Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
low_cut_mode | 4012 | Low cut mode | Low cut mode- Selects the type of the low cut function to be used; LINEAR or ZERO. | R/W | Enum | 2048 |
hl_swap | 4013 | H/L Swap | High/Low swap- Reverses the high pressure side and low pressure side of the transmitter. For example, use this function when assigning the high pressure impulse line connection to the L side of the transmitter. | R/W | Enum | 2048 |
sp_lrv | 4050 | SP LRV | Static Pressure Lower Range Value- Defines the operational endpoint from which the 0% point of the Percent Range are derived. | R/W | Float | 32 |
sp_urv | 4051 | SP URV | Static Pressure Upper Range Value- Defines the operational endpoint from which the 100% point of the Percent Range are derived. | R/W | Float | 32 |
static_pressure_units | 404A | SP Unit | Static Pressure Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit for the Static Pressure. | R/W | Enum | 8 |
ag_select_mode | 4055 | A/G Select | Absolute/gauge selection- Type of Static pressure variable. | R/W | Enum | 2048 |
atm_pres_value | 4056 | Atm. Pres Value | Atmospheric Pressure Value- Sets the coefficient value used for the conversion of the measured absolute pressure value into gauge pressure value. | R/W | Float | 2048 |
sp_hl_select | 404D | SP H/L Select | Static Pressure High/Low Select- Measuring point of the static pressure; high pressure side or low pressure side. | R/W | Enum | 2048 |
amp_temp_value | 405A | Amp temp | Amp Temperature | R | Float | 10 |
temperature_units | 405B | Temp Unit | Field Device Variable Unit- Digital unit that the variable will be displayed with. Sensor Temperature- Temperature associated with the sensor that is responsible for a process measurement. | R/W | Enum | 8 |
Name | ID | Label | Description | Type | Access | Class |