Loading…
Loading…
Name | ID | Label | Description | Type | Access | Class |
---|---|---|---|---|---|---|
loopCurrent | 00ED | Loop current | Loop Current- Loop current value as perceived by the device. | R/W | Float | 66 |
loop_alarm_code | 00EC | Alarm Type | Analog Output Alarm Type- Defines how the Analog Output will respond when the Field Device detects that the Analog Output may not be tracking the associated Field Device Variable. NOTE- The Digital Value representation may not be determinate. | R/W | Enum | 64 |
loop_flags | 00E7 | Channel flags | Analog Channel Flags- Defines the characteristics of the Analog Channel | R | BitEnum | 64 |
percentRange | 00E9 | PV % rnge | Percent of Range- Variable that tracks the Digital Value representation with respect to the range defined by the Lower Range Value and Upper Range Value, for normal operating modes. The units of this variable are always in percent. | R | Float | 34 |
transfer_function | 1F84 | Xfer fnctn | Transfer Function- Defines the transformation function that will be applied from the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function does not affect the Digital Value representation. | R/W | Enum | 32 |
upperRange_value | 00EA | PV URV | Upper Range Value- Defines the operational endpoint from which the Analog Value, and the 100% point of the Percent Range are derived. In addition, the Upper Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
lowerRange_value | 00EB | PV LRV | Lower Range Value- Defines the operational endpoint from which the Analog Value, and the 0% point of the Percent Range are derived. In addition, the Lower Range Value defines an operational endpoint which the alarms associated with the Analog Value, and the alarms associated with the Digital Value representation are derived. | R/W | Float | 32 |
device_variable_code | 1047 | Device Variable | Index into Dynamic Variables Array- An index that identifies a Field Device Variable that is dynamic with respect to time, with no user input | R/W | Index | 4096 |
device_specific_status_0 | 102B | Status Group 0 | Field Device Specific Status Byte 1- Data that has Field Device status information relating to: failures / warnings / status of process's. | R | BitEnum | 2051 |
Name | ID | Label | Description | Type | Access | Class |