Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
pressure_output_transfer_function | 1391 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Enum | 32 |
module_fill_fluid | 139E | Fill fluid | Sensor Fill Fluid- Fluid material in the module | R/W | Enum | 2048 |
flange_type | 139A | Process Conn type | Flange Type- Hardware, adjacent to the sensor, that physically connects the process to the sensor | R/W | Enum | 2048 |
number_of_remote_seals | 139F | Num of RS | Number of Remote Seals- Physical quantity of the seals for the remote seal that is installed | R/W | Enum | 2048 |
remote_seal_type | 139D | RS type | Remote Seal Type- Type of device that is capable of detecting and passing on the process pressure on to the module. This is only unambiguous if 1 remote seal is installed. | R/W | Enum | 2048 |
analog_output_value | 1779 | AO | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes. Analog Output- Measurable physical output which changes with respect to time, without user intervention. | R/W | Float | 66 |
analog_output_alarm_select | 177A | AO alm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. Analog Output- Measurable physical output which changes with respect to time, without user intervention. | R | Enum | 1026 |
module_type_code | 177B | Module type | Measurement Type- Type of measurement application this Field Device is intended to be used with | R/W | Enum | 2048 |
sensor_a_lower_sensor_trim_point | 1774 | P LTP | Lower Sensor Trim Point- Applied process pressure at which the last low sensor trim was performed. Pressure Sensor- Pressure hardware that measures pressure with respect to a reference pressure. | R | Float | 8 |
sensor_a_upper_sensor_trim_point | 1776 | P UTP | Upper Sensor Trim Point- Applied process pressure at which the last upper sensor trim was performed. Pressure Sensor- Pressure hardware that measures pressure with respect to a reference pressure. | R | Float | 8 |