Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
physical_signaling_code | 00AB | Physicl signl code | Physical Signaling Code- The Physical Signaling Code describes the type of Physical Layer that has been implemented in the hardware that is responsible for the HART Communication port | R | Enum | 2048 |
device_flags | 00A0 | Dev flags | Field Device Flags- Describes special features of the Field Device that affect the Data Link Layer | R | BitEnum | 128 |
device_id | 00A1 | Dev id | Field Device Identification- Uniquely identifies the Field Device when combined with the Manufacturer Identification and Device Type. Therefore, this variable cannot be modified by the Host user. | R | Unsigned | 128 |
polling_address | 00A2 | Poll addr | Polling Address- Address used by the Host to identify a Field Device, and changeable by the User to control: the Multidrop Mode for Analog Output 1), and the Analog Output Fixed Mode of Analog Output 1) | W | Unsigned | 128 |
tag | 00A3 | Tag | Tag- Text that is associated with the Field Device installation. This text can be used by the user in any way. A recommended use is as a unique label to a plant that correlates to a Field Device label: a plant drawing, or on a Control System. This variable is also used as a type of data link layer address handle. | R/W | PackedAscii | 2048 |
message | 00A4 | Message | Message- Text that is associated with the Field Device. This text can be used by the user in any way. There is no recommended use. | R/W | PackedAscii | 2048 |
descriptor | 00A5 | Descriptor | Descriptor- Text that is associated with the Field Device. This text can be used by the user in any way. There is no specific recommended use. | R/W | PackedAscii | 2048 |
date | 00A6 | Date | Date- Gregorian calendar date that is stored in the Field Device. This date can be used by the user in any way. There is no specific recommended use. | R/W | HartDate | 2048 |
write_protect | 00A7 | Write protect | Write Protect Mode- Indicates whether variables can be written to the Field Device, or whether commands that cause actions, to be performed in the Field Device, can or cannot occur. Depending on the Field Device, this is a mode that is controllable by the user, either via the Field Device hardware or the HART Protocol. | R | Enum | 2048 |
private_label_distributor | 00A8 | Distributor | Private Label Distributor- References the company that is responsible for the distribution of this Field Device to customers | R | Enum | 2048 |
final_assembly_number | 00A9 | Final asmbly num | Final Assembly Number- Number that is used for identification purposes, and is associated with the overall Field Device. | R/W | Unsigned | 2048 |
xmtr_specific_status_0 | 0FB5 | Status group 1 | Field Device Specific Status Byte 1- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
xmtr_specific_status_1 | 0FB6 | Status group 2 | Field Device Specific Status Byte 2- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
burst_command_number | 0FFD | Burst option | Burst Option- Selects the variable(s) that will be Bursted if Burst Mode is enabled. | W | Enum | 128 |
burst_mode_select | 0FFF | Burst mode | Burst Mode Select- Selects the mode for the Burst Mode functionality. If Burst is enabled the Field Device will generate HART messages on the Link without individual requests from the Host. | W | Enum | 128 |
pressure_units | 138D | Unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Enum | 8 |
pressure_value | 138E | Pres | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 10 |
pressure_percent_range | 138F | % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 34 |
pressure_upper_range_limit | 1393 | USL | Upper Sensor Limit Value- Defines the maximum useable value for the Upper Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 8 |
pressure_lower_range_limit | 1394 | LSL | Lower Sensor Limit Value- Defines the minimum useable value for the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 8 |
pressure_minimum_span | 1390 | Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. Pressure- Pressure of the process measured with respect to a reference pressure. | R | Float | 8 |
pressure_output_transfer_function | 1391 | Transfer function | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Enum | 32 |
pressure_upper_range_value | 1396 | URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 32 |
pressure_lower_range_value | 1397 | LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 32 |
pressure_damping_value | 1398 | Damping | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. Pressure- Pressure of the process measured with respect to a reference pressure. | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |