Loading…
Name ID Label Description Type Access Class
squawk_control 0988 Squawk Control W Enum 2048
xmtr_chk_abort_flag 415E R/W Unsigned 4096
static_pressure_value 4002 SP Static Pressure- Pressure of the process measured with respect to the reference pressure equal to 0. R Float 10
static_pres_percent 4003 SP % Static pressure percent of range- Static Pressure Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. R Float 34
snsr_temp_value 4004 Snsr temp Sensor temperature- Temperature measured at sensor capsule. R Float 10
easy_engr_unit 40B4 Engineer Unit Select Code for Easy Setting R/W Enum 256
engr_disp_value 4005 Engr Disp Engineering display- Process variable displayed in user scale and unit. R Float 258
engr_exp 4006 Engr exp Engineering display exponents- Exponents for user scale display. R/W Enum 256
engr_disp_unit 4007 Engr Unit Engineering unit- Engineering unit for user scale display. R/W ASCII 256
p_lower_trim_dev 4039 P LTD Lower pressure trim deviation- Deviation from the original value. R Float 8
p_upper_trim_dev 403A P UTD Upper pressure trim deviation- Deviation from the original value. R Float 8
sp_lower_trim_point 403D SP LTP Lower static pressure trim point- Applied static pressure at which the last lower static pressure trim was performed. R Float 8
sp_upper_trim_point 403E SP UTP Upper static pressure trim point- Applied static pressure at which the last upper static pressure trim was performed. R Float 8
sp_lower_trim_dev 4040 SP LTD Lower static pressure trim deviation- Deviation from the original value. R Float 8
sp_upper_trim_dev 4041 SP UTD Upper static pressure trim deviation- Deviation from the original value. R Float 8
trim_who 4043 Trim Who Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record who to trim the device. R/W PackedAscii 2048
trim_date 4044 Trim Date Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record when the latest trim is done for the device. R/W HartDate 2048
trim_loc 4045 Trim Loc Trim information- Text that is associated with the trim information. This text can be used by the user in any way. A recommended use is to record where the latest trim is done for the device. R/W PackedAscii 2048
trim_desc 4046 Trim Desc Trim information- Text that is associated with the trim information. This text can be used by the user in any way, and there is no recommended use. R/W PackedAscii 2048
low_cut_point 4011 Low cut Low cut- Sets the range in vicinity of 0% within which the low cut function is activated according to the selected low cut mode. R/W Float 2048
low_cut_mode 4012 Low cut mode Low cut mode- Selects the type of the low cut function to be used; LINEAR or ZERO. R/W Enum 2048
hl_swap 4013 H/L Swap High/Low swap- Reverses the high pressure side and low pressure side of the transmitter. For example, use this function when assigning the high pressure impulse line connection to the L side of the transmitter. R/W Enum 2048
sp_lrv 4050 SP LRV Static Pressure Lower Range Value- Defines the operational endpoint from which the 0% point of the Percent Range are derived. R/W Float 32
sp_urv 4051 SP URV Static Pressure Upper Range Value- Defines the operational endpoint from which the 100% point of the Percent Range are derived. R/W Float 32
static_pressure_units 404A SP Unit Static Pressure Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Static Pressure. R/W Enum 8
ag_select_mode 4055 A/G Select Absolute/gauge selection- Type of Static pressure variable. R/W Enum 2048
atm_pres_value 4056 Atm. Pres Value Atmospheric Pressure Value- Sets the coefficient value used for the conversion of the measured absolute pressure value into gauge pressure value. R/W Float 2048
sp_hl_select 404D SP H/L Select Static Pressure High/Low Select- Measuring point of the static pressure; high pressure side or low pressure side. R/W Enum 2048
amp_temp_value 405A Amp temp Amp Temperature R Float 10
temperature_units 405B Temp Unit Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. R/W Enum 8
bi_dir_mode 4019 Bi-dir mode Bi-directional flow measurement setup- Enables/disables bi-directional flow measurement mode. In this mode, when the pressure equivalent to 0% is applied, the device outputs 50%. Applicable only for differential pressure transmitters. R/W Enum 2048
quick_resp 401A Quick resp Quick response- Enables/disables to set the damping value less than 0.5 sec. R/W Enum 2048
tz_cmp_mode 405C T.Z. Cmp mode Temperature Zero compensation mode- Enables/disables temperature zero compensation. R/W Enum 2048
temp_zero 405D Temp Zero Temperature Zero shift compensation- Defines the value to be used for temperature zero shift compensation. R/W Float 2048
sc_enable 405E S.C. Signal characterizer- Enables/disables signal characterizer function. R/W Enum 2048
num_of_points 405F Num of points Number of break points- Sets the number of points for signal characterizer. R/W Unsigned 2048
x_start 4061 X Start Displays the start point of X. R Float 2048
y_start 4062 Y Start Displays the start point of Y. R Float 2048
x_end 4063 X End Displays the end point of X. R Float 2048
y_end 4064 Y End Displays the end point of Y. R Float 2048
digital_output 4065 Digital Output Status of digital output- Displays the current status of digital output. R Enum 1026
auto_recover 4066 Auto recover Automatic recover- Defines if the device automatically returns to normal operation without restarting or not, once after it recovers from the sensor error status. R/W Enum 2048
ao_lower_limit 4067 AO lower limit Analog output lower limit- Sets the lower limit value for analog output. R/W Float 64
ao_upper_limit 4068 AO upper limit Analog output upper limit- Sets the upper limit value for analog output. R/W Float 64
pres_alert_mode 4069 Pres Alert mode Selects alert mode for pressure alarm. R/W Enum 2048
pres_hi_alert_val 4070 Hi Alert Val Sets threshold value for pressure high alarm. R/W Float 2048
pres_lo_alert_val 4071 Lo Alert Val Sets threshold value for pressure low alarm. R/W Float 2048
sp_alert_mode 406B SP Alert mode Selects alert mode for static pressure alarm. R/W Enum 2048
temp_alert_mode 406D Temp Alert mode Selects alert mode for sensor temperature alarm. R/W Enum 2048
bar_indicator 402F Bar indicator Bar indicator- Defines to show/hide bar indicator on LCD. R/W Enum 256
Name ID Label Description Type Access Class