名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |
---|---|---|---|---|---|---|
pst_sttl_alarm_enable | 406A | PST Slw Trvl Tm: | When enabled, the DEPIC2 will signal this failure alarm when the Maintenance PST fails due to exceeding a Slow Travel Time Limit to reach the Travel-Limit of the Baseline PST as determined by the PST Travel Time Hysteresis % (configuration). | 读/写 | 枚举 | 2050 |
test_invpstn_alarm_enbl | 406B | PST/SOVT Inv Pstn: | When enabled, the DEPIC2 will signal this failure alarm when the PST fails due to the valve being in an invalid position to perform a PST/SOVT. | 读/写 | 枚举 | 2050 |
bit7_alarm_enable | 406C | Reserved Bit7: | . | 读/写 | 枚举 | 2050 |
bit6_alarm_enable | 406D | Reserved Bit6: | . | 读/写 | 枚举 | 2050 |
bit5_alarm_enable | 406E | Reserved Bit5: | . | 读/写 | 枚举 | 2050 |
bit4_alarm_enable | 406F | Reserved Bit4: | . | 读/写 | 枚举 | 2050 |
bit3_alarm_enable | 4070 | Reserved Bit3: | . | 读/写 | 枚举 | 2050 |
pst_exceed_trvl_lim_enable | 4071 | XTrvl Lim Alarm: | When enabled, the DEPIC2 will signal this failure alarm when it has detected the PST has exceeded the designated Travel limit. Possible cause may be the solenoid is becoming sluggish in response to voltage. | 读/写 | 枚举 | 2050 |
test_invld_psi_alarm_enable | 4072 | Invld Press Alarm: | When enabled, the DEPIC2 will signal this failure alarm when it has detected the supply pressure is too low to safely perform a PST/SOVT. | 读/写 | 枚举 | 2050 |
psi_sensor_fail_alarm_enbl | 4073 | PSI Snsr Fail Alarm: | When enabled, the DEPIC2 will signal this failure alarm when it has detected a pressure sensor failure during SOVT. | 读/写 | 枚举 | 2050 |
名称 | ID | 标签 | 描述 | 类型 | 访问 | 分类 |