Name ID Label Description Type Access Class
bi_dir_mode 4019 Bi-dir mode Bi-directional flow measurement setup- Enables/disables bi-directional flow measurement mode. In this mode, when the pressure equivalent to 0% is applied, the device outputs 50%. Applicable only for differential pressure transmitters. R/W Enum 2048
quick_resp 401A Quick resp Quick response- Enables/disables to set the damping value less than 0.5 sec. R/W Enum 2048
tz_cmp_mode 405C T.Z. Cmp mode Temperature Zero compensation mode- Enables/disables temperature zero compensation. R/W Enum 2048
temp_zero 405D Temp Zero Temperature Zero shift compensation- Defines the value to be used for temperature zero shift compensation. R/W Float 2048
sc_enable 405E S.C. Signal characterizer- Enables/disables signal characterizer function. R/W Enum 2048
num_of_points 405F Num of points Number of break points- Sets the number of points for signal characterizer. R/W Unsigned 2048
x_start 4061 X Start Displays the start point of X. R Float 2048
y_start 4062 Y Start Displays the start point of Y. R Float 2048
x_end 4063 X End Displays the end point of X. R Float 2048
y_end 4064 Y End Displays the end point of Y. R Float 2048