Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sp_hi_alert_val | 4072 | SP Hi Alert Val | Sets threshold value for static pressure high alarm. | R/W | Float | 2048 |
sp_lo_alert_val | 4073 | SP Lo Alert Val | Sets threshold value for static pressure low alarm. | R/W | Float | 2048 |
temp_hi_alert_val | 4074 | Temp Hi Alert Val | Sets threshold value for sensor temperature high alarm. | R/W | Float | 8 |
temp_lo_alert_val | 4075 | Temp Lo Alert Val | Sets threshold value for sensor temperature low alarm. | R/W | Float | 8 |
do_select | 4076 | DO Select | DO selection- Select alarm(s) whose status should be output via digital output. | R/W | Enum | 1024 |
do_signal_type | 4077 | DO Signal type | DO signal type- Defines the action of digital output when the alarm is detected. | R/W | Enum | 1024 |
disp_out_1 | 4029 | Disp Out1 | LCD output1- Defines the variable to be shown on LCD. | R/W | Enum | 256 |
disp_out_2 | 402A | Disp Out2 | LCD output2- Defines the variable to be shown on LCD. | R/W | Enum | 256 |
disp_out_3 | 402B | Disp Out3 | LCD output3- Defines the variable to be shown on LCD. | R/W | Enum | 256 |
disp_out_4 | 402C | Disp Out4 | LCD output4- Defines the variable to be shown on LCD. | R/W | Enum | 256 |
disp_func | 402D | Disp Pres % fnctn | Display pressure % function- Defines the display mode for pressure variable in %; Linear or Squareroot. | R/W | Enum | 256 |
disp_pres_percent_reso | 402E | Disp Pres % Reso | Display pressure % resolution- Defines the display resolution level for pressure variable in %; normal or high resolution. | R/W | Enum | 256 |
pres_disp_point | 407D | Pres disp point | Pressure display decimal position- Defines the decimal point position for the pressure variable display. | R/W | Enum | 256 |
sp_disp_point | 407E | SP disp point | Static pressure display decimal point position- Defines the decimal point position for the static pressure variable display. | R/W | Enum | 256 |
engr_disp_lrv | 4030 | Engr LRV | Engineering display lower range value- Sets the lower range value equivalent to 0% for user scale display. | R/W | Float | 256 |
engr_disp_urv | 4031 | Engr URV | Engineering display upper range value- Sets the upper range value equivalent to 100% for user scale display. | R/W | Float | 256 |
engr_disp_point | 4032 | Engr point | Engineering display decimal position- Defines the decimal point position for user scale display. | R/W | Enum | 256 |
asc_model_1 | 4025 | Model 1 | Model 1- Model and Suffix codes of the device. | R/W | PackedAscii | 2048 |
asc_model_2 | 4026 | Model 2 | Model 2- Part of the Model and suffix codes of the device, which follows the codes shown in Model 1. | R/W | PackedAscii | 2048 |
asc_model_3 | 4027 | Model 3 | Model 3- Part of the Model and suffix codes of the device, which follows the codes shown in Model 2. | R/W | PackedAscii | 2048 |
style_no | 4082 | Style No. | Style code- Displays the style code of the device. | R | Float | 2048 |
asc_serial_no | 4033 | Serial No. | Serial number- Displays the serial number of the device. | R | PackedAscii | 2048 |
mftr_date | 4083 | Mftr Date | Manufacturing date- Displays the date of manufacturing the device. | R | HartDate | 2048 |
extra_no | 4084 | Extra No. | Extra number- Reference number for special customization. | R | PackedAscii | 2048 |
ext_sw_mode | 4028 | Ext SW | External zero-adjustment permission- Enables/disables external zero adjustment. | R/W | Enum | 2048 |
Name | ID | Label | Description | Type | Access | Class |