Loading…
Name ID Label Description Type Access Class
valve_type 4042 Rotary/Linear Valve: DEPIC2 can work with linear and rotary valves. R/W Enum 2050
usr_passwrd_enable 4043 User Pswrd Enable: User Password can be Enabled or Disabled. If Enabled, the user can optionally change the password from the default value. R/W Enum 2050
auto_sovt_enable 4044 Auto SOVT Enable: Automatic SOVT can be Enabled and Disabled. R/W Enum 2050
signature_enable 4045 Signature Enable: Enable or Disable collection of Valve Position and Pressure Profiling Signatures (Full Stroke Baseline/Maintenance/PST). R/W Enum 2050
pressure2_enable 4046 Pressure2 Sensor: Enable or Disable Pressure 2 Sensor (P2). If P2 enabled, it may be used to monitor the second chamber of an actuator or to monitor Supply Pressure during Signature collection. R/W Enum 2050
fail_mode 4047 Fail Mode: This setting defines the valve fail-safe position as Fail-Closed or Fail-Open when the solenoid is de-energized such as during ESD, generally used for Spring-Return Actuators. R/W Enum 2050
auto_pst_enable 4048 Auto PST Enable: Automatic PST can be Enabled and Disabled. R/W Enum 2050
pst_enable 4049 PST/SOVT Enable: Enable or Disable PST/SOVT functions. R/W Enum 2050
esd_enable 404A ESD Enable: Enable or Disable ESD monitoring. R/W Enum 2050
user_password 404B User Password The User Password may be changed here if desired, up to 6 characters in length. R/W Password 2050