Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
sensor_value | 4000 | PV | Field Device Variable Value- Digital value that changes magnitude with respect to time with no user intervention | R | Float | 10 |
sensor_unit | 4001 | PV Snsr unit | Field Device Variable Unit- Engineering unit to be displayed with the Digital Value representation, Minimum Span, Upper Range Value, Lower Range Value, Lower Sensor Limit, and Upper Sensor Limit | R/W | Enum | 8 |
sensor_usl | 4003 | PV USL | Upper Sensor Limit Value- Defines the maximum usable value for the Upper Range Value. | R | Float | 8 |
sensor_lsl | 4004 | PV LSL | Lower Sensor Limit Value- Defines the minimum usable value for the Lower Range Value. | R | Float | 8 |
sensor_min_span | 4005 | PV Min span | Minimum Span Value- Defines the smallest allowable difference between the Upper Range Value and the Lower Range Value. | R | Float | 8 |
input_damping_value | 4006 | PV Damp | Damping Value- Damping time constant applied to both the Digital Value representation and Analog Value of the respective Analog Output. The units of this variable are always in seconds. | R/W | Float | 8 |
loop_current | 4007 | AO1 | Analog Output Value- Value that tracks the Digital Value representation, under normal operating modes | R/W | Float | 66 |
alarm_code | 4008 | AO Alrm typ | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R | Enum | 64 |
input_percent_range | 4009 | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
tf_code | 400A | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R | Enum | 32 |
output_urv | 400B | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
output_lrv | 400C | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
sensor_serial_nr | 400D | PV Snsr s/n | Sensor Serial Number- Uniquely identifies the sensor from which the Digital Value representation or Field Device variable is primarily derived. | R/W | Unsigned | 2048 |
el_temperature_value | 4011 | Elect temp | Electronics Temperature- Temperature of the electronics that is responsible for the process measurements, and the HART communications | R | Float | 10 |
temperature_unit | 4012 | Temp unit | Temperature unit of el. and cjc temperature | R | Enum | 8 |
cjc_temperature_value | 4013 | CJC temp | Thermocouple cold junction temperature | R/W | Float | 10 |
sensor_type | 4014 | Snsr typ | Sensor Type- Kind of sensor(s) connected at this time | R/W | Enum | 8 |
sensor_type_local | 401A | Snsr typ | Sensor Type- Kind of sensor(s) connected at this time | R/W | Enum | 4096 |
sensor_mode | 4002 | Linearization mode | The linearisation mode of the PV | R/W | Enum | 8 |
sensor_wires | 401B | Snsr conectn | Sensor Connection- Technique used to connect the sensor to the Field Device | R/W | Enum | 8 |
input_offset_value | 401C | Input Temp.offset | This input temperature offset value will be added to the measured input temperature value (limits: -10..+10 Kelvin). | R/W | Float | 8 |
wid2L_offset_value | 401D | 2W offset | 2 wire resistance offset | R/W | Float | 8 |
Ptx_x_value | 406F | Ptx 0°C resistance | Pt10..1000 0°C resistance value | R/W | Unsigned | 8 |
cjc_mode | 4015 | Cjc mode | The thermocouple cold junction compensation mode. | R/W | Enum | 8 |
cjc_fix_value | 4022 | Cjc fixval | Cjc fixed value (used in the cjc mode 'fixed') | R/W | Float | 8 |
Name | ID | Label | Description | Type | Access | Class |