名称 ID 标签 描述 类型 访问 分类
bi_dir_mode 401B Bi-dir mode Bi-directional flow measurement setup- Enables/disables bi-directional flow measurement mode. In this mode, when the pressure equivalent to 0% is applied, the device outputs 50%. Applicable only for differential pressure transmitters. 读/写 枚举 2048
quick_resp 401C Quick resp Quick response- Enables/disables to set the damping value less than 0.5 sec. 读/写 枚举 2048
tz_cmp_mode 4054 T.Z. Cmp mode Temperature Zero compensation mode- Enables/disables temperature zero compensation. 读/写 枚举 2048
temp_zero 4055 Temp Zero Temperature Zero shift compensation- Defines the value to be used for temperature zero shift compensation. 读/写 浮点 2048
sc_enable 4073 S.C. Signal characterizer- Enables/disables signal characterizer function. 读/写 枚举 2048
num_of_points 4074 Num of points Number of break points- Sets the number of points for signal characterizer. 读/写 无符号 2048
x_start 4075 X Start Displays the start point of X. 浮点 2048
y_start 4076 Y Start Displays the start point of Y. 浮点 2048
x_end 4077 X End Displays the end point of X. 浮点 2048
y_end 4078 Y End Displays the end point of Y. 浮点 2048
名称 ID 标签 描述 类型 访问 分类