cut_point | 4011 | Low cut | Low cut- Sets the range in vicinity of 0% within which the low cut function is activated according to the selected low cut mode. | R/W | Float | 2048 |
low_cut_mode | 4012 | Low cut mode | Low cut mode- Selects the type of the low cut function to be used; LINEAR or ZERO. | R/W | Enum | 2048 |
hl_swap | 4013 | H/L Swap | High/Low swap- Reverses the high pressure side and low pressure side of the transmitter. For example, use this function when assigning the high pressure impulse line connection to the L side of the transmitter. | R/W | Enum | 2048 |
sp_lrv | 4050 | SP LRV | Static Pressure Lower Range Value- Defines the operational endpoint from which the 0% point of the Percent Range are derived. | R/W | Float | 32 |
sp_urv | 4051 | SP URV | Static Pressure Upper Range Value- Defines the operational endpoint from which the 100% point of the Percent Range are derived. | R/W | Float | 32 |
static_pressure_units | 404A | SP Unit | Static Pressure Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Static Pressure. | R/W | Enum | 8 |
ag_select_mode | 4055 | A/G Select | Absolute/gauge selection- Type of Static pressure variable. | R/W | Enum | 2048 |
atm_pres_value | 4056 | Atm. Pres Value | Atmospheric Pressure Value- Sets the coefficient value used for the conversion of the measured absolute pressure value into gauge pressure value. | R/W | Float | 2048 |
sp_hl_select | 404D | SP H/L Select | Static Pressure High/Low Select- Measuring point of the static pressure; high pressure side or low pressure side. | R/W | Enum | 2048 |
amp_temp_value | 405A | Amp temp | Amp Temperature | R | Float | 10 |
temperature_units | 405B | Temp Unit | Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R/W | Enum | 8 |
bi_dir_mode | 4019 | Bi-dir mode | Bi-directional flow measurement setup- Enables/disables bi-directional flow measurement mode. In this mode, when the pressure equivalent to 0% is applied, the device outputs 50%. Applicable only for differential pressure transmitters. | R/W | Enum | 2048 |
quick_resp | 401A | Quick resp | Quick response- Enables/disables to set the damping value less than 0.5 sec. | R/W | Enum | 2048 |
tz_cmp_mode | 405C | T.Z. Cmp mode | Temperature Zero compensation mode- Enables/disables temperature zero compensation. | R/W | Enum | 2048 |
temp_zero | 405D | Temp Zero | Temperature Zero shift compensation- Defines the value to be used for temperature zero shift compensation. | R/W | Float | 2048 |
sc_enable | 405E | S.C. | Signal characterizer- Enables/disables signal characterizer function. | R/W | Enum | 2048 |
num_of_points | 405F | Num of points | Number of break points- Sets the number of points for signal characterizer. | R/W | Unsigned | 2048 |
x_start | 4061 | X Start | Displays the start point of X. | R | Float | 2048 |
y_start | 4062 | Y Start | Displays the start point of Y. | R | Float | 2048 |
x_end | 4063 | X End | Displays the end point of X. | R | Float | 2048 |
y_end | 4064 | Y End | Displays the end point of Y. | R | Float | 2048 |
digital_output | 4065 | Digital Output | Status of digital output- Displays the current status of digital output. | R | Enum | 1026 |
auto_recover | 4066 | Auto recover | Automatic recover- Defines if the device automatically returns to normal operation without restarting or not, once after it recovers from the sensor error status. | R/W | Enum | 2048 |
ao_lower_limit | 4067 | AO lower limit | Analog output lower limit- Sets the lower limit value for analog output. | R/W | Float | 64 |
ao_upper_limit | 4068 | AO upper limit | Analog output upper limit- Sets the upper limit value for analog output. | R/W | Float | 64 |
pres_alert_mode | 4069 | Pres Alert mode | Selects alert mode for pressure alarm. | R/W | Enum | 2048 |
pres_hi_alert_val | 4070 | Hi Alert Val | Sets threshold value for pressure high alarm. | R/W | Float | 2048 |
pres_lo_alert_val | 4071 | Lo Alert Val | Sets threshold value for pressure low alarm. | R/W | Float | 2048 |
sp_alert_mode | 406B | SP Alert mode | Selects alert mode for static pressure alarm. | R/W | Enum | 2048 |
temp_alert_mode | 406D | Temp Alert mode | Selects alert mode for sensor temperature alarm. | R/W | Enum | 2048 |
bar_indicator | 402F | Bar indicator | Bar indicator- Defines to show/hide bar indicator on LCD. | R/W | Enum | 256 |
Name | ID | Label | Description | Type | Access | Class |