Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
output_analog_value | 400A | Output I | Refers to the actual valve position in terms of current in mA. | R | Float | 66 |
damping_val | 400B | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R | Float | 8 |
input_upper_value | 400C | FS In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | R | Float | 32 |
input_lower_value | 400D | Zero In | Refers to the input current to move the valve to full open / close position in normal / reverse operation. | R | Float | 32 |
output_upper_value | 400E | FS Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | R | Float | 32 |
output_lower_value | 400F | Zero Out | Refers to the output current when the valve is at full open / close position in normal / reverse operation. | R | Float | 32 |
sensor_serial_number | 4010 | Sensor Serial | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R | Unsigned | 32 |
min_sensor_span | 4011 | Min_Sensor_Span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 32 |
flow_type | 4016 | Flow Type | The DEPIC supports Linear, Quick Opening, and Equal Percentage flow types. | R/W | Enum | 32 |
cal_busy | 4017 | CAL BUSY | Busy reading limits. | R/W | Enum | 1025 |
Name | ID | Label | Description | Type | Access | Class |